-01 Electromechanical box tripod turnstile with two built-in readers 

 

A special signal “Ready” is generated in each of the above cases.  

 

15

 

 

6.11.2  In case of unauthorized access the “Ready” signal is formed as follows: 

at 8° arm rotation one of the optic sensors (Fig. 10) responds and the 

output contacts “Ready” and “Common” get broken (the beginning of the 

signal). When the barrier arms reset to home position, the both optical 

sensors become normal and the output contacts “Ready” and “Common” 

get closed (the finish of the signal). 

6.11.3 In case of delay of an authorized passage for more than 30 sec. the 

signal “Ready” is formed as follows: if within 30 seconds from the 

moment of passage commencing, which is determined by the arm 

rotation at no less than 8° (i.e. activation of one of the optic sensors), the 

reset of barrier arms to home position does not happen, the output 

contacts “Ready” and “Common” break (the beginning of the signal). 

When the barrier arms reset to home position, the both optic sensors 

become normal and the output contacts “Ready” and “Common” get 

closed (finish of the signal). 

6.11.4  When one or both of the optic sensors become out of order, the output 

contacts “Ready” and “Common” get broken (the beginning of the signal 

“Ready”). After fault removal the closed status of the contacts “Ready” and 

“Common” is resumed. 

7. 

 

MARKING AND PACKAGING  

7.1  The turnstile has a marking sticker on the internal side of the turnstile top 

cover and a label – inside, on the rear side of the turnstile housing. To get 
access to the marking sticker and the label, open the top cover (3). 

To do so proceed as follows: 

  Switch off power supply of the turnstile; 

  Insert the key into the top cover lock (4);  

  Turn the key clockwise till it stops (open the lock, the lock cylinder will move out 

together with a lock bolt at this); 

  Holding the front edge of the top cover (3) carefully lift it and turning it remove it 

from the turnstile housing. Be careful not to damage the CLB located under the 

cover while removing the top cover;  

  Place the top cover on a flat steady surface. 

Installation of the top cover back into its operation position is carried out in reverse 

order. After mounting the top cover, lock the top cover lock by pushing lock cylinder 
into its case till it clicks. Turn on the TB-01 turnstile power supply. 

7.2   To protect the turnstile against damage during transportation and storage 

the TB-01 turnstile as standard (Ref. Section 4) is packed in a transportation 
box, 1200

х

390

х

1100 mm, weight brutto– 88 kg.

 

 

8. SAFETY REQUIREMENTS 

8.1. Installation safety requirements  

8.1.1 The installation should be carried out only by qualified personnel after 

careful study of this Manual with observance of general safety rules. 

8.1.2   Only serviceable tools should be used for installation. 
8.1.3  All works should be performed only after the power supply is switched off 

and disconnected from the AC mains. 

8.1.4  During installation before the turnstile housing is fixed to the floor be care-

Summary of Contents for Turnichetul TB 1

Page 1: ...TB 1 0 Electromechanical box tripod turnstile with two built in readers Assembly Operation Manual...

Page 2: ...01 Electromechanical Box Tripod Turnstile with two built in readers Assembly and operation manual...

Page 3: ...on contingencies and response 14 7 MARKING AND PACKAGING 15 8 SAFETY REQUIREMENTS 15 8 1 Installation safety requirements 15 8 2 Operation safety requirements 16 9 INSTALLATION INSTRUCTIONS 16 9 1 Ins...

Page 4: ...ce points of industrial facilities banks administrative buildings railway terminals airports etc 1 2 To ensure fast and convenient passage through the turnstile it is recommended to install one TB 01...

Page 5: ...and operation manual 1 Certificate 1 Package 1 5 OPTIONAL EQUIPMENT SUPPLIED ON REQUEST Wireless remote control kit consists of a receiver and 2 transmitters tags with operation range up to 40m 1 Sir...

Page 6: ...capture option on entrance or exit the 01 turnstile can be used together with a 01 model featuring a built in card capture reader the TB 01 and TBC 01 models have matching design and dimensions 6 2 D...

Page 7: ...or of ban on passage 6 2 3 Inside the turnstile housing there is a bracket with a CLB mounted on it with terminal clamps for connection of external devices RC panel ACS outputs wireless remote control...

Page 8: ...siren and outputs providing the turnstile status data to the ACS controller XT2 connector block Detector to connect an intrusion detector XT3 12VDC connector block to connect the turnstile power suppl...

Page 9: ...onnection of the devices mentioned in Clause 6 3 1 is made with cables 17 19 20 to the corresponding connector blocks XT1 L and XT1 H of the CLB in accordance with the connection layout Ref Fig A 1 Ap...

Page 10: ...2 The turnstile is operated by input of a low level signal relatively to the GND contact to Unlock A Unlock B and Stop contacts of the XT1 L connector block As a control element there can be used a n...

Page 11: ...Det Out and Common and Alarm contacts Alarm 1 and Alarm 2 have normally open contacts The Common contact common contact for the relays at that is not con nected to the negative terminal of the turnsti...

Page 12: ...rol modes 6 5 1 There are two modes of the turnstile control a pulse control mode and a potential control mode They determine available operating modes of the turnstile Table 3 and Table 4 6 5 2 The c...

Page 13: ...ection if a low level signal already exists at the set direction input at the moment of passage At the low level signal inputting to the Stop input both directions will lock for the time of the signal...

Page 14: ...In the pulse control mode control over the turnstile from an ACS controller is similar to that one with the RC panel 6 5 2 In the potential control mode control over the turnstile from an ACS con tro...

Page 15: ...ow level signal appears at the Fire Alarm input the turnstile turns to the Always locked mode 6 9 3 2 In the potential control mode when a low level signal is removed from the Fire Alarm input both pa...

Page 16: ...on the internal side of the turnstile top cover and a label inside on the rear side of the turnstile housing To get access to the marking sticker and the label open the top cover 3 To do so proceed a...

Page 17: ...r similar foundations at least 150mm thick to level the foundation so that the anchoring points of the turnstile lie in the same plane check it with a level to apply reinforcing elements 550 550 200mm...

Page 18: ...rol cable is 30m The maximum allowed length of the turnstile power cable depends on the cable cross section and should not exceed for cable with 0 75mm2 cross section AWG 18 10 m for cable with 1 5mm2...

Page 19: ...the CLB Ref Fig 3 and Fig 1 Appendix 9 4 7 Check serviceability and accuracy of all the electrical connections Fix the cables using self adhesive cable tie mounts and nylon cable ties supplied with a...

Page 20: ...le routing inside the T 01 turnstile housing 1 power cable 2 cable from the RC panel wireless remote control device 3 rotation mechanism connection cable 4 cables of card readers 1 and 2 5 CLB 6 rotat...

Page 21: ...d connect them to a connector block X1 2 in accordance with color marking for reader 1 blue wire to a clamp 5 yel low wire to a clamp 6 for reader 2 blue wire to a clamp 12 yellow wire to clamp 11 LED...

Page 22: ...Power supply certificate Do not use substances for cleaning of the turnstile that may cause mechanical dam age or corrosion of the surfaces Do not move through the turnstile passage area any objects...

Page 23: ...in one direction the countdown of the passage waiting time 5 sec for the opposite direction is resumed Note Pressing the button on the RC panel corresponds to the low level signal supply to the contac...

Page 24: ...ent table in any sequence The two green indicators left and right are on The two Green arrows left and right are on After passage in the free passage direction the turnstile remains open in both direc...

Page 25: ...the turnstile remains open in the set direction 3 Both passage directions are open the turnstile is open for passage in both directions The low levels are on the contacts corresponding to the both dir...

Page 26: ...p the turnstile won t work no light indication on the turnstile housing and the RC panel No supply voltage to the CLB Switch off the turnstile power supply from the AC mains open the turnstile housing...

Page 27: ...ion 6 Lay the cover on a flat steady surface Inspect the resetting mechanism a pusher springs and a roller optic sensors and a damper Ref Fig 10 Remove dust from a rotation sensor disc located in the...

Page 28: ...lock locks by pressing the lock cylinder without turning the key Check operation of the T 01 turnstile in accordance with Section 9 of this Manual After maintenance works are complete the turnstile i...

Page 29: ...T2 Light A 2 3 2 3 button 2 GND 12VDC TPS button 1 yellow blue red common WRC black ACS outputs turnstile control signals on passage A6 1 right button left indicator stop indicator green yellow orange...

Page 30: ...ector 1 CLIP 4 A3 Emergency unblocking device 1 A4 Remote control panel 1 A5 Siren 1 A6 Access control system 1 A7 Wireless remote control 1 MSRF 4 8 Turnstile power supply unit 1 12 V 1 5 X1 1 Connec...

Page 31: ...roller NC NO XT5 NC NO R0 D1 X1 2 Light B XT3 12V GND 2 1 XT2 XT1 L XT1 L X1 A3 A2 X1 CM A1 Beeper brown blue R0 D0 12VDC 1 1 orange Det Out Ready PASS B PASS A Common Alarm 2 Alarm 1 12V XT1 H 2 GND...

Page 32: ...0 00 1 2 Bracket with CLB and connector blocks 1 A3 CLB 1 A4 Cover TBC01 150 00 with a reader 1 1 A5 Cover TBC01 150 00 with a reader 1 2 X1 1 Connector block 1 X1 2 Connector block 1 1 Turnstile cabl...

Page 33: ...re is a high level at the contacts Stop and Unlock A At this command the passage direction B opens either for 5 sec or until the passage has been effected in this direction or until the command Always...

Page 34: ...pen for free passage in both directions Active front is at the contact Unlock A while there is a low level at the contacts Unlock B and Stop or active front is at the contact Unlock B while there is a...

Page 35: ...n open for passage in the direction There is a low level at the contact Unlock while there is a high level at the con tacts Stop and Unlock At this command the direction B opens till the low level sig...

Page 36: ...PERCo Industrial Tel 7 812 3216172 7 812 3298924 Fax 7 812 2923608 Legal address 123 V ul Leona Pozemskogo Pskov 180600 Russia e mail support perco ru www percoweb com...

Page 37: ...www percoweb com...

Reviews:

Related manuals for Turnichetul TB 1