VISION SC600
Pag. 22
Rev. 02-18
USE AND MAINTENANCE MANUAL
H1
Digital output 1 hour counter (resettable)*
0
999 tens of hours
Read only
H2
Digital output 2 hour counter (resettable)*
0
999 tens of hours
Read only
H3
Digital output 3 hour counter (resettable)*
0
999 tens of hours
Read only
H4
Digital output 4 hour counter (resettable)*
0
999 tens of hours
Read only
H5
Digital output 5 hour counter (resettable)*
0
999 tens of hours
Read only
H6
Digital output 6 hour counter (resettable)*
0
999 tens of hours
Read only
H7
Digital output 7 hour counter (resettable)*
0
999 tens of hours
Read only
H8
Digital output 8 hour counter (resettable)*
0
999 tens of hours
Read only
H9
Digital output 9 hour counter (resettable)*
0
999 tens of hours
Read only
H10
Digital output 10 hour counter (resettable)*
0
999 tens of hours
Read only
I1
Setting of digital input n.1
28 = Night mode digital input (energy saving) (N.O.)
27 = Remote Stand-by (N.O.)
26 = General low pressure alarm EL (N.O.)
25 = General high pressure alarm EH (N.O.)
24 = Freon level alarm (N.O.)
23 = Central alarm in manual mode (N.O.)
22 = Alarm display only - fans (con N.O.)
21 = Alarm display only - compress. (N.O.)
20 = Fan alarm n.10 (N.O.)
19 = Fan alarm n.9 (N.O.)
18 = Fan alarm n.8 (N.O.)
17 = Fan alarm n.7 (N.O.)
16 = Fan alarm n.6 (N.O.)
15 = Fan alarm n.5 (N.O.)
14 = Fan alarm n.4 (N.O.)
13 = Fan alarm n.3 (N.O.)
12 = Fan alarm n.2 (N.O.)
11 = Fan alarm n.1 (N.O.)
10 = Compressor alarm n.10 (N.O.)
9 = Compressor alarm n.9 (N.O.)
8 = Compressor alarm n.8 (N.O.)
7 = Compressor alarm n.7 (N.O.)
6 = Compressor alarm n.6 (N.O.)
5 = Compressor alarm n.5 (N.O.)
4 = Compressor alarm n.4 (N.O.
3 = Compressor alarm n.3 (N.O.)
2 = Compressor alarm n.2 (N.O.)
1 = Compressor alarm n.1 (N.O.)
0 = Disabled
-1 = Compressor alarm n.1 (N.C.)
-2 = Compressor alarm n.2 (N.C.)
-3 = Compressor alarm n.3 (N.C.)
-4 = Compressor alarm n.4 (N.C.)
-5 = Compressor alarm n.5 (N.C.)
-6 = Compressor alarm n.6 (N.C.)
-7 = Compressor alarm n.7 (N.C.)
-8 = Compressor alarm n.8 (N.C.)
-9 = Compressor alarm n.9 (N.C.)
-10 = Compressor alarm n.10 (N.C.)
-11 = Fan alarm n.1 (N.C.)
-12 = Fan alarm n.2 (N.C.)
-13 = Fan alarm n.3 (N.C.)
-14 = Fan alarm n.4 (N.C.)
-15 = Fan alarm n.5 (N.C.)
-16 = Fan alarm n.6 (N.C.)
-17 = Fan alarm n.7 (N.C.)
-18 = Fan alarm n.8 (N.C.)
-19 = Fan alarm n.9 (N.C.)
-20 = Fan alarm n.10 (N.C.)
-21 = Alarm display only - compress. (N.C.)
-22 = Alarm display only - fans (N.C.)
-23 = Central alarm in manual mode (N.C.)
-24 = Freon level alarm (N.C.)
-25 = General high pressure alarm EH (N.C.)
-26 = General low pressure alarm EL (N.C.)
-27 = Remote Stand-by (N.C.)
-28 = Night mode digital input (energy saving) (N.C.)
1
CHAP. 5 - Data programming