Penn F263 Series Installation Instructions Manual Download Page 7

F263 Series Liquid Level Switches Installation Instructions

7

Method of Mounting 

Control

Mounting to sensed media vessel/orientation

Type 1 or Type 2 Action

Type 1.C (Microinterruption)

External Pollution Situation 

Pollution degree 4

Internal Pollution Situation

Pollution degree 2

Rated Impulse Voltage

4,000 VAC

Ball Pressure Temperature

Enclosure:

 266°F (130°C )

Switch Component:

 252°F (122°C)

Control Adjustment 

Instruction

-

Field Wiring Rating

Wire/Cord Temperature Ratings:

•  140°F (60°C) only permitted when ambient air and media are less than 113°F (45°C)
•  167°F (75°C) only permitted when ambient air and media are less than 140°F (60°C)
•  194°F (90°C) only permitted when ambient air is less than 140°F (60°C) and media is 

less than 167°F (75°C)

•  302°F (150°C) permitted when ambient air is less than 140°F (60°C) and media is less 

than 249°F (121°C)

Vessel Pressure

F263 Liquid Level Float Switch with Copper Float: 

100 psi (690 kPa)

F263 Liquid Level Float Switch

 

with Polycarbonate Float:

 150 psi (1935 kPa)

F263 Series Liquid Level Float Switches

Switch

SPDT

Enclosure

UL: Type 4

CE: IP67

Wiring Connections

Three color-coded screw terminals and one ground terminal

Conduit Connection

One 7/8 in. (22 mm) hole for 1/2 in. trade size (or PG16) conduit

Pipe Connector

1 in. 11-1/2 NPT threads

Minimum Tank Diameter

9 in. (229 mm)

Maximum Liquid Pressure

100 psig (690 kPa) for copper float

150 psig (1,035 kPa) for polycarbonate float

Liquid Temperature Range

Minimum: -40°F (-40°C) or liquid freezing point

1

Maximum: 212°F (100°C) polycarbonate, 250°F (121°C) copper

2

Ambient Conditions

Minimum: -40°F (-40°C)

1

Maximum: 140°F (60°C)

2

Compliance

North America:

 cULus Listed; UL 60730, File E6688; 

FCC Compliant to CFR47, Part 15, Subpart B, Class B

Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe:

 CE Mark – Johnson Controls declares that this product is in compliance with the 

essential requirements and other relevant provisions of the EMC Directive and the Low 

Voltage Directive. 

Australia/New Zealand 

Mark: RCM Compliant

1.

Ensure that the low liquid temperature combined with the low ambient temperature does not lead to the freezing the liquid 

inside the body (or bellows, where appropriate). Please observe the liquid freezing point.

2.

At higher temperatures, the maximum allowed liquid temperature becomes lower. The temperature inside of the electrical 

switch should not exceed 158°F (70°C).

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult Johnson Controls/PENN Refrigeration Application Engineering at 1-800-275-5676. Johnson Controls shall not be liable 
for damages resulting from misapplication or misuse of its products.

Table 3:  UL Conformity Declaration Information (Part 2 of 2)

Summary of Contents for F263 Series

Page 1: ...d lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such a...

Page 2: ...voquer des blessures graves IMPORTANT Do not allow the float to touch the side of the tank or any other obstructions IMPORTANT To avoid damaging the switch do not tighten by grasping the switch enclos...

Page 3: ...components are at AC line voltage Contact with components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de d charge lectrique D b...

Page 4: ...ntification See Figure 4 and Figure 5 for suggested circuits for controlling liquid levels with several inches or feet between minimum and maximum levels Table 1 F261 Control Switch Action Flow Action...

Page 5: ...or other property MISE EN GARDE Risque de d g ts mat riels Ne pas r gler le commutateur sur une valeur inf rieure au param tre d usine Le commutateur est r gl en usine sur une valeur correspondant env...

Page 6: ...ons Table 2 F263 Series Liquid Level Switch Electrical Ratings Volts 50 60 Hz UL60730 UL1059 EN60730 24 120 208 240 24 230 Horsepower 1 1 1 Full Load Amperes 16 10 10 8 Locked Rotor Amperes 96 60 60 4...

Page 7: ...Diameter 9 in 229 mm Maximum Liquid Pressure 100 psig 690 kPa for copper float 150 psig 1 035 kPa for polycarbonate float Liquid Temperature Range Minimum 40 F 40 C or liquid freezing point1 Maximum 2...

Page 8: ...rference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer...

Reviews: