IO-Link Parameterization
6.3
SSC1 Param. SP2
Switching Signal Channel 1 Parameter. Setpoint 2
The "SSC1 Param. SP2" parameter is used to set a critical limit value for "SSC1."
The permissible value range of the "SSC1 Param. SP2" parameter is independent of "SSC1
Param. SP1." see chapter 6.2 for a comparison.
The figure below uses an example to illustrate the relationship between SP1 and SP2.
Figure 6.3
The general rule for switch points SP1 and SP2 is that
switch points SP1 and SP2 can be set independently of each other:
•
SP1 can be greater than SP2.
•
SP1 can be smaller than SP2.
•
SP1 can be equal to SP2.
Index
Sub
Parameter
Access
Data Type
Length
64 (0x40)
2
SSC1 Param. SP2
rw
Integer
32 bits
SP2
= 900
SP1
= 100
0
shaft
Switch
Switch
Index
Parameter
Value
0x40 Sub 1 SSC1 Param. SP 1
100
0x40 Sub 2 SSC1 Param. SP 2
900
0x60
Config-ST Resolution
1000