3. parameters
The first parameter to show up during Set-up mode is the Set Point.
Other parameters, their default, minimum and maximum values are
shown in the below table:
parameter
Default
value
Displayed
code
min.
max.
Set Point (°C)
3
0
30
Min. Expected Ambient
1
(°C)
-20
-30
0
Pipe Size
2
1
1
3
Heater Operation if Sensor Error
1
0 (OFF) 1 (ON)
Voltage Free Operation
0
0 (NO) 1 (YES)
1
Min. Expected Ambient Temp. is the temperature whereby the heating
cable is energized for 100%.
Min. Expected Ambient Temp. can only be set in steps of 10 K.
Min. Expected Ambient = Low Temp. Alarm.
2
Select Pipe Size Diameter:
3 for pipes ≥ 2 inch.
2 for pipes ≥ 1 inch.
1 for pipes < 1 inch.