Configuration
22
1980
2010
-0
2
55
Linearization parameters
If the linearization mode "Special Curve" is selected, the "Linearization" leaf must be
opened:
•
Up to 32 value pairs can be entered
•
X values must be entered in increasing order, Y values must rise or fall monotonically
(red = error)
•
Range end values must correspond to those in the 4-20 mA leaf
•
A graphic shows the linearization curve
Figure 5.9: Linearization
Linearization
Parameter
Description
Default
X: mA (1 ... 32)
Input value X1 ... X32 for linearization (mA)
4, 20
Y: unit (1 ... 32)
Output value Y1 ... Y32 for linearization (engineering units) 4, 20
Read
Press to upload values from the device into the DTM.
Happens automatically when the
Linearization
leaf is
opened.
–
Write
Press to download the table from the DTM to the device.
–
Table 5.5: Linearization