background image

Step 5: Connect drain hose

 

By default, the drain hose is attached to the left-

hand side of unit (when you’re facing the back 

of the unit). However, it can also be attached to 

the right-hand side. 
1.  To ensure proper drainage, attach the drain 

hose on the same side that your refrigerant

piping exits the unit.

2.  Attach drain hose extension (purchased

separately) to the end of drain hose.

3.  Wrap the connection point firmly with 

Teflon tape or clamp to ensure a good seal  

 

and to prevent leaks.

4.  For the portion of the drain hose that will 

remain indoors, wrap it with foam pipe 

insulation to prevent condensation.

5.  Remove the air filter and pour a small amount 

of water into the drain pan to make sure that 

water flows from the unit smoothly.

 NOTE ON DRAIN HOSE

 

 PLACEMENT 

Make sure to arrange the drain hose 

according to Fig. 3.5.

  DO NOT

 

kink the drain hose.

 

  DO NOT

 

create a water trap.

   DO NOT

 

put the end of drain hose   

in water or a container that will 

 

PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug 

the unused drain hole with the rubber plug 

provided.

CORRECT 

NOT CORRECT

NOT CORRECT

NOT CORRECT

Fig. 3.5

Fig. 3.6

Fig. 3.7

Fig. 3.8

Page 12

Indoor Unit

Installation

collect water.

Make sure there are no 

kinks or dents in the 

drain hose to ensure 

proper drainage.

Kinks or dents in the 

drain hose will create 

water traps.

Kinks or dents in the 

drain hose will create 

water traps.

Do not place the end of 

the drain hose in 

water or in containers 

that collect water. 

This will prevent 

proper drainage.

Summary of Contents for 2PAMSH09-MZW

Page 1: ...RIES HEAT PUMP INSTALLATION MANUAL MULTI ZONE Before using your air conditioner please read this manual carefully and keep it for future reference along with your receipt FOR MODELS 2PAMSH09 MZW 2PAMS...

Page 2: ......

Page 3: ...14 4 7 Wrap piping and cables 15 4 8 Mount indoor unit 15 Outdoor Unit Installation 17 5 1 Select installation location 17 5 2 Install drain joint 18 5 3 Anchor outdoor unit 19 5 4 Connect signal and...

Page 4: ...tallation can cause water leakage electrical shock or fire 2 Installation must be performed according to the installation instructions Improper installation can cause water leakage electrical shock or...

Page 5: ...ectric heater do not install the unit within 3 feet 1 meter of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas gas accum...

Page 6: ...AAA LR03 Air freshening lter Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation parts electrical shock and fire...

Page 7: ...user manual Connecting pipe assembly Liquid Side 6 35 1 4 in 9 52 3 8 in 9 52 3 8 in 12 7 1 2 in 16 5 8 in Gas Side User manual 1 1 1 NAME ILLUSTRATION QUANTITY These parts must be purchased separate...

Page 8: ...on Page 8 Attach Mounting Plate Page 9 Drill Wall Hole Page 9 Installation Overview Determine Wall Hole Position Page 8 1 2 3 4 4 75 in 12 cm 90 55 in 2 3 m 4 75 in 12 cm 5 9 in 15 cm Page 5 2 Install...

Page 9: ...Mount Indoor Unit Page 15 STEP8 Wrap Piping and Cable Page 15 L N S Connect Piping Page 22 Connect Wiring Page 14 Prepare Drain Hose Page 11 5 6 7 8 9 Page 6 Installation Overview...

Page 10: ...purchased may be slightly different Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Control Some Units Drainage Pipe Louver Remote Holder Functional Filter On Front...

Page 11: ...A location at least 40 in one meter away from all other electrical devices e g TV radio computer DO NOT install unit in the following locations Near any source of heat steam or combustible gas Near am...

Page 12: ...ng the screws directly into the clip anchors Step 3 Drill wall hole for connective piping You must drill a hole in the wall for refrigerant piping the drainage pipe and the signal cable that will conn...

Page 13: ...3mm Indoor unit outline 14 25 in 362mm Model E 49 55 in 1259mm Indoor unit outline 52mm 2 05in 15 3 in 389mm 13 05 in 332mm 10 1 in 257mm 2 05 in 52mm Wall Indoor Outdoor m m 7 5 0 2 0 3in MOUNTING P...

Page 14: ...ult to remove by hand Knock out Panel 3 Use scissors to cut down the length of the insulating sleeve to reveal about 6 in 15 cm of the refrigerant piping This serves two purposes To facilitate the Ref...

Page 15: ...t of water into the drain pan to make sure that water ows from the unit smoothly NOTE ON DRAIN HOSE PLACEMENT Make sure to arrange the drain hose according to Fig 3 5 DO NOT kink the drain hose DO NOT...

Page 16: ...0 of rated voltage Insufficient power supply can cause malfunction electrical shock or fire 5 If connecting power to fixed wiring install a surge protector and main power switch with a capacity of 1 5...

Page 17: ...T5A 250VAC etc 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of signal cable to reveal about 6 in 15 cm of the wires inside b Strip the insulation f...

Page 18: ...esive vinyl tape attach the drain hose to the underside of the frigerant pipes 3 Using insulation tape wrap the signal wire refrigerant pipes and drain hose tightly together Double check that all item...

Page 19: ...ns 4 Keep pipe connection point exposed to perform the leak test refer to Electrical Checks and Leak Checks section of this manual 5 After the leak test wrap the connection point with insulation tape...

Page 20: ...rate Noise from the unit will not disturb others Protected from prolonged periods of direct sunlight or rain Near an obstacle that will block air inlets and outlets Near a public street crowded areas...

Page 21: ...Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the dra...

Page 22: ...e the installation base of the unit according to the dimensions below Fig 4 5 WHEN DRILLING INTO CONCRETE EYE PROTECTION IS RECOMMENDED AT ALL TIMES Page 19 Outdoor Unit Installation inches millimeter...

Page 23: ...1 All wiring must comply with local and national electrical codes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diag...

Page 24: ...ith the labels on the terminal block and firmly screw the u lug 5 After checking to make sure every connection is secure loop the wires around to prevent rain water from flowing into the terminal 6 Us...

Page 25: ...and 24 000 98 5 ft 30 m 66 ft 20 m 24 000 and 36 000 164 ft 50 m 82 ft 25 m 36 000 and 60 000 213 ft 65 m 98 5 ft 30 m Connection Instructions Refrigerant Piping Step 1 Cut pipes When preparing refrig...

Page 26: ...e 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction because you cannot put them on or change their direction after fla...

Page 27: ...in 9 52mm 18 4 lb ft 2 500 N cm 19 18 lb ft 2 600 N cm 0 5 in 12 7mm 25 8 lb ft 3 500 N cm 26 55 lb ft 3 600 N cm 0 63 in 16mm 33 19 lb ft 4 500 N cm 34 67 lb ft 4 700 N cm DO NOT USE EXCESSIVE TORQU...

Page 28: ...ing a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE WRENCH TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut can snap off other par...

Page 29: ...o make sure that both high pressure and low pressure pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check...

Page 30: ...he service port 12 Using hexagonal wrench fully open both the high pressure and low pressure valves 13 Tighten valve caps on all three valves service port high pressure lo w pressure by hand You may t...

Page 31: ...electrician to nd and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are two different methods to check for gas leaks Soap and Water...

Page 32: ...on to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run for 5 minutes and perform the follow...

Page 33: ...ient temperature is below 63 F In this instance you can use the MANUAL CONTROL button to test the COOL function 1 Lift the front panel of the indoor unit and raise it until it clicks in place 2 The MA...

Page 34: ......

Page 35: ......

Page 36: ...formance data is subject to change without notice Printed in China 844 472 2473 www perfectaire us PA Manual_Gen2MZMSHighWallInstall 01182018 Distributed by C L L e r i A t c e f r e P 5401 Dansher Rd...

Reviews: