Pressure Transmitter LHCR-51, LHCS-51
Mounting
8
2.4
Assembling and mounting the "separate housing" version
1
"Separate housing" version
1
In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready
mounted.
2
Cable with connection jack
3
Pressure compensation
4
Connector
5
Locking screw
6
Housing mounted with housing adapter, included
7
Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1-1/4 in up to 2 in diameter)
2.4.1
Assembly and mounting
1.
Insert the connector (4) into the corresponding connection jack of the cable (2).
2.
Plug the cable into the housing adapter (6).
3.
Tighten the locking screw (5).
4.
Mount the housing on a wall or pipe using the mounting bracket (7).
When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at
least 5 Nm (3.69 lbs ft).
Mount the cable with a bending radius ((r)
≥
120 mm (4.72 in).
r
120
mm
≥
1
2
3
4
5
6
7
7