201
8-0
5
26
F99 Fusion Inertial Measurement Unit IMU360D-F99-B20
Example
6.2
Factory reset
The following steps describe how to reset the sensor to the factory default settings:
Step 1: Starting Parameter Mode
See also chapter "Starting Parameter Mode"
xx: unused, bytes optional
Effect
Parameter Mode is started.
■
Message: D0 = Password accepted (see also chapter "J1939 Interface Description",
section "Answer Messages").
■
Yellow LED blinks
■
No more PDOs are sent
Step 2: Send command factory reset
xx: unused, bytes optional
Effect
New parameter is acknowledged.
■
Message: D0 = parameter successfully written or read (see also chapter "J1939 Interface
Description", section "Answer Messages").
■
Yellow LED blinks
■
No more PDOs are sent
Identifier
Data Bytes
Priority
PGN
Source
address
1
CMD
2
Password
3
4
5
6
7
8
0x00
0xEF80
0x01
0xEB
(CMD: Start
parameter
mode)
0x55
xx
xx
xx
xx
xx
xx
Table 6.4
Identifier
Data Bytes
Priority
PGN
Source
address
1
CMD
2
Index
3
4
5
6
7
8
0x00
0xEF80
0x01
0xE2
(CMD:
Factory
reset)
0x00
(CMD:
Factory
reset)
xx
xx
xx
xx
xx
xx
Table 6.5