Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Operation
20
21
-1
0
19
Only if all tests are successfully done, the proof test is successful.
Test No.
Input or Test Input
Output (mA)
1
V
Test
= 24 V DC
between terminals 3b+ and 3a-
•
ETS output (terminals 1a, 5a): shows < 10
•
LED TST is flashing
2
V
Test
= 24 V DC
between terminals 4a+, and 3a-
•
ETS output (terminals 1a, 5a): shows < 10
•
LED TST is flashing
3
V
Test
= 24 V DC
between terminals 4b+ and 3a-
•
ETS output (terminals 1a, 5a): shows < 10
•
LED TST is flashing
4
V
Test
= 24 V DC
between terminals 4a+, 3b+, 4b+, and 3a-
•
ETS output (terminals 1a, 5a): shows < 10
•
LED TST is flashing
5
V
Test
= 0 V DC
between terminals 4a+, 3b+, 4b+, and 3a-
•
ETS output (terminals 1a, 5a): OL
(overload)
•
LED TST is off
6
V
input
= 24 V DC
between terminals 8a+ and 7a- with regular
input polarity
•
ETS output (terminals 1a, 5a): shows < 10
•
LED OUT is on
Table 5.4 Expected test results for the proof test of HiC5863Y1