Guidelines for proper settings
of heating curve :
- underfloor heating
0.2 -0.6
- radiator heating
1.0 - 1.6
- boiler
1.8 - 4
For choosing proper heating curve:
If by falling outer temperature room
temperature is increasing, then value
of chosen heating curve is too big,
If by decreasing outer temperature,
room temperature is also decreasing,
then value of chosen heating curve is
too low,
If
by
frosty
weather
room
temperature is appropriate and in
warmer time is too low
–
it is
recommended to increase parameter
heating curve parallel shift
and then
choose lower heating curve.
If
by
frosty
weather
room
temperature is too low and in warmer
time too high
–
it is recommended to
reduce
parameter heating curve
parallel shift
and choose higher
heating curve.
Buildings which are poorly isolated require
setting heating curve with higher values, and
for better isolated buildings heating curve
will have a lower value.
Preset temperature, counted according to
heating curve can be decreased or increased
by controller when it goes beyond scope of
limits of temperatures for given cycle.
7.16
Description of night time decrease
settings
The regulator offers possibility to select the
time intervals for boiler, heating circuits,
HUW container and HUW circulating pump, at
which lower preset temperature may be set
e.g. for a night time or when the user is not
at home (e.g. he/she left for work). This
feature enables automatic reduction of preset
temperature, which improves heat comfort
and reduces fuel consumption. It is indicated
with a sign
. Select temperature
reduction and beginning and end of
respective time interval.
Time intervals
7.17
Control of HUW circulating pump
Settings of HUW circulation are available in:
MENU Circulating Pump
HUW circulating pump enables quick delivery
of hot utility water to rooms located far away
from HUW container without a need to drain
off the water. Time-based control settings of
circulating pump are analogical to the
settings of night time decrease. In the
defined time intervals designated as
circulating pump will start and remain in
operation for the period of time set in
Circulating Pump Operation Time
, then will
stop and remain out of operation for the
period of time set in
Circulating pump
standstill time
. The circulating pump does
not operate in the time intervals designated
as
To keep the pump in continuous
operation, set all time intervals within the
whole day (24 hours) at
and the
parameter
Circulating pump standstill time
= 0.
Switch on the operation of circulating pump
using the parameter:
HUW Circulation
Support
in MENU
Pump Service
Settings
.
7.18
Grate
Summary of Contents for KSP Duo
Page 1: ...Operation and maintenance manual for the boilers with feeder KSP Duo...
Page 22: ......
Page 23: ......
Page 26: ......
Page 31: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Page 41: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Page 47: ...23...
Page 71: ...47...
Page 82: ......
Page 84: ...wer 13 12 2017 r...