![Pereko AGRO Multi 12 Operation And Maintenance Manual Download Page 57](http://html1.mh-extra.com/html/pereko/agro-multi-12/agro-multi-12_operation-and-maintenance-manual_1528315057.webp)
21
Diagram with two additional mixer circuits upon connection of additional Module B
5
,
where:
1
–
boiler, 2
–
ecoMAXX regulator
–
module A, 3
–
ecoMAXX regulator
–
control panel, 4
–
fan, 5
–
feeder
temperature sensor, 6 - gear-motor, 7
–
boiler temperature sensor, 8
–
HUW temperature sensor, 9 - mixer
1 temperature sensor, 10
–
temperature (weather) sensor, 11
–
boiler pump, 12
–
HUW circuit pump, 13
–
mixer 1 circuit pump 14
–
mixer 1 servo, 15
–
HUW container, 16
–
room thermostat or ecoSTER200, 17
–
extension module B, 18
–
mixer 2 servo 19
–
mixer 3 servo, 20
–
mixer 2 pump, 21
–
mixer 3 pump, 22
–
mixer 2 room thermostat, 23
–
mixer 3 room thermostat, 24
–
mixer 2 temperature sensor, 25
–
mixer 3
temperature sensor, 26
–
autonomous thermostat to protect underfloor heating - max. temp. 55 C (it cuts
off power supply to the mixer pump once the maximum temperature has been exceeded; thermostat is not
included in the regulator supply), 27
–
return temperature sensor (recommended mounting location: bottom
section of boiler water jacket), 28
–
thermostatic 3-way valve (to protect boiler return), 29 - throttle
mushroom valve, 32
–
HUW circulating pump, P
–
electric relay, 38
–
hydraulic coupling, 39
–
room
temperature sensor CT7.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
1,3
Mixer support
ON CO
Service Settings Mixer Settings
Max. preset mixer temperature
75
Service Settings Mixer Settings
Heating curve. mixer
0.8
–
1.4
Service Settings Mixer Settings
Weather control mix.
ON
Menu Mixer Settings
2
Mixer support
Floor ON
Service Settings Mixer Settings
Max. preset mixer temperature
50 C
Service Settings Mixer Settings
Heating curve. mixer
0.2
–
0.6
Service Settings Mixer Settings
Weather control mix.
ON
Menu Mixer Settings
Circulation support
ON
Pump Service Settings
OPERATION mode: Return
Protection
OFF
Service Settings Boiler Settings Return Protection 4D
5
The presented hydraulic diagram does not replace central heating engineering design and may be used for information
purposes only.
Summary of Contents for AGRO Multi 12
Page 1: ...Operation and maintenance manual for the boilers with feeder AGRO Multi...
Page 22: ......
Page 23: ......
Page 34: ......
Page 36: ...wer 13 12 2017 r...
Page 38: ......
Page 43: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Page 53: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Page 59: ...23...
Page 83: ...47...
Page 86: ......
Page 114: ......
Page 115: ......