Penn F263 Series Installation Instructions Manual Download Page 3

F263 Series Liquid Level Switches Installation Instructions

3

Install the F263 control into a properly threaded (and sealed) 1 in. diameter hole in the tank at the desired height for 
the liquid level. Position the control with the arrow on the enclosure pointing upward. Ensure that the threads are 
adequately sealed.

Wiring     

Color-Coded Screw Terminals

IMPORTANT:

To avoid damaging the float, ensure that the float is not subject to pressures exceeding these 

limitations:

•  100 psig (690 kPa) for copper float
•  150 psig (1035 kPa) for polycarbonate float

!

WARNING: Risk of Electric Shock.

Disconnect the power supply before making electrical connections. The printed circuit 
board and its components are at AC line voltage. Contact with components carrying 
hazardous voltage can cause electric shock and may result in personal injury or death.

AVERTISSEMENT : Risque de décharge électrique.

Débrancher l'alimentation avant de réaliser tout raccordement électrique. Le circuit imprimé 
et ses composants présentent une tension CA. Tout contact avec des composants porteurs 
de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des 
blessures graves, voire mortelles.

IMPORTANT:

Use copper conductors only. Make all wiring connections in accordance with local, national, and 

regional regulations. Do not exceed the flow switch’s electrical ratings.

IMPORTANT:

Use the terminal screws provided 

(8-32 x 1/4 in. binder head). Substitution of other screws voids the warranty and agency approvals.

Figure 2:  Installing the Float Switch

240 mm

70 mm

FI

G

:F263

_m

nt

Summary of Contents for F263 Series

Page 1: ...d lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such a...

Page 2: ...voquer des blessures graves IMPORTANT Do not allow the float to touch the side of the tank or any other obstructions IMPORTANT To avoid damaging the switch do not tighten by grasping the switch enclos...

Page 3: ...components are at AC line voltage Contact with components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de d charge lectrique D b...

Page 4: ...ntification See Figure 4 and Figure 5 for suggested circuits for controlling liquid levels with several inches or feet between minimum and maximum levels Table 1 F261 Control Switch Action Flow Action...

Page 5: ...or other property MISE EN GARDE Risque de d g ts mat riels Ne pas r gler le commutateur sur une valeur inf rieure au param tre d usine Le commutateur est r gl en usine sur une valeur correspondant env...

Page 6: ...ons Table 2 F263 Series Liquid Level Switch Electrical Ratings Volts 50 60 Hz UL60730 UL1059 EN60730 24 120 208 240 24 230 Horsepower 1 1 1 Full Load Amperes 16 10 10 8 Locked Rotor Amperes 96 60 60 4...

Page 7: ...Diameter 9 in 229 mm Maximum Liquid Pressure 100 psig 690 kPa for copper float 150 psig 1 035 kPa for polycarbonate float Liquid Temperature Range Minimum 40 F 40 C or liquid freezing point1 Maximum 2...