background image

STARTUP - 360

The system will now need to be placed into operation. Please 

review "INITIATING A CLEANING CYCLE" on page 7 before 

attempting startup.
1.  With the supply water for the system still turned off, 

position the bypass valve to the “not in bypass” (normal 

operation) position.

2.  Turn the control knob counter-clockwise until the indicator 

arrow on the valve body is lined up with "1" on the control 

knob to start a cleaning cycle. The system will be in 

backwash.

3.  Filling the media tank with water:

A.  With the system in backwash, open the water supply 

valve very slowly to approximately the 1/4 open position. 

Water will begin to enter the media tank. Air will begin 

to be purged to drain as the media tank fills with water.

WARNING:

 If opened too rapidly or too far, media may 

be lost out of the tank into the valve or the 

plumbing. In the 1/4 open position, you should 

hear air slowly escaping from the valve drain 

line.

B.  When all of the air has been purged from the media 

tank (water begins to flow steadily from the drain line), 

open the main supply valve all of the way. This will purge 

the final air from the tank.

C.  Allow water to run to drain until the water runs clear 

from the drain line. This purges any debris from the 

media bed.

D.  Turn off the water supply and let the system stand for 

above five minutes to allow any trapped air to escape 

from the media tank. Turn on the water supply after five 

minutes.

4.  Return the system to normal operation by turning the 

control knob counter-clockwise until the indicator arrow is 

lined up with "0" on the control knob.

The system is now fully operational.

STARTUP - 361

The system will now need to be placed into operation. Please 

review "INITIATING A CLEANING CYCLE" on page 7 before 

attempting startup.
1.  With the supply water for the system still turned off, 

position the bypass valve to the “not in bypass” (normal 

operation) position.

2.  Turn the control knob counter-clockwise until the indicator 

arrow on the valve body is lined up with the Recycle icon 

 to start a cleaning cycle. The system will begin the 

backwash cycle.

3.  Filling the media tank with water:

A.  With the system in backwash, open the water supply 

valve very slowly to approximately the 1/4 open position. 

Water will begin to enter the media tank. Air will begin 

to be purged to drain as the media tank fills with water.

WARNING:

 If opened too rapidly or too far, media may 

be lost out of the tank into the valve or the 

plumbing. In the 1/4 open position, you should 

hear air slowly escaping from the valve drain 

line.

B.  When all of the air has been purged from the media 

tank (water begins to flow steadily from the drain line), 

open the main supply valve all of the way. This will purge 

the final air from the tank.

C.  Allow water to run to drain until the water runs clear 

from the drain line. This purges any debris from the 

media bed.

D.  Turn off the water supply and let the system stand for 

above five minutes to allow any trapped air to escape 

from the media tank. Turn on the water supply after five 

minutes.

The system is now fully operational.

INSTALLATION CHECKLIST

___ Read the owner's/installation manual?
___ Follow all safety guidelines in the manual?
___ If metal pipe was used, did you restore the electrical ground?
___ Securely install both drain hoses to an approved drain?
___ Perform a leak test?
___ Move the bypass valve to service?
___ Start a cleaning cycle?

6 • 

AUTOTROL

 360/361 Filter Valves

Summary of Contents for AUTOTROL 360

Page 1: ...AUTOTROL 360 MANUAL 361 SEMI AUTOMATIC FILTER VALVES SERVICE MANUAL waterpurification pentair com ...

Page 2: ...ording to local codes Soldering of the plumbing should be done before connecting to the valve Excessive heat will cause interior damage to the valve Observe local drain line requirements Do not use lead based solder for sweat solder connections Do not support the weight of the system on the control valve fittings plumbing or the bypass It is not recommended to use sealants on the threads Use plumb...

Page 3: ...m failures Temperature Extreme hot or cold temperatures may cause damage to the valve or controller Freezing temperatures will freeze the water in the valve This will cause physical damage to the internal parts as well as the plumbing Insects The controller and valve have been designed to keep all but the smallest insects out of the critical areas TYPICAL TOOLS AND FITTINGS REQUIRED Pipe Cutter Tu...

Page 4: ... 20 gpm 30 76 lpm 3 4 1 9 cm 4 7 gpm 15 29 lpm EQUIPMENT INSTALLATION If you are also installing a water softener the softener should be installed downstream of this system Grounding the Plumbing It is important that the plumbing system be electrically grounded When a water treatment system is installed a nonmetallic bypass valve may interrupt the grounding To maintain continuity a grounding strap...

Page 5: ...mpties into a drain below the level of the control valve form a 7 inch 18 cm loop at the far end of the line so that the bottom of the loop is level with the drain line connection This will provide an adequate siphon trap 4 Secure the discharge end of the drain line to prevent it from moving EQUIPMENT INSTALLATION continued Right Way Figure 6 Drain Line Connection NOTE Waste connections or drain o...

Page 6: ...TUP 361 The system will now need to be placed into operation Please review INITIATING A CLEANING CYCLE on page 7 before attempting startup 1 With the supply water for the system still turned off position the bypass valve to the not in bypass normal operation position 2 Turn the control knob counter clockwise until the indicator arrow on the valve body is lined up with the Recycle icon to start a c...

Page 7: ...wash flushing water through the filtration media in the tank 2 Turn the control knob counter clockwise until the indicator arrow is lined up with 2 Water will flow to drain 3 Turn the control knob counter clockwise to line up the indicator arrow with 0 to return the system back to normal operation Semi Automatic Cleaning Cycle 361 Valve 1 To start a cleaning cycle turn the control knob counter clo...

Page 8: ...ater Backwash Media Tank Inlet Outlet 1 4 3 2 BACKWASH Drain Drain Control FAST RINSE Untreated Water Rinse Media Tank Inlet Outlet 4 3 Drain Control 1 2 Drain Valve No 1 Closed 2 Open 3 Closed 4 Closed Valve No 1 Open 2 Closed 3 Open 4 Closed Valve No 1 Closed 2 Open 3 Closed 4 Open 8 AUTOTROL 360 361 Filter Valves ...

Page 9: ...rans 240V 1000814 EuropeWallTrans 240V 1000810 JapanWallTrans 100V 13 1 4002561 Kit Remote Regeneration 361 Filter 14 1 DrainLineFlowControl 4002459 Kit DLFC 4 0GPM NPT 360 Fltr 4002460 Kit DLFC 4 5GPM NPT 360 Fltr 4002461 Kit DLFC 5 0GPM NPT 360 Fltr 4002462 Kit DLFC 6 0GPM NPT 360 Fltr 4002463 Kit DLFC 7 0GPM NPT 360 Fltr 4002464 Kit DLFC 8 0GPM NPT 360 Fltr 4002465 Kit DLFC 9 0GPM NPT 360 Fltr ...

Page 10: ...cs 361 control will not complete a cleaning cycle automatically AC adapter or motor not connected Connect power Debris is preventing camshaft from rotating Remove debris Defective motor Replace motor Backwashes or purges at excessively low or high rate No drain line flow control Install drain line flow control Restricted drain line Remove restriction TROUBLESHOOTING 10 AUTOTROL 360 361 Filter Valv...

Page 11: ... 25 30 1 6 11 16 21 26 PRESSURE DROP IN PSI FLOW IN GPM Service Cv 5 43 0 5 10 15 20 25 30 35 1 6 11 16 21 PRESSURE DROP IN PSI FLOW IN GPM BW Cv 3 74 FLOW PERFORMANCE DATA CHARTS AUTOTROL 360 361 Filter Valves 11 ...

Page 12: ...marks and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal opportunity employer 4002447 REV B MR15 2013 Pentair Residential Filtration LLC All Rights Reserved For Autotrol Product Warranties visit Autotrol para las garantías de los productos ...

Reviews: