F263 Series Liquid Level Switches Installation Instructions

5

 Setup and Adjustments    

Checkout Procedure

Before applying power, ensure that installation and wiring connections are made to job specifications.

After making all necessary adjustments and electrical connections, put the system into operation and observe at 
least three complete operation cycles before leaving the installation site.

Operation

The F263 Float Switch controls water levels to within approximately 1/2 in. (13 mm).

When the liquid level falls approximately 1/2 in. (13mm) below the height at which the switch is installed, the switch 
closes the red contact (common) to the blue contact. See Figure 6 and Figure 7.

!

CAUTION: Risk of Property Damage.

Do not set the switch lower than the factory setting. The switch is factory set at 
approximately the minimum flow rate. A lower setting may result in the switch failing to 
return to a no-flow position which may result in damage to the controlled equipment or other 
property.

MISE EN GARDE : Risque de dégâts matériels.

Ne pas régler le commutateur sur une valeur inférieure au paramètre d'usine. Le 
commutateur est réglé en usine sur une valeur correspondant environ au débit minimum. 
Un réglage sur une valeur inférieure risque d'empêcher le commutateur de revenir sur une 
position « aucun-débit », ce qui risque d'endommager l'équipement contrôlé ou de 
provoquer d'autres dégâts matériels.

!

CAUTION: Risk of Property Damage.

Do not attempt to change sealed settings. Attempted adjustment may damage the control 
or cause loss of calibration or other property damage.

MISE EN GARDE : Risque de dégâts matériels.

Ne pas essayer de modifier la position des éléments de réglage bloqués. Toute tentative de 
réglage risque d'endommager le dispositif de contrôle ou de provoquer la perte des valeurs 
d'étalonnage ou d'autres dégâts matériels.

IMPORTANT:

All F263 switches are factory-set and factory-sealed. 

Do not

 attempt to change the factory 

settings. Changing the factory settings voids the warranty.

Figure 5:   Circuit for Controlling Dump Levels 

R

R

Y

Y

B

B

Pump Out

R1

R2

Pump

R

High Level

F263 Switch

Low Level

F263 Switch

L

L

FI

G

:d

m

p_l

vl

_c

ntr

l

Summary of Contents for F263 Series

Page 1: ...d lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such a...

Page 2: ...voquer des blessures graves IMPORTANT Do not allow the float to touch the side of the tank or any other obstructions IMPORTANT To avoid damaging the switch do not tighten by grasping the switch enclos...

Page 3: ...components are at AC line voltage Contact with components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de d charge lectrique D b...

Page 4: ...ntification See Figure 4 and Figure 5 for suggested circuits for controlling liquid levels with several inches or feet between minimum and maximum levels Table 1 F261 Control Switch Action Flow Action...

Page 5: ...or other property MISE EN GARDE Risque de d g ts mat riels Ne pas r gler le commutateur sur une valeur inf rieure au param tre d usine Le commutateur est r gl en usine sur une valeur correspondant env...

Page 6: ...ons Table 2 F263 Series Liquid Level Switch Electrical Ratings Volts 50 60 Hz UL60730 UL1059 EN60730 24 120 208 240 24 230 Horsepower 1 1 1 Full Load Amperes 16 10 10 8 Locked Rotor Amperes 96 60 60 4...

Page 7: ...Diameter 9 in 229 mm Maximum Liquid Pressure 100 psig 690 kPa for copper float 150 psig 1 035 kPa for polycarbonate float Liquid Temperature Range Minimum 40 F 40 C or liquid freezing point1 Maximum 2...

Page 8: ...rference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer...

Reviews: