WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
Motor Overload / Over Duty
OVERLOAD is ON solid when over current exists
at motor output
Check for shorts on motor line
Check for shorts to ground
Reset of overload is required; set parameter 01 to 01
and press ENTER to clear (must go to IND mode)
OVERLOAD is flashing when motor run time
exceeds duty
Let motor reset for 5 minutes
Over Duty does not require reset
•
◦
◦
•
•
◦
•
Input Indicators
1
HDO - Hall door open button
2
HDC - Hall door closed button
3
ZNS - Floor Zone switch
4
EUD - Emergency Unlocking Device
5
STOP - hall door stop button
6
AUX1 - Not Used
7
AUX2 - Not Used
8
RE - Hall door light curtain input
(where provided)
Door Stop Sign
Door Stop Sign is ON
whenever motors are not
running
Door Stop Sign is OFF
when power is being
applied to motors
•
•
Landing Zone
Zone is ON solid when
elevator is at a floor with
retiring cam extended and
door unlocked
Input indicator
3
ZNS is
ON when door is ZONED
Zone and
3
are OFF
when doors are locked
and / or car is moving
between floors
Doors will not run if
ZONE is not made
Check ZNS and zone
switch
•
•
•
•
•
Emergency Unlocking Device
EUD is ON solid when EUD is
SET at that floor
Input indicator
4
is ON when
EUD is SET at that floor
EUD is flashing when EUD is SET
at another floor
on same channel
Doors will not run if any EUD is
SET on the same channel
•
•
•
•
Radio Communication
Antenna is ON solid when elevator is at a floor and
door is ZONED
Antenna is ON solid when EUD is SET whether
door is ZONED or not
Antenna is OFF when elevator is not ZONED
For intermittent flashing in ZONE adjust channel
selection
•
•
•
•
Multiple Zone
MULTIZONE indicator is shown
when two or more landing door
controllers are ZONED on the same
channel
Check zone switches and ZNS inputs
at landings
•
•
Number Display
Number display show
encoder count (door
position)
Approximately 0-50
for landing door closed
position
Full count for open
position
May flash fault codes for
Peelle Use
•
•
•
•
7.5 LANDING DOOR LCD