WIRELESS CONTROLLER & BRIDGE
INSTALLATION & INTERFACE GUIDE
Mar 07 / 2018
ELEVATOR TO BRIDGE CONTROLLER INPUT CONNECTIONS CONTINUED
DO - Front Door Open
Momentary front signal required to open doors
DC - Front Door Close
Constant signal required to close doors
SE - Front Inspection
Constant signal required for front door operation
DCM - Front Door Close Momentary
Momentary signal required to initiate Auto Close sequence
RC - Retiring Cam
Input required to lift cam and move car. Signal should be low whenever car is stopped.
X11 - Fire Service Phase 1 Recall
Input required when Fire Service Phase 1 Recall is on.
X12 - Designated Landing Door
Input required when elevator is at designated landing
DOR - Rear Door Open
Momentary signal to open doors
DCR - Rear Door Close
Constant Signal required to close doors
INSR - Rear Inspection
Constant signal required for rear door operation
DCMR - Rear Door Close Momentary
Momentary signal required to initiate Auto Close sequence
X13 - Phase 2 “ON”
Constant signal required in phase 2 operation
X14 - Phase 2 “HOLD”
Constant signal required in phase 2 “HOLD” operation
X18 - Phase 2 “OFF”
Constant signal required in phase 2 “OFF” operation (until recall)
HDB - Hall Door Button Disable
Constant signal required to enable hall buttons
1
2
3
4
5
6
7
1
2
3
4
5
6
7
8