Installer manual Fleck 2850 SXT - Programming
54 / 104
Ref. MKT-IM-030 / C - 12.05.2020
Parameter
Options
Definition
Note
B1
First backwash
0 to 199
Minute
Only displayed for dF2b regeneration
flow. In case of dF1b regeneration
flow, the screen shows BW.
BD
Brine draw
BD consist of time for brine draw and
slow rinse.
B2
Second
backwash
Only shown in dF2b regeneration flow.
RR
Rapid rinse
-
BF
Brine fill
0 to 199
Minute
-
BW
Backwash
-
Rn
Cycle number
n=1 to 6
Only if "Othr" is chosen under
VT
. R1,
R2, R3, etc... will be displayed instead.
Dn
Day of week,
n=1 to 7
ON - OFF
-
Regeneration setting for each day of
the week. OFF by default.
Not available for 9000 serie valves.
CD
Current day
1 to 7
Day of the week
Not available for 9000 serie valves
FM
Flow meter type
P0.7
¾" paddle wheel -
t0.7
¾" turbine
-
P1.0
1" paddle wheel
-
t1.0
1" turbine
-
P1.5
1½" paddle wheel -
t1.5
1½" turbine
-
P2.0
2" paddle wheel
-
Gen
Generic or
non-Fleck
-
K
Meter pulse
0.1 to 999.9
Litre
Only displayed for generic flow meter
type.
6.5.2
Entering master programming mode
1. Press and hold
or
until the programming icon replaces the
service icon and the parameter display reads TD.
2. Set the time to 12:01 PM with
or
.
3. Press
to validate the selection and return to the service mode, or wait
for 10 seconds.
4. Press and hold
and
for 5 seconds until the programming icon
replaces the service icon and the display format screen appears.