V / f characteristic with which IPFC feeds the engine. The linear
characteristic corresponds to constant torque with variable speed. The
quadratic characteristic is normally used with centrifugal pumps. The
selection of torque characteristic should be done ensuring a smooth
operation, a reduction of energy consumption and a lower level of heat
and acoustic noise.
--->
If, during the test, the motor runs in reverse, it is possible to change the
wiring sequence via software without physically changing wires at the
terminals.
If the device is "FOC-ready", motor calibration must be carried out
before commissioning.
Carefully read the pertinent chapter.
Manual setting of the stator resistance.
Manual setting of the stator inductance.
Setting of the control dynamic of the FOC algorithm.
OFF
If ON is selected, after a lack of voltage, IPFC returns to its normal
status; if IPFC was powering the pump before the voltage drop, it
resumes powering the pump automatically.
Warning, review the advice in chapter 1.
V/f lin. --> quad.
XXX [%]
V nom mot
V
f
f nom mot
f min mot
V boost
Rotation sense
---> / <---
MOTOR TUNING
press ENT
Mot. resistance
Rs=XXX.XX [Ohm]
Mot. inductance
Ls=XXX.XX [mH]
FOC dynamic
XXX
Autorestart
ON/OFF
Summary of Contents for IPFC 109
Page 1: ...Operating manual IPFC manIPFC_eng_30 ...
Page 41: ...Manuale d installazione ed uso IPFC manIPFC_ita_30 ...
Page 85: ...Betriebsanleitung IPFC manIPFC_deu_30 ...
Page 126: ...42 BEMERKUNGEN ...
Page 127: ...43 ...
Page 129: ...Manual de instrucciones IPFC manIPFC_esp_30 ...
Page 170: ...42 NOTE ...
Page 171: ...43 ...
Page 173: ...Notice d utilisation IPFC manIPFC_fra_30 ...
Page 214: ...42 REMARQUES ...
Page 215: ...43 ...