Pentair Pool Products Nocchi CPS 10 Use And Maintenance Manual Download Page 19

 

Page 17 of 30

RIP F 

Restart type 

Parameter used to define how the restarting mechanism 
works. If set to FIN, the module will go into a definitive 
alarm after the fourth attempt. If sent to CICL, it will 
attempt to restart indefinitely using the interval specified 
during the fourth attempt.

FIN FIN 

CICL 

RIP T 

Intervention time 

Waiting time after restarting within which pressure must 
return to above the minimum threshold level for lack of 
water. (seconds)

15 5 

300 

ORE P 

Hours running 

Number of hours the pump has been running.

N.A. N.A. 

N.A. 

SCA T 

Exchange time  

Parameter indicating the amount of time a pump must run 
for. Once this value has been reached, the pump will stop 
and a second pump will commence working. This 
parameter is expressed in minutes until it reaches 60, 
after which it is expressed in hours. The difference is 
indicated by the presence of an "H" for hours and an "M" 
for minutes. 
Must be set to primary for a unit or for twin pumps.

0 0 

168 

SCA S 

Exchange time 
mode 

Pumps are exchanged once the SCAT parameter has 
been reached: 

T1:

 The active pump is switched off first, before the 

second pump starts up 

T2:

 The second pump is switched off first, before the first 

pump starts-up.

1 1 

FP

PWM frequency 

Frequency of the PWM which controls the motor.

15.9 5.1 

15.9 

INSTALLATION PARAMETERS 

TAB 

Anti-locking 

Amount of time the pump is inactive. Once this amount of 
time has expired, the pump will start up for 15 seconds at 
maximum frequency. Then, the frequency will be slowly 
lowered until the minimum set frequency is obtained. This 
parameter is expressed in minutes until it reaches 60, 
after which it is expressed in hours. The difference is 
indicated by the presence of an "H" for hours and an "M" 
for minutes.

0 0 

 

999 

5.4  MANUAL START OF MOTOR/PRIMING 

This procedure is applicable when you want to manually start the system or prime the pump. 

 

It is possible to manually start the motor by pressing the following sequence of buttons: 

Buttons sequence with pump off 

The pump remains on until the last button is pressed

  

Last button pressed for 10 seconds 

 

17  - GB -

44

Summary of Contents for Nocchi CPS 10

Page 1: ...g E Manual de uso y manutenci n NL Handleiding voor gebruik en onderhound RUS Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecnf...

Page 2: ...73 23 89 336 en de daaropvolgende wijzigingen EF OVERENSSTEMMELSESERKL RING UndertegnedefirmaPENTAIRWATERITALYSrlerkl rerhermed under ansvar at nedenn vnte elektropumper er fremstillet i overensstemme...

Page 3: ...SURE UNIT TO THE POWER SUPPLY 7 CHAPTER 4 FUNCTIONING 8 4 1 PRODUCT DESCRIPTION 8 4 1 1 MOTOR PUMP 8 4 1 2 PRESSURE UNIT 8 CAPITOLO 5 PROGRAMMING 9 5 1 CONTROL PANEL DESCRIPTION 9 5 2 DESCRIPTION OF S...

Page 4: ...ION 23 CHAPTER 8 TABLES AND DESIGNS 23 8 1 DATA PLATE 23 8 2 TO INSTALL THE NEGATIVE SUCTION HEAD 24 8 3 TO INSTALL THE POSITIVE SUCTION HEAD 25 8 4 ELECTRICAL CONNECTION BOARD POWER BOARD 26 8 5 CONN...

Page 5: ...PS inverter coupled with a NOCCHI motor pump x Incorrect use can dangerously damage the machine or the equipment as well as result in guarantee forfeiture The CPS module has a single phase power suppl...

Page 6: ...otection IP55 x Level of system protection IP55 if installed on motors with an IP55 or superior level x Maximum operational pressure refer to the specific motor pump manual x Voltage of inverter 1x230...

Page 7: ...ations described in the use and maintenance manual for the motor pump used It is possible to use a float to deactivate the system to avoid the system drying up 3 3 PRESSURISED TANK EXPANSION VESSEL x...

Page 8: ...oltage is 1 230Vac 50 60Hz The CPS comes with a Shuko EEC 7 7 type power plug Connect the plug in an accessible position in case it is necessary to deactivate the system In case of damage to the power...

Page 9: ...citors can unload before working on the CPS x Perform the electrical connections in compliance with local standards in force x The installer is responsible for checking that the electrical power suppl...

Page 10: ...oint pressure the speed at which the pump rotates varies based on water requirements as such greater requirements will result in higher speeds until the maximum threshold level is reached After this t...

Page 11: ...he conditions for turning off the system the second pump can support the first in this mode BOOSTER setting CH5 see Chpt 5 3 4 x Settings for the master motor PRI P can be selected using the installat...

Page 12: ...t Current absorbed by the pump in Ampere Frequency graph indicator Day of the week 4 hh mm Time Time Day of the week Frequency graph indicator 5 Complementary pump status unit only STB the complementa...

Page 13: ...change system setting parameters x For a correct configuration we recommend using the installation and advanced parameters with the machine on STOP and connected to the power supply 5 3 1 PROGRAMMING...

Page 14: ...he symbol lights up on the display With the buttons it is possible to modify the pressure values SET POINT 1 Pressure desired by the system the module varies the motor speed to maintain the system pre...

Page 15: ...rement Pressure unit of measurement BAR BAR PSI SET N Number of SET POINTS Number of set points used 1 1 2 ROT Motor rotation direction Motor rotation direction POS POS NEG COR Nominal current Pump no...

Page 16: ...orise the values press the button SET The symbol disappears The words REC will appear on the screen for a few seconds to show that the data has been saved MENU DESCR DISPLAY PARAMETER NAME DESCRIPTION...

Page 17: ...not support the first in this mode BOOSTER setting CH04 Indicates that the first pump to come on at the next request for water will be the one which has run for the least amount of time see functionin...

Page 18: ...ALL P Water alarm pressure Indicates minimum system pressure a lack of water alarm will be generated under this threshold value Set to zero to disable this function 0 5 0 1 RIP 1 1st start up Waiting...

Page 19: ...r twin pumps 0 0 168 SCA S Exchange time mode Pumps are exchanged once the SCAT parameter has been reached T1 The active pump is switched off first before the second pump starts up T2 The second pump...

Page 20: ...START STOP button again to exit the STOP condition CHAPTER 6 SIGNALS ALARM STATUS AND ERRORS 6 1 HISTORY SAVED Key sequence Press ESC for 5 seconds Press ESC Key sequence Press MODE to scroll the err...

Page 21: ...ry Error due to the temporary absence of water This occurs when water is absent and the restart mechanism has been activated The will wait before restarting in order to attempt to automatically reset...

Page 22: ...m condition closes the J3 contact on the power board for possible external signals alarm light siren etc Cut the power off and wait until the LINE Led switches off and after which turn power back on I...

Page 23: ...t customer care centre E12 Memory error This error occurs when eeprom is unable to load the parameters which have been entered Wait for a few minutes If the signal remains press the button START STOP...

Page 24: ...ed wait approximately 10 seconds for the module itself to automatically launch a general reset If this does not reset the system use this key and contact a customer care centre Reset key sequence Pres...

Page 25: ...LATE 1 Type of motor pump 8 Date and year of production 2 Maximum flow rate l min 9 Absorbed current 3 Nominal power P2 10 Frequency 4 Maximum temperature of liquid 11 Software version 5 Nominal curre...

Page 26: ...NEGATIVE SUCTION HEAD 1 Basin or tank 7 Pressure transducer 2 Float 8 Flexible tube 3 Shut off valve 9 Non return valve 4 Outlet tubing 10 Filter 5 Tank autoclave membrane 8 l min 11 Motor pump comple...

Page 27: ...3 Shut off valve 9 Non return valve 4 Outlet tubing 10 Filter 5 Tank autoclave membrane 8 l min 11 Motor pump complete with inverter 6 Gauge For the installation of the positive suction head ensure t...

Page 28: ...W1 Motor connections 8 5 CONNECTIONS BOARD CONTROL BOARD RS 485 Communication port INI INIBIT input NC external contact S P External Set Point EST NA contact NTC NTC sensor input to control temperatu...

Page 29: ...esenting the proof of purchase document receipt invoice or delivery document The guarantee is forfeited if the fault is caused by incorrect treatment or operations or incorrect implementation or stora...

Reviews: