F263 Series Liquid Level Switches Installation Instructions

Applications    

The F263 Series Liquid Level Switches are designed to maintain a liquid level in indoor or outdoor closed tanks 
holding water or other non-corrosive liquids. When the liquid level in the tank rises above or falls below the required 
level, the SPDT switch closes one circuit and opens a second circuit.

Use F263 Series Liquid Level Switches in closed tanks where a liquid level is to be maintained. A change in the 
liquid level opens or closes an electrical circuit.

Use F263MAP switches on indoor or outdoor tanks that hold water or other nonhazardous liquids at temperatures 
greater than the liquid's freezing point and between -20°F (-29°C) and 212°F (100°C). The maximum allowable 
liquid pressure is 150 psig 
(1035 kPa).

Use F263MAC switches on indoor or outdoor tanks that hold water or other nonhazardous liquids at temperatures 
greater than the liquid's freezing point and between -20°F (-29°C) and 250°F (121°C). The maximum allowable 
liquid pressure is 100 psig (690 kPa). 

Note:

Do not use these liquid level switches with liquids with a density less than the density of water. 

IMPORTANT:

Use this F263 Series Liquid Level Switch only as an operating control. Where failure or 

malfunction of the liquid level switch could lead to personal injury or property damage to the controlled equipment 
or other property, additional precautions must be designed into the control system. Incorporate and maintain other 
devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against 
failure or malfunction of the liquid level switch.

IMPORTANT :

Utiliser ce F263 Series Liquid Level Switch uniquement en tant que dispositif de régulation. 

Lorsqu'une défaillance ou un dysfonctionnement du liquid level switch risque de provoquer des blessures ou 
d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit 
intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente 
d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de 
limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement 
du liquid level switch.

IMPORTANT:

Do not use F263MAC and F263MAP Liquid Level Switches where the fluid in the pipes drops 

below the fluid’s freezing point, causing an internal freeze-up.

IMPORTANT:

Do not use F263 Series Liquid Level Switches with hazardous fluids or in hazardous 

atmospheres. Use in these conditions may cause malfunction or improper operation.

This product is made of a copper alloy, which contains lead. The product is therefore not to be used on drinking 
water.

F263 Series Liquid Level Switches

Installation Instructions

Part No. 24-7664-2985, Rev. D

Issued August 2018

Summary of Contents for F263 Series

Page 1: ...d lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such a...

Page 2: ...voquer des blessures graves IMPORTANT Do not allow the float to touch the side of the tank or any other obstructions IMPORTANT To avoid damaging the switch do not tighten by grasping the switch enclos...

Page 3: ...components are at AC line voltage Contact with components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de d charge lectrique D b...

Page 4: ...ntification See Figure 4 and Figure 5 for suggested circuits for controlling liquid levels with several inches or feet between minimum and maximum levels Table 1 F261 Control Switch Action Flow Action...

Page 5: ...or other property MISE EN GARDE Risque de d g ts mat riels Ne pas r gler le commutateur sur une valeur inf rieure au param tre d usine Le commutateur est r gl en usine sur une valeur correspondant env...

Page 6: ...ons Table 2 F263 Series Liquid Level Switch Electrical Ratings Volts 50 60 Hz UL60730 UL1059 EN60730 24 120 208 240 24 230 Horsepower 1 1 1 Full Load Amperes 16 10 10 8 Locked Rotor Amperes 96 60 60 4...

Page 7: ...Diameter 9 in 229 mm Maximum Liquid Pressure 100 psig 690 kPa for copper float 150 psig 1 035 kPa for polycarbonate float Liquid Temperature Range Minimum 40 F 40 C or liquid freezing point1 Maximum 2...

Page 8: ...rference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer...

Reviews: