RTD-03S Waist-high rotor turnstile 

 

Pin number 

Signal 

RIGHT 

STOP 

LEFT 

Pwr Failure E 

GND 

PASS L1 

PASS R1 

Pwr Failure C 

PASS L2 

10 

PASS R2 

11 

Pass Sensor 1 

12 

Bat Failure C 

13 

Bat Failure E 

14 

Pass Sensor 2 

 

 

 

Pin number 

Signal 

+24V 

GND 

GND 

 

 

Figure 4. Control unit connectors 

There are 2 variants of the turnstile control: 

 

Pulse control

  —  the turnstile is operated by input of a low-level signal or by closing the 

contacts 

«RIGHT»

«STOP»

«LEFT»

  and 

«GND» (GROUND) 

of the ACS connector. The 

control signal duration is not less than 100 ms;;

 

 

Potential control

 — the turnstile is operated by input of a low-level signal or by closing the 

contacts 

«RIGHT», «LEFT»

 and 

«GND» (GROUND)

. The set passage mode can be cancelled 

by removal of a low-level signal or by breaking the contacts 

«RIGHT»,

 

«LEFT»

 and 

«GND»

 

(GROUND)

  of the 

“ACS”

  connector. The 

«STOP»

  contact of the 

“ACS”

  connector is not 

used

The control variant is set by the jumper on the X5 connector of the processor module (see Fig. 9)

If the jumper is fixed – pulse control, the jumper is not fixed – potential control. 
The control unit is supplied with pulse control mode preset (the jumper of the X5 connector is set). 
As the control element in the ACS (see Fig. 5) there can be used a normally open relay contact or 

a circuit with open collector output with the following signal characteristics: 

  voltage at open contact ................................................................................................. 5±0,5 V; 

  voltage at closed low-level contact ............................................................................. max 0,8V; 

  current via closed contact ....................................................................................... max 1,5 mA. 

The optic barrier wing rotation sensors, placed inside the turnstile post, track passages through the 

turnstile. The passage direction is determined according to sequence of the sensors operated. 
When turning the barrier wing, the closed contacts 

«Pass R1»,

 

«Pass R2»

 

or

 

«Pass L1», «Pass 

L2»

 of the CU 

“ACS”

 connector are broken. The signal duration depends on the rotation speed of 

the barrier wings. There are several additional signals put out at the CU 

“ACS”

 connector:

 

 

«Pwr failure»

 – AC mains failure (contacts 

“Pwr failure C”

 and 

“Pwr failure E”

 — collector 

(+) and emitter (-) of the galvanic decoupling circuit correspondingly).  

Summary of Contents for RTD-03S

Page 1: ...OPERATION MANUAL RTD 03S Waist high Rotor Turnstile...

Page 2: ...Waist high Rotor Turnstile RTD 03S Operation manual...

Page 3: ...anical unblocking of the turnstile 11 6 MARKING AND PACKAGING 12 7 SAFETY REQUIREMENTS 12 7 1 Installation safety requirements 12 7 2 Operation safety requirements 12 8 INSTALLATION INSTRUCTIONS 12 8...

Page 4: ...egory U4 operation in premises with climate control Operation of the turnstile post is allowed at ambient temperature between 1 C and 45 C and relative air humidity up to 98 at 35 C The control unit i...

Page 5: ...ppendix 1 Wireless remote control kit 1 Note Wireless remote control kit consists of a receiver and 2 transmitters tags with operation range up to 40 m 5 BRIEF DESCRIPTION 5 1 Main features The turnst...

Page 6: ...1 Four barrier wings 6 are mounted on the rotary post 1 The filler panels 7 are set into the barrier wings 6 with the fastenings 15 On the rotary post 1 cover 3 there is the mechanical release lock 4...

Page 7: ...panel which are intended for setting the turnstile operating modes The LED indicators are located above the buttons The button in the middle hereinafter the STOP button is intended to set the turnstil...

Page 8: ...RTD 03S Waist high rotor turnstile 7 Figure 3 Control unit...

Page 9: ...cable connector Control Power cable connector DC 24V External DC power supply connector Bat 24V AC power cable input 220V Entry for intrusion detector and siren cables Alarm Connections for intrusion...

Page 10: ...he X5 connector of the processor module see Fig 9 If the jumper is fixed pulse control the jumper is not fixed potential control The control unit is supplied with pulse control mode preset the jumper...

Page 11: ...Pass Sensor Pwr failure and Bat failure have the galvanic decoupling a Control elements of an external device a normally open relay contact b Control elements of an external device a circuit with ope...

Page 12: ...locking of the turnstile Possibility to unblock the turnstile manually is specially provided for unblocking the turnstile in the emergency mode at all the power supplies failure AC mains switching off...

Page 13: ...l safety requirements for use of electrical equipment Don ts Do not use the turnstile under conditions that do not comply with the requirements of Chapter 2 of this Manual Do not mount the control uni...

Page 14: ...raceways for the control cable 10 and the power cable 11 as shown in Fig 7 and according to your checkpoint layout Figure 7 Marking layout for RTD 03S installation dotted line shows the dimensions of...

Page 15: ...ttings 14 holes Check the strong fastening of the barrier wings 6 and the filler panels 7 8 Check free rotation of the rotary post 1 Unblock the rotary post with the mechanical release key 5 see Claus...

Page 16: ...ector put remote control cable 13 through its cable inlet inside the control unit and connect it to the X3 and X4 connectors on the processor module as per Fig 9 11 Set the CU Power toggle switch and...

Page 17: ...s and the AC power cable operability Prior to the turnstile power up set the Power toggle switch and the Battery toggle switch to the O position Install the Bat 2A fuse which is provided together with...

Page 18: ...nd for the new passage mode entered by the RC will be enquired in the command queue of the turnstile After the barrier wing is reset to the reset state the command from the command queue will be perfo...

Page 19: ...Grn_L or LED Grn_R output is active depending on the set direction The barrier wings rotation in the set direction is allowed 3 Bidirectional single passage open for one by one person passage in each...

Page 20: ...will start blinking with interval of 2 seconds At the further battery discharge the CU will automatically switch off When the AC mains is restored the turnstile turns to the AC mains the Power toggle...

Page 21: ...e and when the CU is powered up with the external SPS via the Bat 24V connector the Battery toggle switch is in the I position the Bat 2A fuse is not installed the turnstile does not work the indicato...

Page 22: ...Guide barriers set posts polished tubular stainless steel dia 50 mm rails beechwood ashwood filler panels tinted polycarbonate plastic mnemonic indication units RB 03S guide barriers set Guide barrier...

Page 23: ...r stainless steel dia 50 mm rails polished tubular stainless steel dia 32 mm filler panels tinted polycarbonate plastic symbol indication units RB 03T guide barriers set Guide barriers set posts polis...

Page 24: ...ut for installation of turnstile with guide barriers set electric raceway to the control unit is laid from the turnstile post center in the direction of the control unit according to the layout Figure...

Page 25: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com...

Page 26: ...www perco com...

Reviews: