Pressure Transmitter LHCR-51, LHCS-51
Operation
User-definable parameters
Example: setting "Set URV" parameter from 100 mbar (1.5 psi) to 50 mbar (0.75 psi).
Local display
Operation
The local display shows the parameter to be changed. The
value highlighted in black can be changed. The "mbar" unit is
specified in another parameter and cannot be modified here.
1. Press "+" or "–" to get to the editing mode.
2. The first digit is highlighted in black.
1. Use "+" to change "1" to "5".
2. Confirm "5" with "E". The cursor jumps to the next position
(highlighted in black).
3. Confirm "0" with "E" (second position).
The third position is highlighted in black and can now be
edited.
1. Switch to the "
↵
" symbol with the "-" key.
2. Use "E"
to save the new value and exit the editing mode.
→
See next graphic.
The new value for the upper range value is 50.0 mbar
(0.75 psi).
• You exit the edit mode for the parameter with "E".
• You can get back to the editing mode with "+"
or "–".