Differential pressure transmitter 
SITRANS P250 (7MF1641) 

Operating Instructions (Compact) 
Safety notes 

 

CAUTION 

This device left the factory in a perfect state with regard to safety. To maintain this status 

and to ensure safe operation of the device, observe the following notes: 
The device may only be used for the purposes specified in these instructions. 

 

Observe the test certification, provisions and laws applicable in your country during 

connection, assembly and operation. 

 

The device can be operated both at high pressure and with aggressive and 

hazardous media. Therefore, improper use of this device may lead to serious injury 

and or considerable damage to property. Above all, it must be noted when the 

device was in use and is to be exchanged. 

 

For this reason, only qualified personnel may set up, install, commission, and 

operate the product. 

 

Application 

The differential pressure transmitter is used to measure the differential pressure of gases 

and liquids in the following industrial areas: mechanical engineering, electrical engineering, 

water supply, shipbuilding, chemistry, and pharmaceutics. 

Hardware configuration 

Description 

Type 7MF1641-*****-1**0 

The differential pressure transmitter 

consists of a piezoresistive measuring cell 

with a ceramic diaphragm, installed in a 

stainless steel housing. It can be 

electrically connected with a plug as per 

EN 175301-803-A (IP65), a round 

connector as per DIN EN 60130-9 (IP65) 

or with a cable (IP65). The output signal is 

optionally 4 to 20 mA (two-wire 

technology), 0 to 5 V DC or 0 to 10 V DC 

(three-wire technology) 

 

Installation 

 

The location of the device has no influence on the precision of the measurement. 

 

Before installation, compare the process data with the data of the rating plate. 

 

The medium being measured must be suitable for the parts of the pressure 

transmitter in contact with the medium. 

 

The burst pressure must not be exceeded. 

 

The following operating conditions apply to installation: 

 

Ambient temperature: -15 °C ... +85 °C (5 °F ... +185 °F) 

 

Process temperature: -15 °C ... +85 °C (5 °F ... +185 °F) 

 

Storage temperature: -40 °C to +85 °C (-40 °F to +185 °F) 

 

Attach the devices with fixed cable installation. 

 

Connecting 

If you use design versions with a plug as per EN 175301-803-A or round connector as per 

DIN EN 60130-9, the following applies: 

 

We recommend that you place the cable shield on one end at the power supply. 

 

Use cable with an outer diameter between 4.5 and 7 mm. 

 

 

 

 

 

 

Legend for fig. 1 to fig. 6 

I

0

 

Output current 

U

B

 

Load 

 

Grounding 

U

0

 

Output voltage 

R

L

Auxiliary power 

Fig. 1: Connecting with current output 4 ... 20 mA and plug connector per  

EN 175301-803-A 
Connection: 1 (+) 2 (-) 

I

O

U

B

R

L

1+

+

2-

1
2

 

Fig. 2: Connect with 4 ... 20 mA current output and round connector as per  

DIN EN 60130-9 
Connection: 1 (+) 3 (-) 

+

U

B

R

L

I

O

3-

1+

1

2

3

 

Fig. 3: Connecting with current output 4 ... 20 mA and firmly attached cable. 
Connection: 1 (+, brown) 2 (-, green) 

U

B

R

L

I

O

2-

1+

+

 

Fig. 4: Connecting with voltage output 0 ... 5 / 0 ... 10 V DC and plug connector per 

EN 175301-803-A 
Connection: 1 (+U

B

) 2 (U

0

) 3 (-) 

+

U

B

R

L

U

O

1+

3-

1

2

3

2+

 

Fig. 5: Connect with 0 to 5 / 0 to 10 V DC current output and round connector as per 

DIN EN 60130-9 
Connection: 1 (+U

B

) 2 (-) 3 (U

0

)  

+

U

B

R

L

U

O

1

2

3

1

2

3

 

Fig. 6: Connecting with voltage output 0 ... 5 / 0 ... 10 V DC and firmly attached cable 
Connection: 1 (+U

B

, brown) 2 (-, white) 3 (U

0, 

green)  

+

U

O

U

B

R

L

1+

2-

3+

 

 
 
 

 

Summary of Contents for SITRANS P250

Page 1: ... 0 to 5 V DC or 0 to 10 V DC three wire technology Installation The location of the device has no influence on the precision of the measurement Before installation compare the process data with the data of the rating plate The medium being measured must be suitable for the parts of the pressure transmitter in contact with the medium The burst pressure must not be exceeded The following operating c...

Page 2: ...Stabilizing valve Mounting Electromagnetic compatibility Interference immunity Test standard Effect Electrostatic discharge ESD EN 61000 4 2 8 kV air 6 kV contact No failure High frequency electromagnetic irradiation HF EN 61000 4 3 3 V m 80 MHz to 3 GHz No influence Grid bound HF EN 61000 4 6 10 V 0 15 to 80 MHz No influence Quick transient burst EN 61000 4 4 2 kV No failure Power surge EN 61000 ...

Page 3: ... Cable 1 5 m Process connection Hose tailpiece Ø 4 mm 6 mm Pipe union Ø 6 mm 8 mm Male thread 7 16 20 UNF G1 8 Female thread 1 8 27 NPT standard G1 8 Material of the wetted parts Process connection Stainless steel 1 4305 AISI 303 CuZn nickel plated Diaphragm Ceramics Al2O3 96 Sealant FPM standard EPDM NBR MVQ CR Auxiliary power UH Terminal voltage on pressure transducer 2 wire 4 20 mA 11 33 VDC 3 ...

Page 4: ...nless steel 1 4305 AISI 303 8 a 12 b 14 26 67 L a 1 8 27 NPT G1 8 Female thread G1 8 stainless steel 1 4305 AISI 303 a 14 12 53 6 a 10 b 12 24 65 a b L 1 8 27 NPT Pipe union with screw in nipple for pipe external CuZn vni 8 a 12 b 14 25 66 4 20 61 a L 1 8 27 NPT Hose connection for hose CuZn vni stainless steel 1 4571 AISI 316TI 6 a 10 b 10 25 66 L b a 1 8 27 NPT Male thread G1 8 CuZn vni a 10 b 1...

Page 5: ...lossen werden Das Ausgangssignal beträgt wahlweise 4 bis 20 mA Zweileitertechnik 0 bis 5 V DC oder 0 bis 10 V DC Dreileitertechnik Montage Die Lage des Geräts hat keinen Einfluss auf die Messgenauigkeit Vergleichen Sie vor der Montage die Prozessdaten mit den Daten des Typschilds Der Messstoff muss für die messstoffberührten Teile des Druckmessumformers geeignet sein Der Berstdruck darf nicht über...

Page 6: ...auen Elektromagnetische Verträglichkeit Störfestigkeit Prüfnorm Auswirkung Elektromagnetische Entladung ESD EN 61000 4 2 8 kV Luft 6 kV Kontakt Kein Ausfall Hochfrequente elektromagnetische Einstrahlung HF EN 61000 4 3 3 V m 80 MHz 3 GHz Keine Beeinflussung Leitungsgebundene HF EN 61000 4 6 10 V 0 15 80 MHz Keine Beeinflussung Schnelle Transienten Burst EN 61000 4 4 2 kV Kein Ausfall Stoßspannung ...

Page 7: ...ten Prozessanschluss Schlauchstutzen Ø 4 mm 6 mm Rohrverschraubung Ø 6 mm 8 mm Außengewinde 7 16 20 UNF G1 8 Innengewinde 1 8 27 NPT Standard G1 8 Werkstoff der messstoffberührten Teile Prozessanschluss Edelstahl 1 4305 AISI 303 CuZn vernickelt Membrane Keramik Al2O3 96 Dichtmaterial FPM Standard EPDM NBR MVQ CR Hilfsenergie UH Klemmenspannung am Druckmessumformer 2 Leiter 4 20 mA DC 11 33 V 3 Lei...

Page 8: ...lstahl 1 4305 AISI 303 8 a 12 b 14 26 67 L a 1 8 27 NPT G1 8 Innengewinde G1 8 Edelstahl 1 4305 AISI 303 a 14 12 53 6 a 10 b 12 24 65 a b L 1 8 27 NPT Rohrverschraubung mit Einschraubnippel für Rohr außen CuZn vni 8 a 12 b 14 25 66 4 20 61 a L 1 8 27 NPT Schlauchanschluss für Schlauch CuZn vni Edelstahl 1 4571 AISI 316TI 6 a 10 b 10 25 66 L b a 1 8 27 NPT Außengewinde G1 8 CuZn vni a 10 b 12 20 61...

Reviews: