8 • WHOLE HOUSE CARBON FILTRATION SYSTEM

QUICK START GUIDE: SYSTEM START-UP INSTRUCTIONS CONTINUED

1.   

Connect the unit to the existing plumbing: 

 

       

 

 

 

(Facing the front of the system, INLET is on the LEFT – OUTLET is on the RIGHT) 

 

 

 

 

             

 

 

              

The

 

bypass is only hand tightened at the factory and must be fully tightened and checked for leaks by 

the installer.

 

            

 

 

             

Connect the drain line to a proper location; adhere to ALL LOCAL and STATE CODES. When turning the 
water back on, leave the system in bypass mode and then the turn water on to the house and check for 
leaks. Run the cold water in bathtub or outdoor faucet to flush debris and air from the lines. (Bathtubs 
do not have aerators that may plug with debris.) Then, once the programming is complete, follow the 
start up procedure starting at step 8.

2.   

Understanding the face plate.

 

         

There are 3 buttons on the face of the unit. The button on the left with the 2 arrows in a circle is called 
the scroll button. The buttons to the right are the up and down buttons.

3.     

Programing the System:

 

          

To begin, verify that the control is in the service mode.   

 

 

 

 

 

 Press and hold the DOWN arrow for 5 seconds; the control will display: SYSTEM CHECK 

 

 

Then enter the following code by pressing and releasing the following buttons.   

 

 

DOWN, DOWN, SCROLL, DOWN,

 THIS MUST BE DONE WITHIN 10 SEC. or the control will return to 

the home screen. The screen will display 

“CAPACITY: 1200 GL”

, by using the UP or DOWN arrow. 

The number will advance by 100 each time you press the arrow. The factory setting is fine for most 
applications. 

            

 

 

            

4.    Press the SCROLL button to advance to the next setting.  

 

 

 

 

 

The screen will read 

“CHANGE PHONE? NO”

 use DOWN button change to 

“YES”

 Press the SCROLL 

button 1 time and the 1st number will flash. 

 

 

 

 

 

 

 

Use the UP or DOWN button to program your phone number to display. After each number press the 
SCROLL button 1 time to advance to the next number. After setting all the numbers, press SCROLL to 
advance to the next setting.

5.     The control will display 

“TIME OF DAY”

, press the UP or DOWN arrow to program the time of day.

6.     Press the SCROLL button to advance to the next setting. The control will then display 

“Go to ADVANCED 

menu? No” 

If you want to go to advanced settings, press the UP or DOWN arrow, change to “YES” 

and press the SCROLL button (Default settings on ADVANCED MENU will not need to be changed for 
most 

applications).           

*The ADVANCED MENU consist of 

RESET AVERAGE:

 NO, 

RESERVE CAPACITY:

 VARIABLE, 

TIME OF 

REGENERATIONS:

 1 AM, 

DAYS OVERRIDE:

 OFF, 

BACKWASH:

 10min, 

BRINE/SLOW RINSE:

 0min,  

FILL/RINSE:

 3min

7.     If you don’t want to access the advanced settings, leave at “NO”. Press SCROLL button 1 time. The 

control will display

 “EXIT: PRESS

 ↓

, press DOWN to exit installer’s program level. The Time of day and 

rolling message “For Service, Call (your number)” will be displayed.

WARNING

Summary of Contents for 1.0

Page 1: ...WHOLE HOUSE CARBON FILTRATION SYSTEMS INSTALLATION AND SERVICE MANUAL pentair com homewater ...

Page 2: ...nstalling this system in a metal conductive plumbing system i e copper or galvanized metal will interrupt the continuity of the plumbing system and grounding source in some homes If your home s electrical appliances are grounded through the plumbing system you will need to install a bypass that consists of the same material as the existing plumbing or a grounded jumper wire to bridge the equipment...

Page 3: ... F 70 C 158 F Humidity The computer board operates properly with relative humidity 10 95 non condensing ENVIRONMENTAL REQUIREMENTS Location The water filter and control cannot be exposed to outdoor elements such as direct sunlight or atmospheric precipitation The system may be installed in a covered open air structure such as a carport residential or commercial building Weather covers are also ava...

Page 4: ...area must be adequate for easy service of all parts This system must be installed in accordance with all applicable state and local laws and regulations This system is designed to treat cold water only and can be installed on any cold water supply ANNUAL MAINTENANCE INSTRUCTIONS Clean the backwash flow control Verify that the flow meter is functioning correctly Clean the impeller if necessary Veri...

Page 5: ...system as close to these items as practical Avoid drain lines over 25 feet long In most applications bypass any outside faucets Place the unit in the desired location The location must have a level smooth surface If the system is located outdoors protect the unit from direct sunlight Direct sunlight can damage the fiberglass and other system components If necessary build a box or shed The system c...

Page 6: ... ground connection Whenever a system is installed on metallic plumbing we recommend you use grounding pipe clamps and a ground cable to maintain continuity of the ground connection from the inlet to the outlet pipe bare stranded wire is recommended for the ground cable Check electrical continuity of the connection after installation 9 INSTALL THE DRAIN LINE AND AIR GAP AIR GAP NOT INCLUDED WITH TH...

Page 7: ...e line If circumstances require you to tie the drain lines together please use one of the following methods to avoid back feed issues Option 1 Run the drain lines from both systems to the point of termination and tee them together before the air gap See figures below Option 2 Install a PVC check valve with a light spring on the Softener side to prevent back flow to the Softener See figure below WA...

Page 8: ... SEC or the control will return to the home screen The screen will display CAPACITY 1200 GL by using the UP or DOWN arrow The number will advance by 100 each time you press the arrow The factory setting is fine for most applications 4 Press the SCROLL button to advance to the next setting The screen will read CHANGE PHONE NO use DOWN button change to YES Press the SCROLL button 1 time and the 1st ...

Page 9: ...ir to purge 2 to 3 seconds then immediately advance the valve to next cycle by pressing and holding briefly the SCROLL button Once the motor starts release the SCROLL button The valve will advance to cycle 3 fast rinse Allow the system to complete the cycle Because carbon can take 24 hours to saturate we advance the valve quickly to avoid the carbon from lifting 10 Flush the system and verify gall...

Page 10: ... reprogrammed When the power is restored the clock will restart at 8 AM and will need to be reset REGENERATION Once an immediate regeneration is requested a complete regeneration must occur to clear the request Once the regeneration starts it must finish or the computer board will not clear Manually walk scroll the control through regeneration to clear the computer board If the regeneration is abo...

Page 11: ...N to advance through the different settings The following settings are available in the Installer s Level 1 CAPACITY The control will display Press the UP or DOWN ARROW to change the volume of treated water between regenerations The gallons are in increments of 100 The setting range is 100 to 999 999 gallons maximum limit Press the SCROLL BUTTON to advance to the next setting 2 SERVICE PHONE NUMBE...

Page 12: ...will display If you want to go to advanced setting press the UP or DOWN ARROW change to YES and press the SCROLL BUTTON see ADVANCED MENU below If you do not want to access advance setting leave this at NO Press Scroll to advance to Exit screen Press the DOWN ARROW to exit the Installer s Level Notice If you need to recheck settings or make a change pressing SCROLL when EXIT is displayed will take...

Page 13: ...ress the UP or DOWN ARROW The control will display Rsrv 200 GL FXd To adjust the reserve press the SCROLL BUTTON Use the UP OR DOWN ARROW to set the reserve capacity in increments to 10 gallons upto 70 capacity of the bed To calculate the reserve capacity take the number of people in the home and multiply it by 70 gallons per day The reserve capacity will equal one day of water use Example Three p...

Page 14: ...setting should be addressed with technical support for your individual conditions Press the SCROLL BUTTON to advance to the next setting 5 CYCLE 1 BACKWASH The control will display Press the UP or DOWN ARROW to change the length of the backwash cycle The setting range is 0 to 99 minutes Press the SCROLL BUTTON to advance to the next setting 6 CYCLE 2 BRINE SLOW RINSE The control will display Press...

Page 15: ... to advance to the next setting Press the DOWN ARROW to exit the Installer s Level If you need to recheck settings or make a change pressing SCROLL when EXIT is displayed will take you back to the start of Installer Settings To activate the new settings you must execute a complete regeneration If you DO NOT manually regenerate the system the settings WILL NOT become active until the unit has compl...

Page 16: ...ontrol will display If the control is left in this position the timer will countdown from 10 to 0 initiating a regeneration at 0 To avoid an immediate regeneration press the SCROLL BUTTON before the timer reaches 0 Press the SCROLL BUTTON to advance to the next setting 3 DELAYED REGENERATION MODE The control will display If the control is left in this position the unit will regenerate at the progr...

Page 17: ...te Displays the current flow rate Avg Vol Displays the average daily water consumption Capacity The control is programmed for a volume setting The display will read capacity along with maximum water to be used before regeneration Rsrv Displays whether the control is programmed for a Fixed or Variable Reserve Regen Displays the time of day the unit will regenerate Override Displays the override mod...

Page 18: ...VALVE EXPLODED VIEW 36 36 25 25 34 34 33 33 28 28 29 29 27 27 26 26 32 32 30 30 38 38 23 23 18 18 24 24 31 31 21 21 14 14 20 20 19 19 16 16 17 17 15 15 13 13 12 12 39 39 11 11 10 10 9 9 8 8 37 37 6 6 7 7 5 5 2 2 4 4 3 3 1 1 35 35 40 41 42 43 ...

Page 19: ...T VALVE SPRING 16 1 71127 FLOAT VALVE 17 1 70660 FLOAT VALVE O RING 18 1 72770 VALVE BODY ROTARY GEN 3 W INSERTS 19 1 71063 INJECTOR 1 RED 20 1 70655 INJECTOR O RING LOWER 21 1 70664 INJECTOR O RING UPPER 23 1 71947 SPRING CLIP 24 1 71344 RISER INSERT GASKET 25 1 71118 RISER INSERT 26 1 70662 RISER INSERT O RING 27 1 70663 TANK O RING 28 1 71010 UPPER BASKET ADAPTER RING 29 2 70630 SCREW 6 19 X 3 ...

Page 20: ...20 WHOLE HOUSE CARBON FILTRATION SYSTEM 1 2 3 4 6 5 10 7 8 9 12 20 17 18 19 16 13 14 11 3 21 15 22 ...

Page 21: ... SR 2P 4 8 1 70962 ELECTRONIC CONTROL BACKPLATE 9 3 71502 SCREW 8 18 X 3 8 LG SELF THREADING 10 4 71497 SCREW 10 16 X 1 LG TYPE BT SS SELF THREADING 11 1 75156 ROTARY WORM DRIVE GEAR 12 1 71656 MOTOR 24VCD WITH INTERNAL CAPACITORS 13 1 75158 1 4IN E RETAINING RING STAINLESS STEEL 14 1 75157 ROTARY WORM COUPLING 15 1 72451 MICROSWITCHES SUBASSY 2401 16 2 70622 SCREW 2 28 X 3 4 LG SELF THREADING 17 ...

Page 22: ... 72599 SCREW 6X32X1 2 TYPE 2 1 72580 BYPASS END CAP 541 3 1 13328 017 O RING 8730 4 2 72584 RETAINING RING VS 15 5 2 71161 568 363 NUT BYPASS VALVE 6 2 71162 568 364 RING NUT RETAINER 7 2 71110 568 320 GASKET 8 1 72669 BYPASS BODY ROTARY 9 2 72585 O RING 220 EPC 70 DURO 10 2 72586 O RING 222 EPC 70 DURO 11 2 72583 SEAL BYPASS VALVE 12 2 72670 BYPASS HANDLE ROTARY ...

Page 23: ...AIR PRINTED TANK COLLAR 1 0 1 5 38947 12 PENTAIR PRINTED TANK COLLAR 2 0 2 1 38256 10 X 44 TANK BLACK W BASE 1 0 38257 10 X 54 TANK BLACK W BASE 1 5 38258 12 X 48 TANK BLACK W BASE 2 0 3 1 83489 PENTAIR ROTARY VALVE CARBON FLT 1 0 1 5 WITH BYPASS 83490 PENTAIR ROTARY VALVE CARBON FLT 2 0 WITH BYPASS 4 1 18961 RISER PIPE ASSY 1 0 18962 RISER PIPE ASSY 1 5 38013 RISER PIPE ASSY 2 0 5 1 70793 3 4 NPT...

Page 24: ...OLE HOUSE CARBON FILTRATION SYSTEM Tank Size DIM A DIM B DIM C 10x44 10 1 4 in 46 in 51 in 10x54 10 1 4 in 55 7 8 in 61 1 4 in 12x48 12 in 50 in 55 1 4 in Ø DIM A DIM C DIM B 4 3 4 in 3 in 8 3 4 in 14 1 2 in ...

Page 25: ...ROUBLESHOOTING GUIDE SYMPTOM CAUSE SOLUTION 1 Untreated water to service 1 Open bypass valve 1 Close the bypass valve 1 Faulty electrical supply 2 The control is not set properly 3 The drive motor is defective 4 The flow meter is defective 5 The computer board is defective 6 The microswitches are defective 6 Replace the microswitches 5 Replace the computer board 4 Replace the flow meter 3 Replace ...

Page 26: ... 2 Computer board failure 3 Defective microswitch es 4 The valve body and timer are out of synchronization 4 Synchronize the valve body and timer 3 Replace the microswitch es 2 Replace the computer board 1 Replace the drive motor 4 Remove and clean the riser pipe 3 Replace the distributor s 2 Remove the debris from the distributor s 1 Clean the filter bed and control valve Increase the regeneratio...

Page 27: ...r visit pentair com register warranty to complete the warranty registration form online For details on your Pentair product warranty please visit pentair com assets residential filtration warranty Send to Pentair 2361 Mason Avenue Suite 100 Daytona Beach FL 32117 Date Item s were Received Order ID Model Dealer Purchased From Name Address City State Zip Model Serial Number ...

Page 28: ...28 WHOLE HOUSE CARBON FILTRATION SYSTEM ...

Page 29: ...WHOLE HOUSE CARBON FILTRATION SYSTEM 29 ...

Page 30: ...United States P 877 842 1635 Technical Services 877 842 1635 pentair com homewater 2022 Pentair All indicated Pentair trademarks and logos are property of Pentair Third party registered and unregistered trademarks and logos are the property of their respective owners ...

Reviews: