Drive & DC Bus Safety
Juno Step Motor Control IC User Guide
83
13
13.3 Settable Parameters
For more information on Juno host commands refer to the
Juno Velocity & Torque Control IC Programming Reference
.
13.4 Signal Processing
The following table shows the signals that are used in connection with the drive and DC Bus safety features.
When using a thermistor the
Temperature
input signal should be filtered to minimize noise. The
Temperature
input is
sampled at a rate of 1kHz or higher, and therefore a low pass filter with a rolloff at 500
Hz or lower is recommended.
Parameter
Host Command
Mnemonic
Range & Description
Overtemperature
threshold
SetDriveFaultParameter
Two parameter command. The first must be 4, the sec-
ond has a range of -32,768 to 32,767 and specifies the
thermistor sense (voltage increasing or decreasing) via the
sign of the specified value and the threshold limit via the
magnitude of the specified value. A value of 32,767 dis-
ables this feature.
Overtemperature hys-
teresis
SetDriveFaultParameter
Two parameter command. The first must be 5, the sec-
ond has a range of 0 to 6,400 and specifies the hysteresis.
DC bus overcurrent
supply threshold
SetDriveFaultParameter
Two parameter command. The first must be 10, the sec-
ond has a range of 0 to 65,534 and specifies the DC bus
supply overcurrent threshold. A value of 65,534 disables
this feature.
DC bus overcurrent
return threshold
SetDriveFaultParameter
Two parameter command. The first must be 11, the sec-
ond has a range of 0 to 65,534 and specifies the DC bus
return overcurrent threshold. A value of 65,534 disables
this feature.
DC bus overvoltage
threshold
SetDriveFaultParameter
Two parameter command. The first must be 0, the sec-
ond has a range of 0 to 65,535 and specifies the DC bus
overvoltage threshold. A value of 65,535 disables this fea-
ture.
DC bus undervoltage
threshold
SetDriveFaultParameter
Two parameter command. The first must be 1, the sec-
ond has a range of 0 to 65,535 and specifies the DC bus
undervoltage threshold. A value of 0 disables this feature.
Current foldback con-
tinuous current limit
SetCurrentFoldback
Two parameter command. The first must be 0, the sec-
ond has a range of 0 to 32,768 and specifies the foldback
continuous current limit A value of 32,768 disables this
feature.
Current foldback
energy limit
SetCurrentFoldback
Two parameter command. The first must be 1, the sec-
ond has a range of 0 to 32,768 and specifies the foldback
energy limit A value of 32,768 disables this feature.
Pin Name
64-Pin TQFP
Pin#
56-Pin VQFN
Pin#
Description
Temperature
9
7
Measured Temperature
BusVoltage
13
11
Measured Bus voltage
BusCurrentSupply
10
8
Measured DC Bus Current