GENERALITY
The
VISION SC600
system allows users to control the machine room of a refrigeration
plant in which there is more than one compressor. It guarantees uniform operation and
proper distribution of operating times among individual machines. All functions are
performed in complete safety and the VISION SC600 Control Console (LCD DISPLAY)
can be installed anywhere, independently of where the power cabinet is located.
APPLICATIONS:
-
Compressor and condenser fan control of a refrigeration plant
MAIN FEATURES:
-
Configurable for control of compressors (up to a maximum of 10) and condenser fans
(up to a maximum of 10).
It’s possible to configure the outputs by setting the number of
compressors and fans to control, so that their sum is less than or equal to 10.
-
Configurable for compressor partition valves control.
-
0-10V Analog output for compressor inverter control.
-
0-10V Analog output for the adjustment of fan speed in alternative to digital outputs
control of the condenser fans.
-
Display of the pressure probe measure in Bar or in °C (conversion based on the type of
refrigerant gas selected).
-
Rotation of compressors / fans according to the time of operation.
-
Management compressors of different or the same powers.
-
Side band regulation.
-
Night / day management (energy saving).
-
Back-lit LCD display.
-
Clock and calendar.
-
Password for keys lock.
- RS485 Serial connection (Modbus-RTU or Telenet protocol).
- Pego programming philosophy that guarantees an immediate start-up.
1.1
CHAPTER 1: INTRODUCTION
CHAP. 1 - Introduction