IUH-F117-V1-*
Commissioning
Single Read Special Read-Only Code
As confirmation, read out the read-only code of the tag within the read/write
head's measurement range via the single read special read-only code command.
see "Single Read Special Read-Only Code SS" on page 31.
Parameterizing the Read/Write Head
Setting and Requesting the Transmission Power
Read out the read/write head's transmission power with the read parameter PT
command:
The read/write head's set transmission power is 2000 mW (7D0
hex
corresponding
to 2000
dec
).
Change the transmission power of the read/write head to 500 mW (500
dec
corresponding to 1F4
hex
) via the write parameter PT command:
Serial
Ethernet
PROFIBUS
Command:
SS10
.00.04.0A.02
.0A.02
Confirmation:
-
.00.06.0A.02.FF.2F
.0A.02.FF.2F
Response:
.30.31.34.00.1
1.22.33.44.55.
66.77.88.99.AA
.BB.CC
.00.14.0A.02.00.48.34.0
0.11.22.33.44.55.66.77.
88.99.AA.BB.CC
.0A.02.00.48.34.00.11.2
2.33.44.55.66.77.88.99.
AA.BB.CC
Table 6.4
Single read special read-only code, tag is in the measurement range
Serial
Ethernet
PROFIBUS
Command:
RP1UPT.00.00
.00.09.BE.03.00.55.50.5
4.00.00
.BE.03.00.55.50.54.00.0
0
Confirmation:
-
.00.06.BE.03.FF.3E
.BE.03.FF.3E
Response:
.30.31.07.D0
.00.08.BE.03.00.3F.07.D
0
.BE.03.00.3F.07.D0
Serial
Ethernet
PROFIBUS
Command:
WP1UPT.00.02
.01.F4
.00.0B.BF.03.00.55.50.5
4.00.02.01.F4
.BF.03.00.55.50.54.04.0
0.02.01.F4
Confirmation:
-
.00.06.BF.03.FF.11
.BF.03.FF.11
Response:
.30.31
.00.06.BF.03.00.12
.BF.03.00.12