2
02
1-
10
18
Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Operation
Test No.
Input or Test Input
Output (mA)
1
V
Test 1
= 24 V DC
between terminals 7+ and 8-
•
ETS output (terminals 1, 2): shows < 10
•
LED TST is flashing
2
V
Test 2
= 24 V DC
between terminals 9+ and 8-
•
ETS output (terminals 1, 2): shows < 10
•
LED TST is flashing
3
V
Test 3
= 24 V DC
between terminals 10+ and 8-
•
ETS output (terminals 1, 2): shows < 10
•
LED TST is flashing
4
V
Test
= 24 V DC
between terminals 7+, 9+, 10+ and 8-
•
ETS output (terminals 1, 2): shows < 10
•
LED TST is flashing
5
V
Test
= 0 V DC
between terminals 7+, 9+, 10+ and 8-
•
ETS output (terminals 1, 2): OL (overload)
•
LED TST is off
6
V
input
= 24 V DC
between terminals 5+ and 6- with regular input
polarity
between terminals 5- and 6+ with inverted input
polarity
•
ETS output (terminals 1, 2): shows < 10
•
LED OUT is on
Table 5.2 Expected test results for the proof test of KCD0-RSH-1.1E.1
Test No.
Input or Test Input
Output (mA)
1
V
Test
= 24 V DC
between terminals 3b+ and 3a-
•
ETS output (terminals 5a, 5b): shows < 10
•
LED TST is flashing
2
V
Test
= 24 V DC
between terminals 4a+, and 3a-
•
ETS output (terminals 5a, 5b): shows < 10
•
LED TST is flashing
3
V
Test
= 24 V DC
between terminals 4b+ and 3a-
•
ETS output (terminals 5a, 5b): shows < 10
•
LED TST is flashing
4
V
Test
= 24 V DC
between terminals 4a+, 3b+, 4b+, and 3a-
•
ETS output (terminals 5a, 5b): shows < 10
•
LED TST is flashing
5
V
Test
= 0 V DC
between terminals 4a+, 3b+, 4b+, and 3a-
•
ETS output (terminals 5a, 5b): OL
(overload)
•
LED TST is off
6
V
input
= 24 V DC
between terminals 8a+ and 7a- with regular
input polarity
•
ETS output (terminals 5a, 5b): shows < 10
•
LED OUT is on
Table 5.3 Expected test results for the proof test of HiC5863