Penn F263 Series Installation Instructions Manual Download Page 6

F263 Series Liquid Level Switches Installation Instructions

6

When the liquid level in the tank rises to the height at which the switch is installed, the switch closes the red contact 
(common) to the yellow contact. See Figure 6 and Figure 7.

Repair Information

Do not make field repairs, except for replacement of the float. For a replacement control or float, contact the 
nearest Johnson Controls/PENN distributor. For more information, contact Johnson Controls/PENN application 
engineering at 1-800-275-5676.

Technical Specifications

   

    

Table 2:   F263 Series Liquid Level Switch Electrical Ratings

Volts 50/60 Hz

UL60730/UL1059

EN60730

24

120

208

240

24

230

Horsepower

1

1

1

Full Load Amperes

16

10

10

8

Locked Rotor Amperes

96

60

60

48

Resistive Amperes

16

16

10

10

16

16

Pilot Duty VA

125

720

720

720

77

720

Table 3:  UL Conformity Declaration Information (Part 1 of 2)

Information

Description

Purpose of Control

F263 Liquid Level Float Switch

Construction of Control

Electronic independently mounted control

Number of Cycles

100,000 cycles

Figure 6:  F263 Float Switch Setup

Dump

Fill

F

H

F

L

FI

G

:F

263

_f

lt_s

w

tc

h_s

et

up

Figure 7:  Terminal and Wiring Identification

Increase in Level

Above Setpoint

Decrease in 

Below Setpoint

Level

Red

Yellow

Blue

FIG

:F2

63_

sw

tc

ha

ct

n

Summary of Contents for F263 Series

Page 1: ...d lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such a...

Page 2: ...voquer des blessures graves IMPORTANT Do not allow the float to touch the side of the tank or any other obstructions IMPORTANT To avoid damaging the switch do not tighten by grasping the switch enclos...

Page 3: ...components are at AC line voltage Contact with components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de d charge lectrique D b...

Page 4: ...ntification See Figure 4 and Figure 5 for suggested circuits for controlling liquid levels with several inches or feet between minimum and maximum levels Table 1 F261 Control Switch Action Flow Action...

Page 5: ...or other property MISE EN GARDE Risque de d g ts mat riels Ne pas r gler le commutateur sur une valeur inf rieure au param tre d usine Le commutateur est r gl en usine sur une valeur correspondant env...

Page 6: ...ons Table 2 F263 Series Liquid Level Switch Electrical Ratings Volts 50 60 Hz UL60730 UL1059 EN60730 24 120 208 240 24 230 Horsepower 1 1 1 Full Load Amperes 16 10 10 8 Locked Rotor Amperes 96 60 60 4...

Page 7: ...Diameter 9 in 229 mm Maximum Liquid Pressure 100 psig 690 kPa for copper float 150 psig 1 035 kPa for polycarbonate float Liquid Temperature Range Minimum 40 F 40 C or liquid freezing point1 Maximum 2...

Page 8: ...rference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer...

Reviews: