background image

P/N 472032

                     Rev. A  1-2-02

26

NORMAL OPERATION SEQUENCE

(Refer to Figure 20 of Pentair Temperature Controller 7800 keyboard)

The heater features a fully automated firing start-up and shutdown sequence under the control of the
MiniMax NT Standard Pentair Temperature Controller 7800.

Now that the heater has been properly installed and wired for either remote operation or local operation, and
you have setup the Pentair Temperature Controller 7800 temperature setpoints as described earlier in manual
in Thermostat section, the following is the normal operating sequence when the heater turns on the and the
thermostat calls for heat for the pool or spa.

1. The fan will start beginning the heater’s safety prepurging cycle which lasts for 1 minute. If at anytime

during the prepurge cycle the Pentair Temperature Controller 7800 detects that a safety control is not
working due to either a safety control malfunction or other unsafe condition the firing sequence will stop
until the unsafe condition is removed— “the fault icon related to the problem will illuminate”.

2. After proper completion of the prepurge cycle, the hot surface ignitor (glow coil) will turn on (preheat)

for 40 seconds. Once the 40 seconds is passed, the main gas valve will open and the heater will fire. At
this time, if flame is not safely established as detected by the flame sensing circuit, the ignition module
and Pentair Temperature Controller 7800 will shut down and will display an ignition fault and luminate
the red service light. 

Please note that on initial firing of heater when gas supply piping is full of air or

after long period of non-operation of the heater it is normal for the first ignition attempt to not complete.

To clear the fault condition power to the Pentair Temperature Controller 7800 must be cycled to reset
system. If heater continues to fail to light have heater inspected by a qualified service person before
placing heater back in service.

Insufficient waterflow (pump icon displays), excessive water temperature (high limit icon) cause a
“soft-lockout” of the firing sequence—which means if the cause of the problem clears by itself (or with
human intervention ie., turning on pump, etc.) such as a slow to prime water pump finally pumping
adequate  waterflow causing the water pressure (safety) switch to close, the ignition sequence
automatically restarts again.

The other category of fault conditions lead to a “hard lockout” of the firing sequence which require a
qualified service person to correct before the heater is returned to service. In “hard lockout” the heater
must be manually reset (by toggling power to Pentair Temperature Controller 7800) after correction of
the fault condition.

3. After normal firing of the heater (main burners) the heater will continue to operate until the

temperature setpoint is reached (thermostat satisfied). As the pool/spa loses heat the heater will refire
and continue to operate cycling automatically to maintain the selected temperature setpoint for either
the pool or spa. 

If at anytime during the firing of the heater an unsafe condition is detected the

heater will stop firing and an automatic safe shutdown sequence will begin. Investigate and have
corrected the cause of the abnormal firing termination before placing heater back in operation.

Please Note: 

During the firing of the heater, you decide to change to the pool or spa selection by

depressing the selector key for “POOL” or “SPA”, the heater will first acknowledge the new selection by
flashing the new selection’s corresponding selection LED “POOL” or “SPA”, however, the heater will first
complete a safe shutdown sequence before automatically switching to the new selected setting and safely
initiating a new firing sequence using the new temperature setpoint. During this automatic crossover
sequence the keyboard on the Pentair Temperature Controller 7800 will not accept any further keying until
the cycle completes—the exception is you may still stop the heater with the “OFF” key.

Troubleshooting—Normal Operation Sequence of Heater

Summary of Contents for MiniMax NT Standard 200

Page 1: ...tallation and service must be performed by a qualified installer service agency or the gas supplier MiniMax NT Standard Series POOL SPA HEATERS OPERATION INSTALLATION MANUAL WARNING WHAT TO DO IF YOU...

Page 2: ...art Gas Pressure Requirements 12 Regulated Manifold Pressure Test 12 Venting Indoor Installations 13 16 Venting Outdoor Installations 17 Basic Operation General Description 18 Basic Operation Safety C...

Page 3: ...tor of the MiniMax NT Standard pool and spa heater The manufacturer s warranty may be void if for any reason the heater is improperly installed and or operated Be sure to follow the instructions set f...

Page 4: ...h an accurate thermometer Spa or hot tub thermostats may err in regulating water temperatures by as much as 4 F 5 Persons with a medical history of heart disease circulatory problems diabetes or blood...

Page 5: ...ON LIGHTING OPERATION 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device whic...

Page 6: ...state be sure your contractor bears the appropriate license SPECIFICATIONS 24 05 2 in SOCKET A DIM 8 84 6 64 30 63 LEG LEG 14 50 3 50 4 875 MODEL 200 250 24 63 21 63 A DIM 15 50 300 400 34 13 27 63 7...

Page 7: ...und is connected to the ground terminal GND see below Figure 5 NOTE If any of the original wiring supplied with this heater must be replaced installer must supply No 18 AWG 105 C U L approved AWM low...

Page 8: ...troller then the second wire to either the SPA or POOL tab b Now return power to the heater but leaving the temperature controller in the OFF position see Page 22 Note If you used the main power switc...

Page 9: ...erate NOTE The heater factory settings are 78 F for the pool and 104 F for the spa When connecting a remote control to the MiniMax you must install the low voltage thermostat wires in separate conduit...

Page 10: ...ETY GROUND WIRE GREEN HERE CHASSIS BOND LUG EXTERNAL ORG WHT GRN 2 1 3 2 1 4 3 2 5 1 4 3 6 2 1 F2 F1 P11 P10 P7 P4 ORG RED THERMAL FUSE WHT BLU RED SWITCH WATER PRESSURE THERMAL SWITCHES EXHAUST HIGH...

Page 11: ...emperature sensing bulb from the inlet outlet header Note If needed you may cut the wire ties holding them together 5 Remove the 16 bolts holding the main inlet outlet head and return head in place ex...

Page 12: ...e to test the gas line Use soapy water or another nonflammable method A manual main shut off valve must be installed externally to the heater Pipe Sized For Length Of Run In Equivalent Feet l e d o M...

Page 13: ...ombustible materials must be maintained in accordance with type of vent pipe employed in the absence of a clearance recommendation by the vent pipe manufacturer the requirements of the Uniform Mechani...

Page 14: ...non combustible floor or on a non combustible base and in an area where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure W...

Page 15: ...contaminated by corrosive chemical fumes which can void the warranty NOTE The openings listed in Table 2 are free open vent area if the vents incorporate restrictive louvers the vent openings must be...

Page 16: ...walkways must be at least 3 ft above any outside air intake located within a 10 ft radius must NOT be within 3 ft of an inside corner of the structure must be at least 1 ft above grade must be locate...

Page 17: ...ll a minimum of 4 feet below and 4 feet horizontally from any opening to a building see Figure 17 IMPORTANT When locating the heater consider that high winds can roll over or deflect off adjacent buil...

Page 18: ...ee page 21 4 Open the access doors 5 Push in the gas control knob slightly and turn the knob clockwise to OFF See page 5 for Instructions 6 Wait 5 minutes to clear out any gas If you then smell gas ST...

Page 19: ...y switch closes when there is a sufficient flow of water to the heat exchanger to safely operate the heater The switch operation must be verified during initial operation of the heater after installat...

Page 20: ...fan prepurge cycle the hot surface ignitor is activated for a heat up period followed by energization of the gas valve for the trial for ignition period When flame is detected during the trial for ign...

Page 21: ...ION NO REMOTE Each temperature setting in either POOL or SPA mode is settable independently If the Factory s presetting of 78 F for Pool and 104 F for Spa is not desirable you may adjust these setting...

Page 22: ...ure is now set 4 You can leave the right window displaying the set Temperature or by pressing the MODE key you can return to the Time Mode NOTE To re set the Spa Temperature follow the above steps 1 t...

Page 23: ...er Minute setting then press the SET key The Day and Time are now set and the Day icon will be flashing 6 Press the SET and MODE keys at the same time to return to the Operational Mode SET MODE PROGRA...

Page 24: ...tighten the thermostat knob stopper 5 Set time clock to start circulation system no earlier than daybreak The swimming pool loses less heat at this time 6 For pools that are only used on the weekends...

Page 25: ...Then test only once every month or so to be sure it is being maintained See your local pool dealer for help in properly balancing the water chemistry 7 2 6 8 7 0 7 4 7 6 7 8 8 0 8 2 8 4 Add Soda Ash...

Page 26: ...acing heater back in service Insufficient waterflow pump icon displays excessive water temperature high limit icon cause a soft lockout of the firing sequence which means if the cause of the problem c...

Page 27: ...b r e k a e r b t i u c r i C e s u F C n o y d a e t s r o f D E L k c e h c l o r t n o c d a B D n o i t i n g i o n n o t a t s o m r e h T 2 d e r i w s i M A W l a n i m r e t t a e g a t l o v...

Page 28: ...n the cabinet The cause of the fault must be corrected and the one shot fuse replaced before icon can be cleared This fault icon displays whenever there is a failure of either the low gas pressure swi...

Page 29: ...h Replace switch Defective gas controls Call serviceperson On Off switch in OFF position Turn switch to ON Heater Short Cycling Rapid On and Off Operation Insufficient water flow Clean filter and pump...

Page 30: ...472032 Rev A 1 2 02 30 MINIMAX NT STANDARD HEATER Dual Voltage 1 4 3 5 6 8 9 10 12 33 34 36 48 47 46 44 42 43 38 37 18 17 16 15 21 14 32 39 2 7 11 22 23 20 19 35 45 41 40 13 30 27 28 31 26 24 25 29 50...

Page 31: ...y Propane 471907 471913 471925 471931 28 Igniter 1 Gas Manifold Assy Natural Gas 472023 472022 472021 472020 Gas Manifold Assy Propane 472027 472026 472025 472024 Burner Only 2 3 4 6 200 250 300 400 B...

Page 32: ...ident negligence alteration abuse misapplication or misuse The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual pro...

Reviews: