HART Multiplexer System KFD*-HM*-16
Diagnosis and fault elimination
DO
C
T-0
120D
06/
2014
54
The following response codes can occur on the Multiplexer:
Code Description
Meaning
Can occur with
commands ...
2
Invalid selection
The selected code/index is not permissible.
147, 149, 151, 153
3
The parameter value was too
large
59, 129, 155
4
The parameter value was too
small
59
5
Too few data bytes received
The message has no error, but it contains
fewer bytes than expected for the execution of
the command.
17, 18, 59, 129 ... 141,
145, 147, 149, 151,
153, 154, 155, 157
8
Warning
Here (132): Preamble length not within range
5 ... 20 and has been set to 5 or 20.
132
9
1st parameter too large
The first of the two parameters is too large.
145
11
2nd parameter too large
The second of the two parameters is too large.
145
16
Access restricted
The command has been ignored, since the
current device status does not permit the
command to be carried out correctly.
6, 17, 18, 38, 41, 42,
48, 59, 106, 128 ... 157
17
Too many items requested
131, 132, 133,
135 ... 141, 154
31
Warning
Here (137): SCAN value has not been
changed, since it is identical.
137
32
Busy
The device is executing a function, which
cannot be interrupted by this command.
6, 17, 18, 38, 41, 42,
59, 106, 128,
130 ... 157
64
Command not implemented
The command does not exist and therefore
cannot be executed.
This error message is also output if an error
occurs that cannot be accurately specified by
the device.
almost all
65
Not specified
Parameter not in the permissible range.
132, 137