Assembly and Operation Manual
6.5.4
12
The pulse control mode is intended for the turnstile operation from the RC
panel, wireless remote control or an ACS controller, outputs of which
support pulse control mode
Standard control inputs: “Unlock A”, “Unlock B” and “Stop”.
Special control input: “Fire Alarm”.
Refer to Table 3 for the turnstile operating modes at this control mode.
The algorithm of control signals at this mode is described in Appendix B.
To change operating mode of the turnstile the minimum input signal duration
should be 100msec. The passage waiting time is 5 sec. and it does not depend on the
input signal duration.
Refer to Clause 6.9.3.1 for the turnstile operation at special “Fire Alarm” control in-
put.
6.5.5 The potential control mode is intended for the turnstile operation from an
ACS controller, outputs of which support potential control mode (for
instance lock controller).
Standard control inputs: “Unlock A” and “Unlock B”
Special control inputs: “Stop” and “Fire Alarm”.
See Table 4 for the turnstile operating modes at this control mode.
The algorithm of control signals at this mode is described in Appendix C.
To change operating mode of the turnstile the minimum input signal duration
should be 100msec. The passage waiting time is equal to the low-level signal
duration (the turnstile remains open in the set direction if a low-level signal already
exists at the set direction input at the moment of passage).
At the low-level signal inputting to the “Stop” input, both directions will lock for
the time of the signal duration regardless of the signal strength at the inputs “Unlock
A” and “Unlock B”. At the removing of a low-level signal from the “Stop” input, the
directions will set to the modes according to the signal strength at the inputs
“Unlock A” and “Unlock B”.
See Clause 6.9.3.2 for the turnstile operation at the special “Fire Alarm” control
input.
6.6. Operation from the RC panel
6.5.1 When the buttons on the RC panel are pressed (the
STOP button and the
two buttons corresponding to a passage direction), the closing of the
relevant contact “Stop”, “Unlock A” or “Unlock B” to the contact “GND”
occurs (i.
е
. forming of the low-level signal relatively to the contact “GND”).
6.5.2 Operation logic of the turnstile at the single passage in the
А
(
В
) direction at
the pulse control mode:
6.5.2.1 When the button, corresponding to the
А
(
В
) passage direction, is
pressed on the RC panel, the closing of the contact “Unlock A(
В
)” to the
contact “GND” occurs (i.
е
. forming of the low-level signal on the contact
“Unlock A(
В
)” relatively to the contact “GND”).
6.5.2.2 The CLB microcontroller processes an incoming command and gen-
erates a command to the control mechanism, which opens the
А
(
В
)
passage direction (lifts the upper (lower) edge of the key holt).
6.5.2.3 The microcontroller traces a status of the optic sensors, which be-
come active/normal in a certain sequence at barrier arm rotation,
Summary of Contents for Turnichetul TB 1
Page 37: ...www percoweb com...