Sequence for configuring a start/stop ramp

Send the following data values and parameter values to the motor control module:

1.

For each of steps 1 ... 6, send the data value "4" via DO0 ... DO3 and then via P0 ... P2, the 
corresponding value from the parameter sequence 3, 1, 6, 3, 1, 6.

2.

If configuration mode is active, as step 7, send the required ramp number via DO ... DO3 and 
via P0 ... P2 the parameter value "6".

3.

As step 8, send the ramp number again via DO0 ... DO3 and via P0 ... P2 the parameter value 
"4".

4.

As step 9, send data value "0" via DO0 ... DO3 and via P0 ... P2 the parameter value "7".

 The motor control module has stored the new start/stop ramp and switched back to normal 

mode.

Contexts of module communication

Note

Sequence for command transmission

For each step, you generally send the data value via DO0 ... D03 first and then the parameter 
value P0 ... P2. The following table shows the contexts of communication between the master 
and motor control module. The value "x" represents any of the values in the table.

Step

DO0 ... DO3 P0 ... P2

DI0 ... DI3

Comment

4

x

x

Motor control module in normal mode

1

4

3

x

Start activation sequence for configuration 
mode

2

4

1

x

3

4

6

x

4

4

3

x

5

4

1

x

6

4

6

11xx = C ... F

End activation sequence for configuration 
mode

7

Ramp num-
ber

6

11xx = C ... F

The ramp number is transferred to the motor 
control module.

8

Ramp num-
ber

4

10xx = 8 ... B

The ramp is stored.

9

0

7

x

Motor control module switches back to normal 
mode.

Table 5.10

Summary of Contents for VBA-4E4A-G20-ZEJ/M3L-P9

Page 1: ...VBA 4E4A G20 ZEJ M3L P9 AS Interface motor control module Manual...

Page 2: ...sion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs c...

Page 3: ...UL Information 7 3 Product Description 8 3 1 Use and application 8 3 2 Housing 8 3 3 Displays and operating elements 9 3 4 Interfaces and connections 11 3 5 Accessories 12 4 Installation 13 4 1 Storag...

Page 4: ...icable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility...

Page 5: ...rs or compatible types The motor control module has two inputs for connecting three wire sensors Read through these instructions thoroughly Familiarize yourself with the device before install ing moun...

Page 6: ...using the device Secure the device against unintended operation To have the device repaired return it to your local Pepperl Fuchs representative or your sales center 1 6 Declaration of Conformity Thi...

Page 7: ...or indoor use only This device may be operated in altitudes up to 2000 m The ambient temperature range is from 25 C to 70 C The device must be installed in accordance with applicable national laws and...

Page 8: ...power supply may be loaded in total with 100 mA For each motor a maximum current load of 5 A is permitted briefly 2 s Figure 3 1 VBA 4E4A G20 ZEJ M3L P9 motor control module Essential function and app...

Page 9: ...Peripheral fault Display of the AS Interface operating states The AUX LED shows the status of the AUX external auxiliary voltage supply 100 120 122 135 5 8 16 6 15 27 5 25 8 54 LED PWR Green LED FAULT...

Page 10: ...X external auxiliary voltage is inverted Off AUX external auxiliary voltage is missing LED FUSE1 LED FUSE2 Green Status On Power supply for motor is OK Off Power supply for motor is missing Fuse is fa...

Page 11: ...sensors and motors are connected to the motor control module via cables with round M8 connectors Sensors socket 4 pin Motors socket 5 pin The cable length is 1 m LED DIR Yellow Status On Direction of...

Page 12: ...pin socket screw locking coding A Suitable counterpart connector M8 4 pin plug screw locking coding A IN1 IN2 1 IN sensor supply 2 Not used 3 IN sensor supply 4 IN input Motor Motor in accordance with...

Page 13: ...ut the needs for tools The profiled flat cables have a narrow upper side with a visibly offset profile edge and a wide under side profile edge not visible The cable guide allows the flat cables to be...

Page 14: ...this push the locking bracket 1 slightly to one side 2 Insert the black AUX flat cable with the profile edge 3 to the motor control module into the lower guide see the module tag Black AUX 3 Insert th...

Page 15: ...at cable The profile edge 2 does not point to the motor control module the flat cable is therefore inserted with reverse polarity The flat cable is located on the reverse polarity protection 1 with a...

Page 16: ...Connecting motors and sensors Figure 4 4 Connection wiring diagram for motors and sensors n c PWR AUX AUX AS Interface AS Interface FAULT AUX 1 4 3 2 IN 1 2 4 5 3 FUSE IN1 IN2 IN IN IN MOT1 MOT2 MOT...

Page 17: ...e sets the output data DO0 DO3 to logical 0 Starting Stopping motors DO0 DO1 You can start or stop the motors separately via bits DO0 and DO1 To start motors you must set the corresponding data bit to...

Page 18: ...This always applies to both motors simultaneously To do this you must parameterize 1 of 4 predefined speed values The speed values correspond to analog voltage values If the master does not change the...

Page 19: ...nds to the time from stopped to reaching the maximum speed or from the maximum speed to stopped The inclines of the ramps are constant for each of the 8 ramps and independent of the set speed The refe...

Page 20: ...s are possible as long as a period of 10 s is not exceeded for steps 1 6 The configuration of a new start stop ramp runs in the following phases In steps 1 6 the master sends parameter values to the m...

Page 21: ...has stored the new start stop ramp and switched back to normal mode Contexts of module communication Note Sequence for command transmission For each step you generally send the data value via DO0 D03...

Page 22: ...rol module reaction 1 6 Incorrect data or parameter values or steps 1 6 take longer than 10 s Motor control module remains in normal mode 7 or 8 Incorrect data or parameter values The motor control mo...

Page 23: ...t AUX off AUX external power supply is miss ing Check AUX voltage and AUX flat cable AUX red on AUX external power supply is inverted Correct the polarity of the AUX flat cable in the cable guide AUX...

Page 24: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 6524A...

Reviews: