P70, P72, P170 Series Controls for High Pressure Applications Installation Instructions

    

 

Table 1: Pressure Control Switch Action, Low Events, High Events, Model Types, and Electrical Ratings 
Tables References 

Switch and Action 

Low Event 

High Event 

Model Types - Electrical 
Rating Table References 

Single-Pole Single-Throw 
(SPST) Open-Low 

Cutout 
(Opens Line to M1) 

Cut In 
(Closes Line to M1) 

P70A, P70B, P170A 
See Table 3. 

Single-Pole Single-Throw 
(SPST) Open-High 

Cut In 
(Closes Line to M1) 

Cutout 
(Opens Line to M1) 

P70C, P70D, P170C, P170D 
See Table 3. 

Single-Pole Double-Throw 
(SPDT) 

Opens 1 to 2 and  
Closes 1 to 3 

Closes 1 to 2 and  
Opens 1 to 3 

P70E, P70F 
See Table 4. 

4-Wire, 2-Circuits,  
1-NO, 1-NC  
Open-Low 

Cutout 
(Opens M2 to Line and 
Closes M1 to Line) 

Cut In 
(Closes M2 to Line and 
Opens M1 to Line) 

P70G, P70H 
See Table 5. 

4-Wire, 2-Circuits,  
1-NO, 1-NC  
Open-High 

Cut In 
(Closes M2 to Line and 
Opens M1 to Line) 

Cutout 
(Opens M2 to Line and 
Closes M1 to Line) 

P70J, P70K, P170K 
See Table 5. 

Double-Pole Single-Throw 
(DPST)  
Open-Low 

Cutout 
(Opens M1 to Line and  
M2 to Line) 

Cut In 
(Closes M1 to Line and  
M2 to Line) 

P72A, P72B 
See Table 6. 

(DPST)  
Open-High 

Cut In 
(Closes M1 to Line and  
M2 to Line) 

Cutout 
(Opens M1 to Line and  
M2 to Line) 

P72C, P72D 
See Table 6. 

Adjustments 

Adjustments of the P70, P72, and P170 high 
pressure controls vary, depending on the model. 
The following guidelines and diagrams illustrate the 
procedures for adjusting these controls. Refer to the 
product label inside the control cover for model 
number and switch action. Refer to Table 1 for 
switch action, low event, and high event for the 
various control models. 

High Pressure Cutout - Automatic Reset 

High pressure Cutout controls with automatic reset 
have a scaleplate that displays the Cut In and 
Cutout setpoints. (See the visible scale on the 
control.) Turn the range screw to adjust the Cut In 
and Cutout setpoints up or down simultaneously, 
while maintaining a constant pressure differential. 
Turn the differential screw to adjust (only) the low 
event on the left side of the scale (which changes 
the differential pressure value). 

High Pressure Cutout - Manual Reset Lockout 

High pressure Cutout controls with the Manual 
Reset Lockout option have a scaleplate that displays 
the Cutout setpoint. There is no pointer for the Cut In 
setpoint. (See the visible scale on the control.) 

Turn the range screw to adjust the Cutout setpoint 
on the right side of the scale. There is no differential 

screw on Manual Reset Lockout models. The differential 
pressure value is fixed. 

Condenser Fan Cycling - Open-Low Switch Action 

Condenser fan cycling pressure controls have a 
scaleplate that displays the Cut In

 

setpoint

 

and 

Differential setting. (See visible scale on the control.) 
Turn the range screw to adjust the Cut In setpoint on the 
right side of the scale. Turn the differential screw to 
adjust the Differential setting on the left side of the scale 
(which changes the Cutout pressure value). 

IMPORTANT: 

Do not adjust pointers beyond the 

highest or lowest indicator marks on the control’s 
pressure scale. Adjusting pointers beyond indicator 
marks may damage screw threads, may cause 
inaccurate control operation, and will void the 
warranty.  

 

IMPORTANT: 

Use the pressure control settings 

recommended by the manufacturer of the controlled 
equipment. Do not exceed the pressure ratings of the 
controlled equipment or any of its components when 
checking pressure control operation or operating the 
controlled equipment. 

 

Summary of Contents for P170A

Page 1: ...models with Single Pole Double Throw SPDT or 4 Wire 2 Circuit switch action allow users to install alarm devices or other control circuits P72 Series models have a Double Pole Single Throw DPST switch...

Page 2: ...mounting screws supplied with the Universal Mounting Bracket to avoid damaging internal components Be careful not to distort or bend the control case when mounting the control to an uneven surface Us...

Page 3: ...n wiring the control WARNING Risk of Electrical Shock Disconnect each of multiple power supplies before making electrical connections More than one disconnect may be required to completely de energize...

Page 4: ...ut Automatic Reset High pressure Cutout controls with automatic reset have a scaleplate that displays the Cut In and Cutout setpoints See the visible scale on the control Turn the range screw to adjus...

Page 5: ...operation Manual Reset Operation Pressure controls with the Manual Reset option lock out when they reach Cutout pressure and must be manually reset by the user to restart the controlled equipment The...

Page 6: ...or All Range Control Models for Noncorrosive Refrigerants P70CA 2 SPST Open High 50 to 500 345 to 3448 Minimum 60 414 Maximum 150 1034 1 4 in Male Flare Connector 525 3620 P70CA 3 36 in Capillary with...

Page 7: ...or models not included in this table contact the Refrigeration Application Engineering Group at 1 800 275 5676 for details and availability Note See Dimensions and Technical Specifications for additio...

Page 8: ...e Amperes 16 0 9 2 8 0 7 2 6 0 6 0 6 0 6 0 Pilot Duty for both sets of contacts 125 VA at 24 to 600 VAC 57 5 VA at 120 to 300 VDC Not for compressor motor loads Table 6 DPST Electrical Ratings P72A B...

Page 9: ...ntrols 60 lb 27 2 kg Compliance For information on specific models contact the Refrigeration Application Engineering Group at 1 800 275 5676 Accessories 271 51 Universal Mounting Bracket supplied with...

Reviews: