Operation and maintenance manual for the KSP Spark series boilers equipped with feeders. The producer reserves the right to introduce technical modifications.
4.5.2. Menu 02 “CLOCK SETTINGS”
This menu is used to set current hour and date. The card is
equipped with a lithium battery, which is responsible for main-
taining current data and hour after cutting off the power from
the boiler.
This MENU allows setting:
01 Weekday . . . . . . . . . . . . . . . . . . . . . . . .(Monday…Sunday)
02 Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .(0..23)
03 Minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .(0..59)
04 Days of the month . . . . . . . . . . . . . . . . . . . . . . . . . . . .(1..31)
05 Month of the year . . . . . . . . . . . . . . . . . . . . . . . . . . . . .(1..12)
06 Current year . . . . . . . . . . . . . . . . . . . . . . . . . . . .(2000.. 2099)
4.5.3. Menu 03 “OPERATION
PROGRAMMING”
Menu 03 gives an option to program weekly schedule for the
boiler, firing up and damping.
4.5.4. Menu 04 “LANGUAGE SELECTION”
This parameter is used to for language choice.
4.5.5. Menu 5 “SIREN MODE”
The parameter is responsible for activation/deactivation of
sound signals in case of alarm occurrence.
4.5.6. Menu 6 “PRELIMINARY LOADING”
Allows filling the feeder pipe during first firing up. The feeder is
started by pressing the arrow (1) button. The feeder is shutdown
with the switch on/off button (4) when the sound of a pellet
falling down to the box is heard.
4.5.7. Menu 7 “BOILER STATUS”
BOILER STATUS menu displays instantaneous equipment status
showing values from probes and boiler parameters.
4.5.8. Menu 08 “SERVICE SETTINGS”
Menu intended for a service technician, protected with a code.
4.5.9. Menu 09 “PELLET TYPE”
Parameter responsible for pellet feeding time. Change the value
in the range from -9 to 9 using arrows (1) and (2). Each unit
increases or decreases feeding time by 2.5%.
4.5.10. Menu 10 “CHIMNEY TYPE”
This parameter is responsible for exhaust fan power. Each unit
increases or decreases fan rpm by 2.5%.