Assembly and Operation Manual 

 

6.5.4

12

 

  The pulse control mode is intended for the turnstile operation from the RC 

panel, wireless remote control or an ACS controller, outputs of which 
support pulse control mode 

 

Standard control inputs: “Unlock A”, “Unlock B” and “Stop”. 
Special control input: “Fire Alarm”. 
Refer to Table 3 for the turnstile operating modes at this control mode. 
The algorithm of control signals at this mode is described in Appendix B. 
 
To change operating mode of the turnstile the minimum input signal duration 

should be 100msec. The passage waiting time is 5 sec. and it does not depend on the 
input signal duration. 

Refer to Clause 6.9.3.1 for the turnstile operation at special “Fire Alarm” control in-

put. 

 

6.5.5 The potential control mode is intended for the turnstile operation from an 

ACS controller, outputs of which support potential control mode (for 
instance lock controller).  

Standard control inputs: “Unlock A” and “Unlock B” 
Special control inputs: “Stop” and “Fire Alarm”. 
See Table 4 for the turnstile operating modes at this control mode. 
The algorithm of control signals at this mode is described in Appendix C. 

To change operating mode of the turnstile the minimum input signal duration 

should be 100msec. The passage waiting time is equal to the low-level signal 
duration (the turnstile remains open in the set direction if a low-level signal already 
exists at the set direction input at the moment of passage).  

At the low-level signal inputting to the “Stop” input, both directions will lock for 

the time of the signal duration regardless of the signal strength at the inputs “Unlock 
A” and “Unlock B”. At the removing of a low-level signal from the “Stop” input, the 
directions will set to the modes according to the signal strength at the inputs 
“Unlock A” and “Unlock B”. 

See Clause 6.9.3.2 for the turnstile operation at the special “Fire Alarm” control 
input. 

6.6.  Operation from the RC panel 

6.5.1  When the buttons on the RC panel are pressed (the

 

STOP button and the 

two buttons corresponding to a passage direction), the closing of the 
relevant contact “Stop”, “Unlock A” or “Unlock B” to the contact “GND” 
occurs (i.

е

. forming of the low-level signal relatively to the contact “GND”). 

6.5.2  Operation logic of the turnstile at the single passage in the 

А

(

В

) direction at 

the pulse control mode: 

6.5.2.1  When the button, corresponding to the 

А

  (

В

) passage direction, is 

pressed on the RC panel, the closing of the contact “Unlock A(

В

)” to the 

contact “GND” occurs (i.

е

. forming of the low-level signal on the contact 

“Unlock A(

В

)” relatively to the contact “GND”). 

6.5.2.2  The CLB microcontroller processes an incoming command and gen-

erates a command to the control mechanism, which opens the 

А

 (

В

passage direction (lifts the upper (lower) edge of the key holt). 

6.5.2.3  The microcontroller traces a status of the optic sensors, which be-

come active/normal in a certain sequence at barrier arm rotation, 

Summary of Contents for Turnichetul TB 1

Page 1: ...TB 1 0 Electromechanical box tripod turnstile with two built in readers Assembly Operation Manual...

Page 2: ...01 Electromechanical Box Tripod Turnstile with two built in readers Assembly and operation manual...

Page 3: ...on contingencies and response 14 7 MARKING AND PACKAGING 15 8 SAFETY REQUIREMENTS 15 8 1 Installation safety requirements 15 8 2 Operation safety requirements 16 9 INSTALLATION INSTRUCTIONS 16 9 1 Ins...

Page 4: ...ce points of industrial facilities banks administrative buildings railway terminals airports etc 1 2 To ensure fast and convenient passage through the turnstile it is recommended to install one TB 01...

Page 5: ...and operation manual 1 Certificate 1 Package 1 5 OPTIONAL EQUIPMENT SUPPLIED ON REQUEST Wireless remote control kit consists of a receiver and 2 transmitters tags with operation range up to 40m 1 Sir...

Page 6: ...capture option on entrance or exit the 01 turnstile can be used together with a 01 model featuring a built in card capture reader the TB 01 and TBC 01 models have matching design and dimensions 6 2 D...

Page 7: ...or of ban on passage 6 2 3 Inside the turnstile housing there is a bracket with a CLB mounted on it with terminal clamps for connection of external devices RC panel ACS outputs wireless remote control...

Page 8: ...siren and outputs providing the turnstile status data to the ACS controller XT2 connector block Detector to connect an intrusion detector XT3 12VDC connector block to connect the turnstile power suppl...

Page 9: ...onnection of the devices mentioned in Clause 6 3 1 is made with cables 17 19 20 to the corresponding connector blocks XT1 L and XT1 H of the CLB in accordance with the connection layout Ref Fig A 1 Ap...

Page 10: ...2 The turnstile is operated by input of a low level signal relatively to the GND contact to Unlock A Unlock B and Stop contacts of the XT1 L connector block As a control element there can be used a n...

Page 11: ...Det Out and Common and Alarm contacts Alarm 1 and Alarm 2 have normally open contacts The Common contact common contact for the relays at that is not con nected to the negative terminal of the turnsti...

Page 12: ...rol modes 6 5 1 There are two modes of the turnstile control a pulse control mode and a potential control mode They determine available operating modes of the turnstile Table 3 and Table 4 6 5 2 The c...

Page 13: ...ection if a low level signal already exists at the set direction input at the moment of passage At the low level signal inputting to the Stop input both directions will lock for the time of the signal...

Page 14: ...In the pulse control mode control over the turnstile from an ACS controller is similar to that one with the RC panel 6 5 2 In the potential control mode control over the turnstile from an ACS con tro...

Page 15: ...ow level signal appears at the Fire Alarm input the turnstile turns to the Always locked mode 6 9 3 2 In the potential control mode when a low level signal is removed from the Fire Alarm input both pa...

Page 16: ...on the internal side of the turnstile top cover and a label inside on the rear side of the turnstile housing To get access to the marking sticker and the label open the top cover 3 To do so proceed a...

Page 17: ...r similar foundations at least 150mm thick to level the foundation so that the anchoring points of the turnstile lie in the same plane check it with a level to apply reinforcing elements 550 550 200mm...

Page 18: ...rol cable is 30m The maximum allowed length of the turnstile power cable depends on the cable cross section and should not exceed for cable with 0 75mm2 cross section AWG 18 10 m for cable with 1 5mm2...

Page 19: ...the CLB Ref Fig 3 and Fig 1 Appendix 9 4 7 Check serviceability and accuracy of all the electrical connections Fix the cables using self adhesive cable tie mounts and nylon cable ties supplied with a...

Page 20: ...le routing inside the T 01 turnstile housing 1 power cable 2 cable from the RC panel wireless remote control device 3 rotation mechanism connection cable 4 cables of card readers 1 and 2 5 CLB 6 rotat...

Page 21: ...d connect them to a connector block X1 2 in accordance with color marking for reader 1 blue wire to a clamp 5 yel low wire to a clamp 6 for reader 2 blue wire to a clamp 12 yellow wire to clamp 11 LED...

Page 22: ...Power supply certificate Do not use substances for cleaning of the turnstile that may cause mechanical dam age or corrosion of the surfaces Do not move through the turnstile passage area any objects...

Page 23: ...in one direction the countdown of the passage waiting time 5 sec for the opposite direction is resumed Note Pressing the button on the RC panel corresponds to the low level signal supply to the contac...

Page 24: ...ent table in any sequence The two green indicators left and right are on The two Green arrows left and right are on After passage in the free passage direction the turnstile remains open in both direc...

Page 25: ...the turnstile remains open in the set direction 3 Both passage directions are open the turnstile is open for passage in both directions The low levels are on the contacts corresponding to the both dir...

Page 26: ...p the turnstile won t work no light indication on the turnstile housing and the RC panel No supply voltage to the CLB Switch off the turnstile power supply from the AC mains open the turnstile housing...

Page 27: ...ion 6 Lay the cover on a flat steady surface Inspect the resetting mechanism a pusher springs and a roller optic sensors and a damper Ref Fig 10 Remove dust from a rotation sensor disc located in the...

Page 28: ...lock locks by pressing the lock cylinder without turning the key Check operation of the T 01 turnstile in accordance with Section 9 of this Manual After maintenance works are complete the turnstile i...

Page 29: ...T2 Light A 2 3 2 3 button 2 GND 12VDC TPS button 1 yellow blue red common WRC black ACS outputs turnstile control signals on passage A6 1 right button left indicator stop indicator green yellow orange...

Page 30: ...ector 1 CLIP 4 A3 Emergency unblocking device 1 A4 Remote control panel 1 A5 Siren 1 A6 Access control system 1 A7 Wireless remote control 1 MSRF 4 8 Turnstile power supply unit 1 12 V 1 5 X1 1 Connec...

Page 31: ...roller NC NO XT5 NC NO R0 D1 X1 2 Light B XT3 12V GND 2 1 XT2 XT1 L XT1 L X1 A3 A2 X1 CM A1 Beeper brown blue R0 D0 12VDC 1 1 orange Det Out Ready PASS B PASS A Common Alarm 2 Alarm 1 12V XT1 H 2 GND...

Page 32: ...0 00 1 2 Bracket with CLB and connector blocks 1 A3 CLB 1 A4 Cover TBC01 150 00 with a reader 1 1 A5 Cover TBC01 150 00 with a reader 1 2 X1 1 Connector block 1 X1 2 Connector block 1 1 Turnstile cabl...

Page 33: ...re is a high level at the contacts Stop and Unlock A At this command the passage direction B opens either for 5 sec or until the passage has been effected in this direction or until the command Always...

Page 34: ...pen for free passage in both directions Active front is at the contact Unlock A while there is a low level at the contacts Unlock B and Stop or active front is at the contact Unlock B while there is a...

Page 35: ...n open for passage in the direction There is a low level at the contact Unlock while there is a high level at the con tacts Stop and Unlock At this command the direction B opens till the low level sig...

Page 36: ...PERCo Industrial Tel 7 812 3216172 7 812 3298924 Fax 7 812 2923608 Legal address 123 V ul Leona Pozemskogo Pskov 180600 Russia e mail support perco ru www percoweb com...

Page 37: ...www percoweb com...

Reviews: