INSTALLATION INSTRUCTIONS

INSTALLATION DIAGRAM

  

•  Above figure is only a simple presentation of the unit, it may  

not match the external appearance of the unit you purchased.

•  Installation must be performed in accordance with the national 

wiring standards by authorized personnel only.

Distance 
from ceiling 
should be over 
7.9in/200mm

Distance 
from the wall 
should be over 
2in/50mm

Distance from the obstacle  
should be over 20in/500mm

Air intake 
distance 
from the wall 
should be over 
10in/250mm

Air intake 
distance 
from the wall 
should be over 
10in/250mm

Air out

let distance fr

om t

he wall 

should be o

ver 20in/500mm

Over 
10in/250mm

Distance from 
wall should be 
over 2in/50mm

Distance from the 
obstacle should be 
over 9.8ft/3m

Distance from floor  
should be over 8ft/2.4m

BEST INSTALLATION PRACTICES

• 

A SURGE PROTECTOR IS HIGHLY 

RECOMMENDED TO PREVENT DAMAGE 

TO THE EQUIPMENT DUE  

TO ELECTRICAL FAILURE

• 

VERIFY THE WALL IS PLUMB. AN 

UNPLUMB WALL WILL CAUSE BLOWER 

WHEEL TO BE UNBALANCED

• 

NEVER USE WIRE NUTS ON THE 

COMMUNICATION CABLE. CRIMP  

TYPE CONNECTORS ARE ALLOWED

• 

WIRING BETWEEN INDOOR AND 

OUTDOOR UNITS IS POLARITY 

SENSITIVE.(EXAMPLE: IF INDOOR UNIT 

IS WIRED BLACK ON 1, RED ON 2 AND 

WHITE ON 3, IT NEEDS TO BE THE SAME 

ON THE OUTDOOR UNIT)

• 

A MINIMUM OF 16 AWG, STRANDED 4 WIRE, 

FT4 RATED, 300 VOLTS WIRE IS NEEDED

• 

BE SURE TO MAKE ALL FLARES WITH AN 

APPROVED 410A FLARING TOOL

• 

A MINIMUM OF 10 FT. LINE SET IS REQUIRED

• 

ON SINGLE-ZONE: IF LINE SET IS LONGER 

THAN 25 FT. YOU WILL NEED TO WEIGH 

IN THE RECOMMENDED AMOUNT OF 

REFRIGERANT. SEE INSTALLATION AND 

OPERATION MANUAL

• 

ON MULTI-ZONE: THERE IS ENOUGH 

REFRIGERANT FOR 25 FT. OF LINE SET 

PER ZONE (EXAMPLE: 3-ZONE = 75 FT.  

OF LINE SET)

• 

USE OIL OR NYLOG ON THE THREADS 

AND TORQUE NUTS TO THE PROPER 

SPECIFIED VALUE. SEE INSTALLATION 

AND OPERATION MANUAL

• 

ALWAYS USE THE SUCTION/GAS LINE TO 

ADD OR REMOVE REFRIGERANT

• 

TEST FOR LEAKS BY PRESSURIZING THE 

SYSTEM WITH MINIMUM 500 POUNDS 

OF NITROGEN AND HOLD FOR AT LEAST 

60 MINUTES

• 

EVACUATE THE SYSTEM DOWN TO A 

MINIMUM OF 500 MICRONS AND HOLD 

FOR 30 MINUTES

INSTALLATION INSTRUCTIONS

(Continued)

BOX PART BREAKDOWN

•  Screw Driver
•  Standard Wrench
•  Hex Keys or Allen Wrenches
•  Adjustable/Crescent Wrench
•  Drill
•  Drill Bits
•  Torque wrench
•  Vacuum Pump
•  Manifold and Gauges

SUGGESTED TOOLS

In order to install your air-conditioner more conveniently and safely, you might use those special tools  

listed below.

•  Level
•  Clamp on Amp Meter
•  Safety Glasses
•  Work Gloves
•  Refrigerant Scale
•  Pipe Cutter
•  R410A Flaring Tool
•  Micron Gauge
•  Hole Saw

OUTDOOR UNIT BOX

(1) Outdoor Condenser

(4) Anti-Vibration Pads

INDOOR UNIT BOX

(1) Indoor Evaporator

(1) Mounting Bracket

(1) Drain Joint 

(1) Drain Joint  

Rubber Seal

(1) Remote Control

(2) AAA Batteries for 

Remote Control

INDOOR UNIT BOX

                            

(Continued)

(1) Remote Control  

Wall Bracket

(1) Bag of Wall Anchors 

& Screws

(2) Flare Nuts

Summary of Contents for 3PAMSH30B-SZO

Page 1: ...SINGLE ZONE DUCTLESS MINI SPLIT SYSTEM OWNER S MANUAL MODELS 3PAMSH30B SZW 3PAMSH30B SZO 3PAMSH36B SZW 3PAMSH36B SZO ...

Page 2: ...remote electric power supplies before servicing The best length of the connecting pipe between the indoor unit and outdoor unit is less than 24 6ft 7 5 meters It will affect the efficiency of the air conditioner if the distance longer than that length This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and ...

Page 3: ...NCE This marking indicates that this product should not be disposed with other household wastes throughout the North America To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where th...

Page 4: ...EEDED BE SURE TO MAKE ALL FLARES WITH AN APPROVED 410A FLARING TOOL A MINIMUM OF 10 FT LINE SET IS REQUIRED ON SINGLE ZONE IF LINE SET IS LONGER THAN 25 FT YOU WILL NEED TO WEIGH IN THE RECOMMENDED AMOUNT OF REFRIGERANT SEE INSTALLATION AND OPERATION MANUAL ON MULTI ZONE THERE IS ENOUGH REFRIGERANT FOR 25 FT OF LINE SET PER ZONE EXAMPLE 3 ZONE 75 FT OF LINE SET USE OIL OR NYLOG ON THE THREADS AND ...

Page 5: ...more than 24 6ft 7 5m the refrigerant should be charged additionally according to below table model required amount of additional refrigerant oz ft 9K 18K 0 22 24K 0 32 30K 36K 0 43 Indoor unit Outdoor unit Indoor unit is higher than outdoor unit Pipe length is 65 4ft 20m Max Height should be less than 32 8ft 10m Indoor unit Outdoor unit Outdoor unit is higher than indoor unit Pipe length is 65 4f...

Page 6: ...mum of six screws evenly spaced to properly support indoor unit weight NOTE The shape of your mounting plate may be different from the one above but the installation method is similar NOTE As the above figure shown the six holes matched with tapping screw on the mounting plate must be used to fix the mounting plate the others are prepared MOUNTING PLATE INSTRUCTIONS ON WOODEN WALL INSTALLATION INS...

Page 7: ...he drain hose Then connect the power cords After connecting wrap the piping cords and drain hose together with thermal insulation materials NOTE Dimensions are in inch unless otherwise stated in the table INSTALLATION INSTRUCTIONS Continued PIPING JOINTS THERMAL INSULATION Wrap the piping joints with thermal insulation materials and then wrap with a vinyl tape PIPING THERMAL INSULATION a Place the...

Page 8: ...g floor If installed on the wall or roof make sure to fix the supporter well to prevent it from shaking due to serious vibration or strong wind Service Valve Cover PIPE DIAMETER NUT SIZE TIGHTENING TORQUE INCH MM INCH MM FT LBS 1 4 6 35 1 4 17 11 to 15 3 8 9 5 3 8 22 22 to 26 1 2 12 7 1 2 25 37 to 41 5 8 15 9 5 8 29 44 to 48 3 4 19 3 4 32 52 to 55 NOTE Over tightening may damage flare connections ...

Page 9: ...ressor and outdoor fan turn on in cooling mode Push the mode button to HEAT and adjust the room setting to 85 F 30 C deg wait up to 3 minutes for compressor time guard Does compressor and outdoor fan turn on in heat mode EVACUATION INSTRUCTIONS Before using a manifold gauge and a vacuum pump read their operation manuals to make sure you know how to use them properly Using a valve core removal tool...

Page 10: ...ive device may trip and stop the appliance For some models can keep cooling at 5 F 15 C outdoor ambient via unique design Normally optimum cooling performance will be achieved above 70 F 21 C Please consult the merchant to get more information For some models can keep heating at 5 F 15 C outdoor ambient some models heat at 4 F 20 C outdoor ambient even heat at lower outdoor ambient The temperature...

Page 11: ...ble for a few minutes when you come home the unit will have the room back to your desired temperature in no time DON T FORGET THE FAN The fan is much like a car The faster it runs the more energy is consumed Sometimes we need the car to go fast but slow is good enough most of the time Try saving money by using the comfortable quiet low fan speed as much as possible TROUBLESHOOTING PROBLEM SOLUTION...

Page 12: ...ours of usage as reminder to clean the filter After filter cleaning press the filter reset button located on the indoor unit behind the front panel in order to reset the display optional Running indicator It lights up when the AC is running It flashes during defrosting Timer indicator It lights up during set time Sleep indicator It lights up in sleep mode To let the AC run or stop by pressing the ...

Page 13: ...844 4PA AIRE 844 472 2473 support perfectaire us CANADA SUPPORT 877 997 2473 supportcanada perfectaire us www perfectaire us 5401 Dansher Road Countryside IL 60525 Printed in China 1121_M868 ...

Reviews: