Configuration
22
1980
2010
-0
2
58
Burst Command
Number
Determines which commands are to be sent in the burst
message.
• 1 Primary variable: Returns the primary value and units.
• 2 Loop current and percentage of range: Returns the
loop current and its associated percent of range.
• 3 Dynamic variables and loop current: Returns the loop
current and up to four predefined dynamic variables
and units (PV, SV, TV, QV).
• 9 Device variables: Returns the value of up to 8 device
or dynamic variables with units.
• 33 Device variables and additional device status:
Returns the value of up to four device variables and the
device status information.
• 48 Additional device status: Returns the device status
information.
For connected HART devices, check the operating manual
to see which commands are supported: if you are
uncertain, use Command 3 as default
1
Device Variable
0 ... 7
Selects the device variables to be transmitted in the burst
message when command 9 or 33 is entered as
Burst
Command Number
:
• For the adapter, select the variable you want to transmit
from the drop-down menu.
• For a connected HART device, check the operating
manual (loop-current, PV, SV, TV and QV can be
selected).
250
Cancel
Click to make the setting to revert to their original values.
–
Apply
Click to download the changes to the device.
–
Table 5.6: Burst Mode 1 ... 10 Parameters
Parameter
Description
Default