![Pereko AGRO Multi 12 Operation And Maintenance Manual Download Page 17](http://html1.mh-extra.com/html/pereko/agro-multi-12/agro-multi-12_operation-and-maintenance-manual_1528315017.webp)
17
Page
Operation and maintenance manual for the AGRO Multi series boilers with feeders. The producer reserves the right to introduce technical modifications.
5. BOILER OPERATION DISTURBANCES
–
BEFORE CALLING
THE SERVICE
The customer will bear the costs of travel and work of the sere technician in case of the unjusti
fi
ed calling of producer’s service. There-
fore, before you call the producer’s service please read the section concerning the most often occurring disturbances in boiler operation
and methods of dealing with them.
Symptom
Cause
Repair
Smoking outwards
insu
ffi
cient chimney draught
remove leaks in chimney,
fl
ue or boiler doors
insu
ffi
cient chimney height
lift chimney to height min. 1.5 m over roof ridge
too small chimney’s intersection
adjust damper of the
fl
ue, decrease blowing force
very low atmospheric pressure
use fan supporting chimney draught
contamination of chimney
fl
ue
clean ducts
Low thermal e
ffi
ciency of the boiler
combustion of low heat fuel
replace fuel with high heat fuel
no supply of air to the boiler-room
facilitate correct air supply through the window or
air supply duct
failure of forced draught fan or controller
re-set parameters in compliance with the user’s
manual or replace with a new one - in good working
contamination of gas passes in smoke tubes chamber
clean passes, adjust damper
Moistening and tar deposits inside the boiler
(symptoms similar to leak)
use of wood as a primary fuel in the heating process
use fuel recommended by the user’s manual
low temperature maintained in the boiler
use boiler having temp. min. 57°C
Leak
to be assessed by the producer
repair by PEREKO service
Too high chimney’s draught
—
adjust chimney draught with a damper in boiler
fl
ue
Fuel suspends in the container
Too moist fuel
Remove fuel from the container and dry it
Fuel does not evacuate from the container
ruptured protection of feeder’s split pin
remove item jamming the endless screw and insert
new split pin
Screw-conveyor feeder does not start
no supply
check supply
controller switched o
ff
check the main switch of the controller
switch on motor
check switch on motor
Summary of Contents for AGRO Multi 12
Page 1: ...Operation and maintenance manual for the boilers with feeder AGRO Multi...
Page 22: ......
Page 23: ......
Page 34: ......
Page 36: ...wer 13 12 2017 r...
Page 38: ......
Page 43: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Page 53: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Page 59: ...23...
Page 83: ...47...
Page 86: ......
Page 114: ......
Page 115: ......