NO WATER
(DRY RUN COSPHI)
Motor cosphi is lower than the set value of
dry running cosphi
Check if the pump is primed
Check the set value of dry running cosphi.
Dry running cosphi is approximately 60% of
the rated cosphi (at rated frequency) listed
on the motor plate.
If pump’s cosphi is lower than the set dry-
running cosphi for at least 2 seconds, IPFC stops
the pump. IPFC tries to run the pump every
10, 20, 40, 80, 160 minutes and then the pump
is stopped.
WARNING: if dry running protection occurs,
IPFC will try to start the pump automatically. Be
sure to cut power supply to IPFC before
performing any maintenance.
SENSOR FAULT
Sensor error
Check the transducer
Check the wiring of transducer
MAX. VALUE ALARM
Measured value has reached the maximum
value accepted by the system.
Check possible causes of reaching max
value
Check the max alarm value setting
MIN. VALUE ALARM
Measured value has reached the lowest
value accepted by the system.
Check possible causes reaching min value
(i.e. broken pipe, open pressure relief valve,
etc.)
Check the min alarm value setting.
IGBT TRIP ALARM
The current drawn by the load exceeds the
capacity of IPFC.
IPFC is still able to continue to power the
load for 10 minutes with an output current
of 101% of nominal and for 1 minute with
an output current of 110% of nominal
Increase the ramp-up time
Make sure that the load current is at least
10% below the IPFC nominal current
Check the voltage drop along the supply
cable to the motor
NO
COMMUNICATION
Communication between Master and
slave(s) has been interrupted
Check the wiring connections
Make sure the Master is not in the Menu
level; if so, exit from the level.
In the STATUS of the slave (where the alarm
is displayed) try to reset the alarm by
pushing STOP button.
ADDRESS ERROR
Same address as other IPFCs in the group
The address of each IPFC needs to be
different
KEYBOARD FAULT
A Button on the keyboard has been
pressed for more than 150 seconds
Make sure buttons are not depressed
Call service assistance
ACTIVE DIG.IN.X
Digital input X opened /closed
Check the input digital configuration
(IN/OUT Parameters menu )
ALARM SLAVE XX
slave XX error detected by master
check the status of the slave
Summary of Contents for IPFC 109
Page 1: ...Operating manual IPFC manIPFC_eng_30 ...
Page 41: ...Manuale d installazione ed uso IPFC manIPFC_ita_30 ...
Page 85: ...Betriebsanleitung IPFC manIPFC_deu_30 ...
Page 126: ...42 BEMERKUNGEN ...
Page 127: ...43 ...
Page 129: ...Manual de instrucciones IPFC manIPFC_esp_30 ...
Page 170: ...42 NOTE ...
Page 171: ...43 ...
Page 173: ...Notice d utilisation IPFC manIPFC_fra_30 ...
Page 214: ...42 REMARQUES ...
Page 215: ...43 ...