45
check whether correct type of boiler/ burner has been selected.
See sec. 21.1
open fully fan baffle and/ or return flap
clean off ducts supplying air to the furnace
change Fuzzy Logic settings in: MENU
→
Service Settings
→
Boiler Settings
→
Burner Settings
→
Fuzzy Logic (accessible to
boiler manufacturers only)
When Fuzzy Logic mode is
active, combustion is too
intensive and the furnace
lowers into retort.
increase fuel feeding rate by higher setting of the parameter
Fuel correction in Fuzzy Logic mode. See sec. 7.7
check whether too intensive combustion occurs in SUPERVISION
mode. If YES - adjust this mode acc. sec. 11,
check whether too intensive combustion is caused by the setting
Cycle order OPERATION - see sec. 37,
if the regulator has the option of fuel type selection - make sure
the correct fuel type has been selected (see sec. 7.10),
check whether correct type of boiler has been selected. See sec.
21.1.
change Fuzzy Logic settings in: MENU
→
Service Settings
→
Boiler Settings
→
Burner Settings
→
Fuzzy Logic (accessible
only to boiler manufacturers only)
The
temperature
is
measured incorrectly
Check if there is a good thermal contact between the
temperature sensor and measured surface,
Check if sensor wire not goes too closely to network wire,
Check if sensor is connected to terminal,
Check if sensor is not broken
–
check with point 11.8
In
the
DHW=SUMMER
mode, the radiators are hot
and the boiler overheats.
increase the setting of the parameter:
HUW pump operation
extension time
to cool down the boiler. See sec. 39,
increase the setting of the parameter:
max. HUW temperature
to
enable excessive heat discharge to HUW container. See sec. 42,
Note: inform the users of high temperature of hot utility water!
the DHW pump is active
even if the DHW tank has
been filled.
Set the parameter
HUW pump operation time extension = 0
,
sec.38
The
boiler
overheats
despite disabled airflow
the reason may be boiler defect or improper chimney design -
lack of protection against too excessive flue draught.
In hydraulic system with
mixing valve and servo -
mixer is closed
The reason may be response of return protection function - see
sec.37. If the return protection function is active, i.e. Return
Protection 4D = ON - check whether the sensor of water return
to the boiler is thermally isolated from environment and apply
thermal paste to improve thermal contact between the sensor
and the pipe. Increase preset boiler temperature to have enough
power to heat return water. Check whether hydraulic system is
properly made - upon valve closing, return temperature should
increase to above the value set in the parameter "Min.return
temperature
”
+
“
Return temp. hyst
”.
the reason may be filling HUW container at active HUW priority.
Wait until completed HUW container filling or deactivate HUW
priority,
the reason may be active SUMMER function,
In hydraulic system with
mixing valve and servo
–
preset
boiler/mixer
temperature is not stable -
servo performs unnecessary
movements
Adjust the parameters:
Mixer input dead zone
or
Proportional
range
or
Integr. time const.
Summary of Contents for KSP Duo
Page 1: ...Operation and maintenance manual for the boilers with feeder KSP Duo...
Page 22: ......
Page 23: ......
Page 26: ......
Page 31: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Page 41: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Page 47: ...23...
Page 71: ...47...
Page 82: ......
Page 84: ...wer 13 12 2017 r...