3.8

Technical data

Functional Safety Data

Conformity

Approvals and Certificates

PFH

d

2.81 E-9

Performance Level

PL e (EN ISO 13849-1)

Category

Cat. 4 (in accordance with ISO 13849-1)

Life time

20 a

Functional Safety

ISO 13849-1

Product Standards

EN 61496-1; IEC 61496-2

CE conformity

CE

CCC approval

Products with a maximum operating voltage of 

 36 V are not subject to approval and 

are therefore not assigned a CCC mark.

TÜV approval

TÜV

SLP8-2-...

SLP10...

SLP30...

SLP65...

General data

Effective operating range

0.2 ... 8 m

0.2 ... 10 m

6 ... 30 m

12 ... 65 m

Number of beams

See table 3.3

Beam gap

See table 3.3

Obstacle size

Static: 32 mm

Dynamic: 50 mm (where v = 1.6 m/s for the obstacle)

Light source

LED

Type of light

Modulated red light

LED risk group designation

Free group according to DIN EN 62471

Opening angle

< 5°

Indicators/Operating Cont-

rols

Function indicator

Red LED: per receiving channel, off: interruption 

Flashing: receiving  receiving with less than double signal strength 

Permanently lit: reception with sufficient signal strength

Muting indicator

Signal lamps, optional

Failure warning display

Function display flashing

Electrical data

Operating display

Red LED in active column

Operating voltage

Power supply via control unit

Protection class

III

Ambient conditions

Ambient temperature

-20 ... 60 °C (253 ... 333 K)

Storage temperature

-20 ... 70 °C (253 ... 343 K)

Relative humidity

max. 95 % non-condensing

Mechanical specifications

Summary of Contents for SLP Series

Page 1: ...ORIGINAL INSTRUCTIONS FACTORY AUTOMATION Safety light grid SLP series ...

Page 2: ...st version of the General Terms of Supply for Products and Services in the Electronics Industry issued by the German Electrical and Electronic Manufacturers Association ZVEI and the Extended Retention of Title clause apply to this document ...

Page 3: ... 3 7 2 Conformity with Standards and Directives 8 3 7 3 Approvals and Certificates 8 3 8 Electrical Connection 9 3 9 Dimensions 10 3 10 Ordering Information 12 4 Deviation Mirror 13 4 1 Application 13 4 2 Technical Data 13 4 3 Dimensions 14 4 4 Ordering Information 14 5 Signal Lamps 15 5 1 Mounting 15 5 2 Technical Data 15 5 3 Electrical Connection 16 5 4 Dimensions 16 5 5 Ordering Information 16 ...

Page 4: ...eration of the device Can utilize the entire range of device functions Avoid faulty operation and associated faults Reduce costs associated with downtime and incidental repairs Increase the effectiveness and operating efficiency of your plant Store these instructions somewhere safe in order to have them available for future work on the device Directly after opening the packaging please ensure that...

Page 5: ...y All products were developed and manufactured under observance of the applicable European stan dards and guidelines The product manufacturer Pepperl Fuchs GmbH 68307 Mannheim has a certified quality assurance system that conforms to ISO 9001 Note A Declaration of Conformity may be requested from the manufacturer ISO9001 ...

Page 6: ... access protections as specified in EN ISO 13855 The beam spacings are fixed and meet the specifications out lined in the standard SLP light grids consist of an emitter and receiver The emitter and receiver for the SPL 8 2 A active column are incorporated into a single housing A deviation mirror SLP 8 2 M must be positioned on the opposite side to operate the device A complete safety device includ...

Page 7: ...hat the emitter and receiver profiles are installed vertically and that the axis of the first beam is positioned at the prescribed dis tance from the ground EN ISO 13855 The emitter profile must be aligned so that the light beams fall on the receiver profile The receiver profile must then be adjusted so that the indicators for the receiver channels light up continuously Check the control unit to s...

Page 8: ... 3 Beam gap See table 3 3 Obstacle size Static 32 mm Dynamic 50 mm where v 1 6 m s for the obstacle Light source LED Type of light Modulated red light LED risk group designation Free group according to DIN EN 62471 Opening angle 5 Indicators Operating Cont rols Function indicator Red LED per receiving channel off interruption Flashing receiving receiving with less than double signal strength Perma...

Page 9: ... SLP emitter and SLP receiver Degree of protection IP65 Connection M16 cable gland terminal compartment Material Housing Extruded aluminum profile RAL 1021 yellow coated Lens Plastic lens Weight See table 3 3 Type SLP8 2 SLP 2 SLP 3 SLP 4 Number of beams 1 2 3 4 Beam gap 500 mm 500 mm 400 mm 300 mm Weight 2100 g 2100 g 3200 g 3500 g Emitter SLP Receiver SLP L Control Unit SafeBox module 4X only wi...

Page 10: ...X Control Unit SafeBox Module 4X Transceiver SLP8 2 A Transceiver SLP8 2 A L muting lamp muting lamp trigger emitter x output receiver x input receiver 24 V receiver 0 V emitter x output receiver x input receiver 24 V receiver 0 V nc nc nc T1 nc nc nc nc R1 U T1 R1 U nc nc nc T1 nc L L1 nc R1 U T1 R1 U 0 V L L1 SB4 4M Emitter Receiver Option L with indicator lamp receiver only Cable gland M16 Oper...

Page 11: ...tus indicator of the particular safety beam first beam second beam Indicator lamp topmost beam third beam Emitter Receiver 197 ø 57 64 32 70 33 5 936 90 400 400 46 Option L with indicator lamp receiver only Cable gland M16 Operating display Receiver Status indicator of the particular safety beam first beam second beam Indicator lamp topmost beam third beam Emitter Receiver fourth beam 197 ø 57 64 ...

Page 12: ... T SLP65 2 T Receiver SLP10 2 R SLP30 2 R SLP65 2 R Receiver with muting lamp SLP10 2 R L SLP30 2 R L SLP65 2 R L 3 Emitter SLP10 3 T SLP30 3 T SLP65 3 T Receiver SLP10 3 R SLP30 3 R SLP65 3 R Receiver with muting lamp SLP10 3 R L SLP30 3 R L SLP65 3 R L 4 Emitter SLP10 4 T SLP30 4 T SLP65 4 T Receiver SLP10 4 R SLP30 4 R SLP65 4 R Receiver with muting lamp SLP10 4 R L SLP30 4 R L SLP65 4 R L cabl...

Page 13: ...all components are arranged vertically and at the same height To roughly align the mirror turn it so that you can see the profile of the re ceiver reflected in the mirror when looking at the mirror with the emitter behind you Aligning the mirrors is made easier by using the beam alignment aid It is important to ensure that the mirror surfaces are clean Scratch free cleaning agents and lint free cl...

Page 14: ...ensions Figure 4 2 Deviation mirror dimensional drawing 4 4 Ordering information Table 4 3 Deviation mirror ordering information Model number Number of beams SLP 2 M 2 SLP 3 M 3 SLP 4 M 4 300 300 300 400 400 636 1036 936 68 68 60 70 64 46 68 68 60 38 2 64 46 68 60 64 46 9 5 10 5 6 5 5 5 500 68 ...

Page 15: ...nd C must line up 3 Turn the bayonet ring in the direction of the arrow ring must engage Removal is performed in reverse order Press down the bulb and turn counterclockwise to remove from the bayonet holder When mounting several lamps observe the sequence of the lamp modules 5 2 Technical data Light grids in the SLP series with option L correspond to basic devices in terms of their technical prope...

Page 16: ...Chapter 3 9 5 4 Dimensions Figure 5 2 Dimensional drawing signal lamps 5 5 Ordering information SLP safety light grid S L P D D N F L Muting lamp L Signal lamp Number of beams E Emitter R Receiver A Active column Number of beams 2 2 beams 3 3 beams 4 4 beams Effective operating range 8 8 m 10 10 m 30 30 m 65 65 m ...

Page 17: ... 30 50 90 An opaque rod with a diameter of 30 mm must be used to test safety light grids in the SLP series this rod is used to interrupt the beams 6 3 Beam alignment tool Model number BA SLP Laser alignment aid for SLP safety light grids The basic device and corresponding adapter are included with the delivery 6 4 Profile alignment aid Model number PA SLP SLC This small spirit level is ideal for a...

Page 18: ... fully functional units when used in conjunction with Safe box SB4 control units The information provided in the operating instructions for the SB4 applies in all cases Note Observe the relevant laws and standards The relevant laws and standards that apply to the use of photoelectric protective devices must be followed There are differences depending on the area of use ...

Page 19: ...Date of issue 05 08 2008 SLP series safety light grid ...

Page 20: ...eim Deutschland Tel 49 621 776 0 E Mail info de pepperl fuchs com Zentrale USA Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E Mail sales us pepperl fuchs com Zentrale Asien Pepperl Fuchs Pte Ltd Singapur 139942 Tel 65 67799091 E Mail sales sg pepperl fuchs com FABRIKAUTOMATION SENSING YOUR NEEDS DOCT 1864B 221139 05 2018 ...

Reviews: