VISION SC600
Pag. 46
Rev. 02-18
USE AND MAINTENANCE MANUAL
23
– 24
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 9 / Partition 9 / Fan 9
25 - 26
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 8 / Partition 8 / Fan 8
Analog/digital inputs
PIN
TERMINAL
PROBE
TYPE
DESCRIPTION
27 (RH)
–
28 (V+)
4
–20 mA
Low pressure probe
(set jumper)
29 (RH)
–
30 (V+)
4-20 mA
High pressure probe
(set jumper)
31
– 32
digital
Digital input DI13
33
– 34
digital
Digital input DI14
35
– 36
digital
Digital input DI15
PIN
TERMINAL
DESCRIPTION
44
– 42
Output 0-10V inverter fans
44
– 41
Output 0-10V inverter compressor
Digital inputs
PIN
TERMINAL
DESCRIPTION
59
– 47
Digital input DI1
59
– 48
Digital input DI2
59
– 49
Digital input DI3
59
– 50
Digital input DI4
59
– 51
Digital input DI5
59
– 52
Digital input DI6
59
– 53
Digital input DI7
59
– 54
Digital input DI8
59
– 55
Digital input DI9
59
– 56
Digital input DI10
59
– 57
Digital input DI11
59 - 58
Digital input DI12
TeleNET
PIN
TERMINAL
DESCRIPTION
39
line A o terminal 3 of TWRS485
40
line B o terminal 4 of TWRS485
Attachments
To ensure correct reading by the pressure probes
you
need
the
right
hardware
jumpers
’
configuration on the 100N MASTER3 under the
removable front cover (see picture).
In particular the factory configuration is the
following:
J11=2-3, J12=1-2, J13=open
J21=2-3, J22=1-2, J23=open
J31=1-2, J32=2-3, J33=open
J41=1-2, J42=2-3, J43=open
J51=1-2, J52=2-3, J53=open
Attachments