Troubleshooting and Diagnosis
5.2
Recommended Action for Field Diagnostics according to NE 107
5.3
Resource Block
Alarm Type
Diagnostic Event
Alarm Text String
Maintenance required
Configuration error
Check blocks for configuration
error.
Stroke counter exceeded
Check transducer blocks for
more details.
Valve maintenance
Failed
Valve failure
Sensor lead fault
Valve lead fault
Device failure
Send the device to
Fuchs for repair.
Function Check
Check
Check block modes according
to normal mode.
Problem
Troubleshooting
Parameter
Message
Cause
Solution
BLOCK_ERR Lost Static
Data
The parameterization data
stored in the device were
faulty and replaced by the
default settings.
Repeat parameterization. If
this error occurs repeatedly,
send the device to
Fuchs for repair.
Device
Maintenance
Hardware error.
Send device to
Fuchs for repair.
Simulation
Switch 1 is set to "Simulation
enabled".
Check if the simulation setting
was intended.
OOS
The target mode of the block
is OOS.
Set block to "Auto" mode.
RS_STATE
Online
No error.
Failure
Hardware error.
Send device to
Fuchs for repair.
Stand-by
The target mode of the block
is OOS.
Set block into "Auto" mode.
Online Linking One or several communication
links to other field devices are
not established.
Check whether all necessary
field devices are available at
the segment.
Check configuration.