Certificate & Operation Manual
Attention
!
When mounting the reader please provide the cable bending radius of min. 10 mm at
reader basis.
8. Run the cable, attach it and connect to external devices. Layout of reader connection
to external devices under Wiegand interface is shown in Fig. 5. Switching the output
data format is recommended to carry out directly at the junction of the regular reader
cable with an extension cable (see section 5.2).
Figure 5. Connection layout of the reader to external devices
under Wiegand interface
8. TROUBLESHOOTING
Possible faults that can be resolved by the Customer and their remedy are given in the
table below:
Table 3. Troubleshooting guide
Fault
Possible cause
Remedy
At the power-up the LED
indicator of the reader does not
light, reader does not react on
card presentation.
No supply voltage to the reader
Check the accuracy of reader
connection to power supply
LED operation mode does not
switch to «double line»
Electric contact between
«single-double» jumper wires
or with ground bar
Insulate «single-double» jumper
wire ends (prior power off the
reader)
The required reader output
data format does not switch on
No electric contact between
orange wire and necessary
conductor according Table 2
Find the disconnection and reset
the electric contact (prior power off
the reader)
If the fault is not cleared please contact the Manufacturer.
12