Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Planning
SILCL and PL application
•
The standards IEC/EN 62061 and EN/ISO 13849-1 require that the safety device
is implemented according to the idle current principle. As the device is implemented
following the working current principle, no safety classification according
to IEC/EN 62061 and EN/ISO 13849-1 was carried out. If you use the device
in machinery safety applications, assess the specific application and show
that an equivalent safety level will be achieved.
3.3
Safety Function and Safe State
Safety Function
The safety function of the device is defined: Whenever the input of the device is energized,
the ETS output is conducting.
Safe State
In the safe state of the safety function the ETS output is closed (conducting).
Reaction Time
The reaction time is < 150 ms.