13
Outside air is
REQUIRED ON ALL MOBILE HOME INSTALLATIONS
.
Outside air is strongly recommended for all other installations. Failure to install intake
air may result in improper combustion as well as the unit smoking during power failures.
Metal pipe, ONLY, either solid or flexible, must be used in all outside air installations.(B)
NOTE
:
Non-metallic material, such as PVC or ABS plastic piping.
MUST
NOT BE USED
for outside air installations.
A wind shield, (C), over the termination of the outside air pipe or a 90 degree elbow or
bend directed away from the prevailing winds
MUST
be used when an outside air pipe
is in-stalled through the side of a building. Keep the outside air pipe termination at least
1 foot away from the exhaust system termination.
When outside air is taken from an existing chimney, the exhaust system must not
terminate in the same chimney.
The outside air pipe on your stove is 2" OD. The outside air connecting pipe must be at
least 2" ID The outside air connecting pipe must be as short and free of elbows as
possible, and
must fit over
, (A), not inside, the outside air pipe on your stove.
For distances over 10’ long, 3‖ or 4‖ OD pipe is recommended, then reduce to 2‖.
Through The Wall Kits Include
:
3
FOOT
PACKAGE
–
PART
#
KS
5150-1450
10
FOOT
PACKAGE
– P
ART
#
KS
5150-1460
1 – 2‖ Galvanized Hood c/w screen
1 – 2‖ Galvanized Hood c/w screen
1 – 2‖ Aluminum Flex Duct –
1 – 2‖ Aluminum Flex Duct –
compressed 15‖ length, extends to 30‖ – 36‖
compressed 4’ length, extends to 120‖
2 – 2‖ Worm Gear Clamps
2 – 2‖ Worm Gear Clamps
NOTE:
Available from your local
Authorized Dealer or Hearth &
Home Technologies
1-877-427-3316