Electrical Reference
DK58113 Developer Kit User Manual
51
3
Minimum Current Read Time
2,000 nSec
To ensure sufficient minimum current read time with
BLDC motors this parameter must be set to this value.
Leg Current Conversion
.733 mA/count
This value should be entered so that the leg current can
be traced and displayed correctly in amps.
Brushless DC Motor: Foldback
Continuous Current Limit
5.0 A
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
Brushless DC Motor: Foldback Total
Energy Limit
125 A
2
sec
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
DC Brush Motor: Foldback
Continuous DC Current Limit
5.0 A
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
DC Brush Motor: Foldback Total
Energy Limit
125 A
2
sec
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
Step Motor: Foldback Continuous
Current Limit
5.0 A
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
Step Motor: Foldback Maximum
Energy Limit
125 A
2
sec
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
Temperature Limit
75.0 C
This value should be entered to ensure the on-card
amplifier does not operate above the maximum safe
current output.
Bus Current Supply Conversion
.505 mA/count
This value should be entered so that the DC bus current
supply can be traced and displayed correctly in amps.
Bus Current Supply Limit
20.0 A
This value should be entered to ensure safe operation of
the DK58113.
Bus Current Return Limit
20.0 A
This value should be entered to ensure safe operation of
the DK58113.
Bus Voltage Display
.966 mV/count
This value should be entered so that the DC bus voltage
can be traced and displayed correctly in volts.
Undervoltage Limit
10.0 V
This value should be entered to ensure safe operation of
the DK58113.
Overvoltage Limit
60.0 V
This value should be entered to ensure safe operation of
the DK58113.
Parameter
Value & Units
Comments