background image

5

For example, assume that the test 

is enabled with a START TEST 

time of 15 seconds.  When a pump 

is called a timer is started for that 

pump.    If  the  timer  reaches  15 

seconds and the AUX/DIS input 

for that pump has not been shorted 

to ground then a fail to start test 

failure is set for that pump.  The 

pump is then disabled and the 

next available pump is called in 

its place.  This failure condition 

is displayed on the front panel 

and will remain active until reset 

by either a reset button or reset 

input.  The high level alarm will 

also reset this condition.  This 

is to make sure that a broken or 

misadjusted check valve switch 

does not cause an overflow.

Pump Up 

Operation

Pump up mode is used in 

situations, like water distribution, 

where the pumps must maintain 

a pressure or fill a tank (like a 

water tower).  For the purposes of 

this description assume we have 

three pumps which will be used to 

maintain the level in a water tank.  

The level is sensed by a pressure 

transmitter mounted in the base of 

the tank and all three pumps send 

water to the tank.
As water is dispensed from the 

tank the level drops.  If the level 

drops far enough to reach the lead 

on setpoint then the lead pump is 

called to run.  This should cause 

the level to rise until the lead off 

setpoint is reached and the pump 

is shut down.  If the alternator 

is on then the lead pump will be 

sequenced to the next available 

pump.  If the level continues to 

fall then the lag on setpoint will 

be reached and the lag pump will 

be called.  As in pump down 

operation each pump has separate 

on and off setpoints and there are 

setpoints for high and low alarm.  

Unlike pump down the pump up 

mode does not have a float backup 

system.

Pump               

Alternation                           

The NOVUS 4000 has an automatic 

alternation system which can be 

used to cause a different pump to 

be used each pump cycle.  This 

is useful to equalize pump wear.  

When the alternator is off the lead 

pump can be selected and that 

pump will always be called first.  

The alternator on the NOVUS 

4000 is controlled by a toggle 

switch on the front panel.  When 

the switch is in the up position 

the alternator is on and the lead 

pump will be changed each cycle.  

When the switch handle is in the 

center position the alternator is 

off and the lead pump is selected 

by pushing the handle down.  The 

handle has a spring return from 

the down position.  Each time the 

handle is pushed down the lead 

pump will be incremented to the 

next available pump.  The current 

lead pump is displayed on the right 

side of the first line of the display 

(LP=2).  
For systems with two pumps, 

alternation, if on, simply swaps 

lead pump duty between the two 

pump each pump cycle.  If there 

are three pumps, alternation can be 

either of two options.  In normal 

alternation of each pump cycle the 

next available pump is selected 

as lead so that if all pumps are 

available then each will be lead 

every third time.  The other option 

is jockey pump.  In this type of 

system  pump  1  is  a  small  pump 

and pumps 2 and 3 are large.  The 

small  pump  (pump  1)  is  always 

the lead pump and the other two 

pumps alternate.  When either of 

the two large pumps is on the 

small one is turned off.  This is 

useful in systems where demand 

can be low at some times and large 

at others.

Pump                     

Startup

When the NOVUS 4000 is first 

powered up it executes an internal 

self test.  During this test many 

internal functions are checked and 

the displays are sequenced.  The 

system is controlled by an internal 

microcomputer which is monitored 

by a watchdog timer system which 

will restart the system in the 

unlikely event that the program 

fails to execute properly.  After 

the self test is complete several 

timers are started which prevent 

any relay outputs from activating 

until all of the system inputs have 

had a chance to settle and all of the 

input filtering has resolved to their 

proper values.

Front Panel 

Indicators & Controls

Figure  1  is  a  view  of  the  front 

panel of the NOVUS 4000.  It 

includes eight LED lamps, a 32 

character  LCD  display,  5  push 

buttons, one toggle switch and one 

adjustment knob.  They have the 

following functions:
  1. PUMP 1 THRU PUMP

   3 LAMPS
   These three green LED lamps 

indicate which pump is 

currently being called.

 2. OFF LAMP
   This green lamp indicates that 

no pumps are currently called 

to run.

Summary of Contents for Hydromatic Novus 4000

Page 1: ... provide this manual to the owner of the equip ment or to the responsible party who maintains the system NOVUS 4000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Item H 03 518 Part 5625 518 1 2012 Pentair Pump Group Inc 11 02 12 ...

Page 2: ...ler so no wires need to be disconnected Unpacking Panel Remove panel from carton When un pack ing unit check for con cealed damage Claims for damage must be made at the receiving end through the delivery carrier Dam age cannot be processed from the factory Pump Features 32 character alpha numeric liquid crystal display for level status and setpoint information Alternation selector switch on front ...

Page 3: ...tion repair or service with re gard to the control panel refer to the schematic appropriate for that panel The schematic will provide guidance with regard to the terminal block con nec tions CAUTION A nonmetallic enclosure does not provide grounding conduit con nec tions Use grounding bush ing and jumper wires Make the Following Electrical Con nec tions a Connect the pump leads to the control pane...

Page 4: ...pumps are selected for the maximum number of pumps If the level continues to rise then it will reach the high alarm setpoint and set a high alarm condition The high alarm light and relay will be activated If the horn is enabled then it too will be activated until the alarm condition clears or until the mute button is depressed Single Float Backup A single float backup system is provided in pump do...

Page 5: ...oggle switch on the front panel When the switch is in the up position the alternator is on and the lead pump will be changed each cycle When the switch handle is in the center position the alternator is off and the lead pump is selected by pushing the handle down The handle has a spring return from the down position Each time the handle is pushed down the lead pump will be incremented to the next ...

Page 6: ...UTTON This button will reset any current latched up alarms such as temp fail or on floats It will also silence the horn if an alarm is currently active 12 TEST ADJUST BUTTON AND KNOB The function of these two operators depends on the mode of the controller When the controller is in the normal not menus mode these operators are used to test the system When the TEST button is depressed and held the ...

Page 7: ...ill take about 10 seconds 2 The display should say MAX LEVEL XX X FT where XX X is the current value This parameter is the level when the level transmitter is at 20 Ma full scale For example if the transducer is a 10 psig submersible pressure transducer then 10 psi is 23 1 feet so adjust this value to 23 1 3 If no change to this setting is required then press the MENU NEXT button To change this va...

Page 8: ...d must be cleared by the MUTE RESET button SEAL INVR AUTO R In this mode the seal fail input is set to cause a failure if the resistance to ground is greater than 2000 ohms and the alarm will auto reset if the alarm condition clears SEAL INVR LATCH In this mode the seal fail input is set to cause a failure if the resistance to ground is greater than 2000 ohms and the alarm will latch up and must b...

Page 9: ...lack and Red pow er wires are con nect ed to pan el correct ly 3 WARNING Live voltage can kill Check incoming power volt age to make sure that it is correct for panel and pump model 4 Energize control panel Turn on power to panel 5 Check overload relay and verify reset mode if overload is sup plied 6 WARNING Live voltage can kill Check voltage to the panel and at secondary of control trans form er...

Page 10: ...and secondary If required 2 Contactor 3 Bulbs for any light requiring a bulb 4 Control transformer If required 5 Alternator relay If required Seal Fail Inputs Each pump has an input for the seal fail moisture sensor commonly found in submersible pumps The controller measures the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 2000 ohms One...

Page 11: ...c E Severe humming chat ter ing of contactors and control relays 1 There may be low voltage Check voltage at primary and secondary of control transformer us ing a volt me ter This low voltage condition may cause severe chat ter ing and burnout of contactors and relays 2 Contactor may have dust around magnet of coil struc ture Dry or clean as re quired 3 Check voltage to the control panel Contactor...

Page 12: ...te to Highest Red Main Start c Capacitor check Make sure the ca pacitor is dis charged Use extreme caution as a spark might occur Disconnect the ca pac i tor leads and connect an analog type volt ohmmeter to the capacitor terminals Set the meter on the RX1 000 scale to check the start ca pacitor Set the meter on the RX10 000 scale to check the run ca pac i tor The meter should in di cate low ohms ...

Page 13: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 16: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Reviews: