background image

To Advance Regeneration Cycles:

• 

Press and hold SET - showing current cycle time.

• 

Simultaneously press SET and UP to advance on cycle. An 

hourglass will display while cam is advancing. When cam 

reaches next cycle, "C2” will be displayed.

• 

Repeat SET and UP to advance through each cycle.

• 

Press and hold SET and UP for 5 seconds to cancel 

regen. Hourglass will flash once cancelled. Camshaft will 

advance to home – may take 1 to 2 minutes.

Regeneration Cycles:

• 

 C1 – Backwash

• 

C2 – Regeneration Draw/Slow Rinse (not used in  

filter mode)

• 

C3 – Slow Rinse (not used in filter mode)

• 

C4 – System Pause (to repressurize tank)

• 

C5 – Fast Rinse cycle 1

• 

C6 – Backwash cycle 2

• 

C7 – Fast Rinse cycle 2

• 

C8 – Regenerant Refill (not used in filter mode)

For system start-up procedure, including: purging the mineral 

tank, refilling the regenerant tank, and drawing regenerant, 

see the system start-up procedure in the Dealer Installation 

and Service Manual.

Programming The 700 For FA Filter Applications

Sizing FA Filters

Potassium permanganate regenerating iron filters should be 

sized for the appropriate backwash and injector sizes.

Backwash Controller

Be sure to choose the appropriate backwash flow rate control 

(see Parts section) as recommended by your  

media manufacturer.

Injector

Use the same injector size as you would for your conditioner 

control tank diameter.

Refill Controller

A FA filter can use the 0.33 gpm refill control that is featured 

as standard with a Logix controller. Use a check valve in your 

potassium permanganate feeder to prevent overflow.

Initial Resin Volume Setting

Programming for a manganese greensand system requires 

a few minor adjustments to the programming to operate 

the control correctly. The initial resin volume should be set 

to the closest volume of the manganese greensand in the 

system. For example, if the system contains two cubic feet of 

manganese greensand, program in 2.00 for the resin volume.

"Salt" Setting for KMNO

3

 Regenerant

Since the same injector is used for the filter application (FA) 

system and the conditioner system, be sure the regenerant 

(salt) setting is set to High “H” to allow adequate time to rinse 

the media.
All other settings will remain the same as mentioned in the 

previous programming sections.

Days Between Regeneration Setting (740 FA)

To set the days between regenerations, consult the media 

manufacturer for the actual capacity of the media.
In general, manganese greensand has a capacity of 10,000 

ppm of removal capability per cubic foot of media. Calculate 

the capacity of the system by taking the number of cubic feet 

of media and multiply by 10,000.
For example, using a 1 cubic foot system provides 10,000 ppm 

of removal capability.
The next step is to calculate the demand for the system. Multiply 

the predicted daily water usage by the iron content in ppm.
For example, an average person uses 75 gallons of water per 

day. Four people living in a home use 300 gallons of water (75 

gallons x 4 people) per day. Assume the incoming water has 

10 ppm of iron. Now calculate the daily demand: multiply the 

gallons of water used per day (300) by the ppm of iron content 

(10) = 3000 ppm of daily capacity usage.
Now take the system capacity (10,000), divided by the daily 

demand (3,000) = 3.3 days of capacity. Since you will run out 

of capacity before the beginning of the fourth day, the proper 

setting for days between regeneration is 3 days.
For example:

4 people x 75 gallons per person = 300 gallons used per day.
10 ppm iron x 300 gal/day = 3000 ppm/day
10,000 ppm capacity ÷ 3000 ppm/day = 3.3 days of total capacity
Solution = regenerate every 3 days.

Volume/Demand Regeneration Setting

To set a 760 demand system for iron removal you must:
1.  Know your media capacity. Generally, one cubic foot of 

magnesium greensand can remove 10,000 ppm of iron.

2.  Know the iron concentration in your water.
To have your system regenerate on demand, set your system’s 

capacity (P7) to the appropriate factor. On the 760, it will read 

Kg, but you will actually be working in ppm of iron.

Time & Day

Regen Time & Day

Salt Amount

SU MO TU WE TH FR SA DAYS

Capacity

Hardness

KG

Time & Day

Regen Time & Day

Salt Amount

SU MO TU WE TH FR SA DAYS

Capacity

Hardness

1.  If your system is one cubic foot, set the capacity to "10" kg, 

meaning 10,000. For two cubic feet, set the capacity to  

"20" kg.

2.  Set your hardness to the level of ppm iron in your water. If 

you have 3 ppm of iron, set the 760 control to "3".

3.  The control will calculate the remaining volume capacity in 

gallons (m

3

) and count down to regeneration.

PROGRAMMING 

CONTINUED

 

AUTOTROL

®

 740/760 Control 255 & Performa Series Valves (268, 268FA) Service Manual 

 

21

Summary of Contents for AUTOTROL 740

Page 1: ...AUTOTROL 740 760 CONTROL 255 PERFORMA SERIES VALVES 268 268 FA SERVICE MANUAL www pentairaqua com...

Page 2: ...used on connections that do not use an O ring seal Do not use pliers or pipe wrenches All plumbing must be completed according to local codes Soldering near the drain line should be done before connec...

Page 3: ...port valve outlet to spin the turbine The controller will verify that the turbine works and the self test will finish Proceed with the initial start up procedure Initial Start up Step by step Instruc...

Page 4: ...TH FR SA DAYS Capacity Hardness Low Setting High Efficiency Set desired regenerant amount Default setting is S standard salting 3 salt settings are available on 740 and 760 controls S Standard Salt 9...

Page 5: ...t SET and UP to advance through each cycle Press and hold SET and UP buttons for 5 seconds to cancel regen Hourglass will begin flashing indicating regen is cancelled Camshaft will advance to home may...

Page 6: ...ested and Certified by WQA to NSF ANSI Std 61 Section 8 Mechanical Devices WQA Certified 255 Valve Systems WQA Certified 268 Valve Systems 255 740 075 844 268 740 948 255 740 100 948 268 740 150 1054...

Page 7: ...sted by WQA and conform to NSF ANSI 44 for specific performance claims as verified and substantiated by test data These systems are not intended to be used for treating water that is microbiologically...

Page 8: ...less that 3350 grains of total hardness exchanged per pound of salt based on NaCl equivalency 477 grams of total hardness exchanged per kilogram of salt and shall not deliver more salt than its liste...

Page 9: ...NSI 44 for specific performance claims as verified and substantiated by test data These systems are not intended to be used for treating water that is microbiologically unsafe or of unknown quality wi...

Page 10: ...that 3350 grains of total hardness exchanged per pound of salt based on NaCl equivalency 477 grams of total hardness exchanged per kilogram of salt and shall not deliver more salt than its listed rati...

Page 11: ...er Bypass Flapper Open Cycle C4 This cycle closes the flappers for a short time to allow the air and water to hydraulically balance in the valve before continuing the regeneration 5 Fast Rinse Downflo...

Page 12: ...r 34 F 1 C and below 120 F 49 C Water pressure below 125 psi 8 61 bar and above 20 psi 1 4 bar In Canada the water pressure must be below 100 psi 6 89 bar Constant electrical supply to operate the con...

Page 13: ...itioner Figure 7 Typical Globe Valve Bypass System WARNING The inlet water must be connected to the inlet port of the valve When replacing non Pentair Water valves the inlet and outlet may be reversed...

Page 14: ...Drain Secure hose in place Drain Tubing Overflow Fitting Figure 9 Overflow Line Connection Regenerant Line Connection not used with filter system The regenerant line from the tank connects to the valv...

Page 15: ...play The World controller will sense the input power as 50 or 60 Hz and operate accordingly Controller Location The 700 Series controllers are designed to be mounted on the valve or attached to a flat...

Page 16: ...u ve selected If incorrect setting is programmed see Resetting the Control section below NOTE If the controller was incorrectly set to the wrong valve body press the DOWN button and SET button for fiv...

Page 17: ...acity Hardness System capacity is displayed in total kilograins or kilograms of hardness removed before a regeneration is necessary Value is derived from the system s resin volume input and salt amoun...

Page 18: ...m the line D Do not let the water flow down the line to the tank for more than one to two minutes or the tank may overfill E Once the air is purged from the line press the SET button and the UP button...

Page 19: ...powered up for the first time Variable Reserve Function The 700 Series metered demand volumetric controllers 760 and 760C are designed to have a variable reserve feature This feature automatically ad...

Page 20: ...regenerate button immediately returns the controller to normal operation Programming Conventions The 700 Series controller is programmed using the buttons on the keypad The programming instructions w...

Page 21: ...ious programming sections Days Between Regeneration Setting 740 FA To set the days between regenerations consult the media manufacturer for the actual capacity of the media In general manganese greens...

Page 22: ...cription Range H0 Resin volume initial setting value Cubic feet or liters H1 Days since last regeneration 0 255 H2 Current flow rate 0 47 GPM or 0 177 LPM H3 Water used today in gallons m3 since Time...

Page 23: ...tion Key Duration Display Enter Level II programming UP and DOWN 5 sec P1 display Return to operation UP and DOWN 5 sec Time and day of week Increment through menus UP and DOWN P R Next parameter disp...

Page 24: ...back into one site To install control module Wire Clips Slots for Motor and Turbine Harness 1 Be sure the power is disconnected 2 Check model 3 Check routing of wires and plug them into the controlle...

Page 25: ...le in the hollow of the cup An arrow on the top plate points to the current marking The numbers represent regeneration cycles as follows C0 Treated water normal operation mode C1 Backwash C2 Regeneran...

Page 26: ...This switch is turned on off by a cam lobe on the camshaft Its function is to signal that the unit is in service or out of service regenerating Microswitches are available as kits from Pentair Water o...

Page 27: ...ack further to remove the spring To install spring 7 5 6 6 1 Inspect the spring for damage Do not attempt to repair a bent spring 2 Position yourself on the spring side of the valve discs 3 Position t...

Page 28: ...mpletely into the port cavity 3 The metal portion will be positioned straight up and the top of the shoulder will be level with the valve To install the top plate 1 5 9 13 17 15 11 7 3 4 8 12 16 18 14...

Page 29: ...those sold for commercial laundries adjust the dosage accordingly 1 Dosage F Polystyrene resin 1 2 fluid ounce 35 5 ml per cubic foot G Non resinous exchangers 0 8 fluid ounce 23 7 ml per cubic foot...

Page 30: ...AMS 255 Valve 1 10 8 9 7 6 5 4 3 2 11 18A 19 17A 16 15 14 13 12 20 21 17B 20 18B WARNING Do not use flow control ball with 17B or 18A 30 AUTOTROL 740 760 Control 255 Performa Series Valves 268 268FA S...

Page 31: ...High Efficiency Tan 8 inch tank 1035733 H Injector High Efficiency Lt Purple 9 inch tank 1035734 J Injector High Efficiency Lt Blue 10 inch tank 1035735 K Injector High Efficiency Pink 12 inch tank 10...

Page 32: ...9 Bypass Body Assembly with Install Kit 1040524 Bypass Installation Kit Tube Adapter Kits 1 1001606 3 4 inch Copper Tube Adapter Kit 1 1001670 1 inch Copper Tube Adapter Kit 1 1001608 22 mm Copper Tub...

Page 33: ...ONTINUED Performa Valve 1 10A 8 9 7 6A 5 4 3 2 11 18 19 17 16 15 14 13 12 6B 10B WARNING Do not use the flow control ball with 6B or 10A 11 AUTOTROL 740 760 Control 255 Performa Series Valves 268 268F...

Page 34: ...gpm 34 Lpm 1030360 Drain Line Flow Control 10 gpm 38 Lpm 7 1 3019221 Motor Optical Cable Assembly 8 1 1000226 Screen Cap Assembly w O Ring 9 1 Injector High Efficiency Options 1035730 E Injector HIgh...

Page 35: ...ter Kit 3023824 3 4 inch BSPT SS Pipe Adapter Kit 3023828 1 inch NPT SS Pipe Adapter Kit 3023807 1 inch BSPT SS Pipe Adapter Kit 17 1 1001986 13 16 inch Rubber Insert Optional 18 1 1235446 Turbine Cab...

Page 36: ...cal Components 3019221 Motor Optical Cable Assembly 700 Series Control 60 Hz 2 AC Adapter 1000810 Japanese 1000811 North American 1000812 Australian 1000813 British 1000814 European 1030234 Transforme...

Page 37: ...haft is not turning during ERR 3 display Check that motor is connected Verify that motor wire harness is connected to motor and controller module Verify that optical sensor is connected and in place V...

Page 38: ...er pressure Set pump to maintain 20 psi at softener Restricted drain line Change drain to remove restriction Injector plugged Clean injector and screen Injector defective Replace injector Contact deal...

Page 39: ...nd flush with clean water Turbine should spin freely if not replace meter Contact dealer Regenerant tank overflow Regenerant valve disc 1 being held open by foreign matter Manually operate valve stem...

Page 40: ...Check 1 5 2 4 Valve No 1 Open 2 Closed 3 Closed 4 Open 5 Open 6 Closed Backwash Position Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 3 6 Drain Control 6 Air Check 5 2 4 1 Valve No...

Page 41: ...Tank Drain Inlet Outlet Hard Water Soft Water 5 3 1 2 4 6 Drain Control 6 Air Check Valve No 1 Open 2 Open 3 Open 4 Closed 5 Closed 6 Closed Fast Rinse Position Brine Tank Mineral Tank Drain Inlet Ou...

Page 42: ...en 3 Closed 4 Closed 5 Closed 6 Open 7 Closed Backwash Position Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 5 4 1 3 2 6 7 Backwash Flow Control Valve No 1 Closed 2 Open 3 Closed 4...

Page 43: ...5 B A C K W A S H F L O W C v 1 2 0 LWR 4630 SVC LWR 5236 BW 2 6 4 8 10 12 16 14 0 0 9 1 4 1 8 0 5 0 2 3 2 7 3 2 3 6 1 10 1 00 0 90 0 80 0 70 0 60 0 50 0 40 0 30 0 20 0 10 0 00 16 14 12 10 8 6 4 2 0...

Page 44: ...0 0 20 0 10 0 00 LWR6151 20 2 3 5 5 6 7 5 40 60 80 100 120 Injector H Light Purple For 9 inch Tanks 0 18 0 16 0 14 0 12 0 10 0 08 0 06 0 04 0 02 0 00 m 3 hr 0 80 0 60 0 40 0 20 0 00 LWR6151 20 2 3 5 5...

Page 45: ...AUTOTROL 740 760 Control 255 Performa Series Valves 268 268FA Service Manual 45...

Page 46: ...46 AUTOTROL 740 760 Control 255 Performa Series Valves 268 268FA Service Manual...

Page 47: ...AUTOTROL 740 760 Control 255 Performa Series Valves 268 268FA Service Manual 47...

Page 48: ...s and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair...

Reviews: